Turn the power off and on or press SW7 (reset button) 

7. 

to exit from address setting mode.  

This time, please refer to the “7. TURNING ON THE 

POWER” for the content displayed in D19 LED.

INITIAL SETTING (SOFTWARE)

91 

The initial settings for the Network Convertor must be per-

formed before the commissioning. Please see the attached 

“Application Manual - Tool for Network Convertor” and 

complete the settings.

BINDING & COMMISSIONING (NOTICE)

101 

It is necessary to make an XIF (External Interface 

(1) 

File) for binding.

The commissioning doesn’t end if the number of 

(2) 

Indoor/Outdoor Unit of the XIF file made with Tool 

of Network Convertor is not in consistency with 

the number after Indoor/Outdoor Unit Address is 

registered.

In addition, the Network Convertor can not oper-

ate normally if the number of Indoor/Outdoor Unit 

of the XIF file is not in consistency with the num

-

ber after Indoor/Outdoor Unit Address is regis-

tered.

Binding and commissioning must be performed 

(3) 

again if the number of connecting units (indoor/

outdoor units) has changed after system op-

eration. Please always register the allocation 

information that is in consistency with the VRF 

system, Functional Block in the Network Con-

vertor and the Network Convertor, if register the 

changed XIF file in according to the “Tool for 

Network Convertor”.

Important:

Network Convertor will not operate if,

VRF network system address (Indoor & Outdoor units ad-

 

dress) allocation information are not registered to Net-

work Convertor.

XIF data information and VRF network system address 

 

allocation information must not be same.

Binding & Commissioning is not executed.

 

The ID number registered on Network Convertor is differ-

 

ent from the ID number when XIF file is created.

Two or more Network Convertors are connected to BMS, 

 

and these are set the same ID number.

LED DISPLAY (D19)

111 

(1) Normal code

Normal code

Contents

Normal mode

Set state of “Tool for Network Con-

vertor”

Address setting mode

Under maintenance

FB and unit address allocation 

information is registered with 

“Tool for Network Convertor”

FB* : Functional Blocks

(2) Error code

Error code

Contents

FB and unit address allocation 

information is not registered

Main PCB error

VRF Network error

D9 LED lit or blinking

D9

D9

Communication error 

(Error of the Network Interface De-

vice on VRF System)

D14 LED lit or blinking

D14

D14

Communication error 

(Error of the Network Interface De-

vice on BMS)*1
When V series or S series is con-

nected

D14 is ON for 1 second, OFF for 1 second, and repeats. When 

*1. 

D19 is in Normal mode, Commissioning is unset. 

Summary of Contents for Airstage UTY-VLGX

Page 1: ...ANUAL DE INSTALAÇÃO For authorized service personnel only 只适用于专业维修人员 Uniquement réservé aux techniciens agréés Sólo para personal de mantenimiento autorizado Apenas para técnicos de assistência autorizados PART NO 9708436029 NETWORK CONVERTOR CONVERSOR DE REDE CONVERTIDOR DE RED ADAPTATEUR RESEAU 网络转换器 UTY VLGX ...

Page 2: ...such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Do not use the unit for special purposes such as storing food raising animals growing plants or preserving pre cision devices or art objects It can degrade the quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sunlight Do not operate this uni...

Page 3: ...d the transmis sion cable together with or parallel to the power supply cable of the indoor and outdoor units It may cause er roneous operation When performing wiring work be careful not to damage the cable or injure yourself Also connect the connectors securely Loose connectors will cause trouble heating fire or electric shock Install the indoor and outdoor units power supply cable transmission c...

Page 4: ...cable The shield metal should be earthed grounded Do not forget to earth ground the Network Convertor Install the disconnect switch to the easily accessible loca tion Install the fuse 3A to the L line of power supply cable Confirm the name of each unit and name of each terminal block of the unit and connect the wiring in accordance with the directions given in the manual so that there is no incorr...

Page 5: ...arth Ground Cable Binder Binder Lock nut Cut for Others Remove the 4 screws M4 6 mm and then remove the cover Open the knockout hole and then install dust proof bushing If small animals such as insects and dust enter this unit a short circuit may be caused Make a hole in the center of the dust proof bush ing with the Phillips head screwdriver Pass the power supply cable through the hole of dust pr...

Page 6: ...l for Network Convertor D14 D14 Binding and Commissioning is not executed Normal Mode Ready for operation Others Refer to 11 LED DISPLAY D19 for more detail Network Convertor does not operate during initialization If an error occurs the D9 or D14 LED lights or flashes or the error code is displayed on the right side of the D19 LED display ADDRESS SETTING 888 Setting up more than 1 Network Converto...

Page 7: ...ock in the Network Con vertor and the Network Convertor if register the changed XIF file in according to the Tool for Network Convertor Important Network Convertor will not operate if VRF network system address Indoor Outdoor units ad dress allocation information are not registered to Net work Convertor XIF data information and VRF network system address allocation information must not be same Bin...

Reviews: