background image

En-7

1

6.1. Electrical requirement

Voltage rating

208 / 230 V

Operating range

187 to 253 V

•  Select the power cable type and size in accordance with relevant local and national 

regulations.

•  Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with local 

code.

• Select the correct cable type and size according to the country or region’s regulations.
•  Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform 

the power crossover wiring within the range of the same refrigerant system. When the 
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B 
below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR (Fuse capacity)

ARUH36TLAV

2.70 A

15 A

ARUH48TLAV

4.83 A

ARUH60TLAV

4.83 A

MCA: Minimum Circuit Ampacity
MAX. CKT. BKR : Maximum Circuit Breaker
When the power crossover wiring is done, make it so that the total of the MCA of the 
connected RB units and indoor units does not exceed the 11 A. For RB unit MCA, refer to 
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add 
breakers or use a breaker with a greater capacity.

B. Ground Fault Equipment Breaker requirements

Breaker capacity

* Maximum connectable

“indoor units” or “indoor units + RB units”

30 mA, 0.1 sec or less

36 or less **

100 mA, 0.1 sec or less

37 to 90

* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
** If the total number of units connected to the breaker exceeds 36, either add a 30mA 
breaker, or use breakers with a greater capacity.

6.1.1. Transmission and remote controller wiring speci

fi

 cations

Follow the speci

fi

 cations below for the transmission and remote controller cable.

Cable size

Wire type

Remarks

Transmission cable

22 AWG 

(0.33 mm²)

LEVEL 4 (NEMA) non-

polar 2core, twisted 

pair solid core diam-

eter 0.026 in. (0.65mm)

LONWORKS ® 

compatible cable

Remote controller cable

(2-wire type)

22 AWG to 16 AWG

(0.33 to 1.25 mm²)

Sheathed PVC cable

Non polar 2 core

Remote controller cable

(3-wire type)

22 AWG

(0.33 mm²)

Sheathed PVC cable

Polar 3 core 
Twisted pair

]1

6.2. Wiring method

EXAMPLE

Outdoor unit or RB unit *1

Breaker 1:  Ground Fault Equipment 

Breaker (GFEB)

Breaker 2:  Maximum Circuit Breaker 

(MAX. CKT. BKR)

Transmission

Transmission
Power supply

Breaker2

Breaker2

Breaker2

Breaker1

Breaker1

Breaker1

Power supply

Remote controller 

(Master)

Breaker shall be located in sight from and readily accessible from all indoor units.
*1:  When connecting to the Heat Recovery System, refer to the installation manual of 

the RB unit.

*2: When connecting the 2-wire type remote controller, Y3 is not used.

Remote controller 

(Slave)

Remote controller 

Indoor unit

Remote 

control

*2

*2

*2

Indoor unit

Indoor unit

(Crossover wiring of power supply)

Breaker2

Breaker1

Indoor unit

Power supply

Pull box

Pull box

Power supply

: Disconnect switch

Power supply

Power supply

Indoor unit

Indoor unit

Disconnect switch shall be installed between indoor unit and pull box.

]1

6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring 

fi

 gure 

below.
Power supply cable

Earth (Ground) 
wire

Conduit connector

2-3/8 in. (60mm)

2-3/4 in. (70mm)

A. For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable.

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Strip 1 in.
(25 mm)

Screw with 
special washer

Terminal block

Cable end (Loop)

Cable end (Loop)

Loop

Screw with 
special washer

Cable

Cable

 WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 
cables with the ring terminal, the ring terminal’s pressure bonding may malfunction 
and cause the cables to abnormally heat up.

B. For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a 

screwdriver that is too small, otherwise, the screw heads may be damaged and 
prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

9373870135-03_IM.indb   Sec1:7

9373870135-03_IM.indb   Sec1:7

10/24/2013   2:57:14 PM

10/24/2013   2:57:14 PM

Summary of Contents for Airstage VR-II ARUH36TLAV

Page 1: ...0135 03 ARUH36TLAV ARUH48TLAV ARUH60TLAV MANUEL D INSTALLATION MANUAL DE INSTALACIÓN APPAREIL INTÉRIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9373870135 03_IM indb 1 9373870135 03_IM indb 1 10 24 2013 2 57 02 PM 10 24 2013 2 57 02 PM ...

Page 2: ... added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow ...

Page 3: ...nd thoroughly ventilate the area If the refrigerant comes in contact with a flame it produces a toxic gas 1 2 2 Special tool for R410A WARNING To install a unit that uses R410A refrigerant use dedicated tools and piping materials that have been manufactured specifically for R410A use Because the pressure of R410A refrigerant is approximately 1 6 times higher than the R22 failure to use dedicated p...

Page 4: ...tall the unit near a source of heat steam or flammable gas Install the unit where drainage does not cause any trouble Install the indoor unit power supply cable transmission cable and remote controller cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you...

Page 5: ...after a prolonged period causing refrigerant to leak and generate a hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attach...

Page 6: ...before connecting the connection pipe Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Flare nut in mm Tightening torque lbf ft N m 1 4 6 35 dia 11 8 to 13 3 16 to 18 3 8 9 52 dia 23 6 to 31 0 32 to 42 1 2 12 70 dia 36 1 to 45 0 49 to 61 5 8 15 88 dia 46 5 to 55 3 63 to 75 3 4 19 05 dia 66 4 to 81 1 90 to 110 4 4 ...

Page 7: ...e outdoor unit or RB unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the i...

Page 8: ... be located in sight from and readily accessible from all indoor units 1 When connecting to the Heat Recovery System refer to the installation manual of the RB unit 2 When connecting the 2 wire type remote controller Y3 is not used Remote controller Slave Remote controller Indoor unit Remote control 2 2 2 Indoor unit Indoor unit Crossover wiring of power supply Breaker2 Breaker1 Indoor unit Power ...

Page 9: ...ich will lead to a communication failure 1 6 4 Connection of wiring 1 Remove the control box cover and install each connection cable Loosen the screws 2 locations Cover box 2 After wiring is complete clamp the remote controller cable transmission cable and power supply cable with cable tie CAUTION When switching the DIP switch SW1 be sure to turn off the power supply to the indoor unit Otherwise t...

Page 10: ...s DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected unit be sure to make a branch outside the indoor unit using a pull box etc as shown on below example DC power supply 12 to 24V connected unit Load resistance P C B P ...

Page 11: ...ible current 50mA Output select When indicator etc are connected directly Indicator 1 Indicator 2 Indicator 3 Indicator 4 connected unit P C B CNB 01 When connecting with unit equipped with a power supply CNB 01 P C B Connected device 1 Connected device 2 Connected device 3 Connected device 4 Relay Field supply Operation behavior If function setting 60 is set to 00 Connector Output voltage Status ...

Page 12: ...ceiver unit Optional parts For the installation method please refer to the INSTALLATION MANUAL of IR receiver unit Connection methods Connection terminals Controller PCB IR receiver unit terminal CN18 Wiring arrangement Core Controller PCB Cable clamp Cable tie Field supply 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting...

Page 13: ... 0 5 5 0 5 6 0 6 6 0 6 7 0 7 7 0 7 8 0 8 8 0 8 9 0 9 9 0 9 10 1 0 10 0 0 11 1 1 11 1 1 12 1 2 12 1 2 99 9 9 63 6 3 Do not set the indoor unit address IU AD SW at 64 to 99 It may result in failure 3 Remote controller address i 3 wire type Rotary switch RC AD SW Factory setting 0 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD SW in sequence from ...

Page 14: ...tputs terminals 60 00 Mode 0 Set this function when connecting the VRF system to a ventilator economizer humidifier or other external device The connection terminal functions can be changed depending on the type of external device For details of the connection terminal func tions see the Design Technical Manual 01 Mode 1 02 Mode 2 03 Mode 3 04 Mode 4 05 Mode 5 06 Mode 6 07 Mode 7 08 Mode 8 Control...

Page 15: ...door unit main PCB error 3 10 Indoor unit communication circuit wired remote controller error 4 1 Indoor unit room temp thermistor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 13 1 RB unit error Indicator mode 0 5s ON 0 5s OFF 0 1s ON 0 1s O...

Reviews: