- (02 - 08) -
O
U
TD
O
O
R U
N
IT
AO
G
09
-1
2LT
O
U
TD
O
O
R U
N
IT
AO
G
09
-1
2LT
MODEL
: AO
G12LT
Height difference H
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
15
-
-
-
0.956
0.938
10
-
-
1.004
0.956
0.938
7.5
-
1.013
1.004
0.956
0.938
5
1.000
1.013
1.004
0.956
0.938
0
1.000
1.013
1.004
0.956
0.938
Û
2
Indoor unit is
under than
outdoor unit
-5
0.995
1.008
0.999
0.951
0.933
-7.5
-
1.005
0.997
0.948
0.931
-10
-
-
0.994
0.946
0.929
-15
-
-
-
0.937
0.919
COOLING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
upper than
outdoor unit.
15
-
-
-
0.893
0.909
10
-
-
0.955
0.908
0.924
7.5
-
0.975
0.959
0.912
0.928
5
0.992
0.979
0.963
0.916
0.931
0
1.000
0.987
0.970
0.923
0.939
Û
2
Indoor unit is
under than
outdoor unit
-5
1.000
0.987
0.970
0.923
0.939
-7.5
-
0.987
0.970
0.923
0.939
-10
-
-
0.970
0.923
0.939
-15
-
-
-
0.923
0.939
Summary of Contents for AO*G09LTC
Page 2: ...1 INDOOR UNIT WALL MOUNTED TYPE AS G09LTCA AS G12LTCA DTR_AS054E_03 2011 11 14 ...
Page 10: ... 01 07 WALL MOUNTED TYPE AS G09 12LT WALL MOUNTED TYPE AS G09 12LT INSTALLATION PLACE Unit mm ...
Page 31: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LTC AO G12LTC DTR_AO086E_01 2011 04 08 ...
Page 37: ... 02 05 OUTDOOR UNIT AO G09 12LT OUTDOOR UNIT AO G09 12LT WIRING DIAGRAMS 444 MODEL AO G09LT ...
Page 38: ... 02 06 OUTDOOR UNIT AO G09 12LT OUTDOOR UNIT AO G09 12LT MODEL AO G12LT ...
Page 44: ... 02 12 OUTDOOR UNIT AO G09 12LT OUTDOOR UNIT AO G09 12LT SOUND LEVEL CHECK POINT 88888 ...