Trouble shooting 7
OUTDOOR UNIT Error Method:
Indicate or Display:
Detective Actuators:
Detective details:
Forecast of Cause :
OK
OK
OK
OK
4.8
15
6.0
7.6
9.6
16.1
21.0
27.8
Resistance value (k )
10
0
-5
-10
95.6
-30
50.3
-20
Temperature (
°C )
20
25
Outdoor Heat Exchanger Temperature
Thermistor Error
Outdoor unit Main PCB
Heat exchanger temperature thermistor
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
1. Connector connection failure 2. Thermistor failure 3. Inverter PCB failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
If Thermistor is either open or shorted, replace it and reset the power.
02-09
Refer to error code table.
12.4
5
Resistance value (k )
Temperature (
°C )
3.8
30
3.1
35
2.5
40
2.1
45
1.7
50
1.2
60
0.8
70
0.6
80
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
If the voltage does not appear, replace Main PCB.