En-8
3.
The “Maintenance” screen is displayed. Touch [Next Page] or
[Previous Page] to switch between screens.
(Items that indoor unit does not support are not displayed.)
Back
Next
Page
Page 1/ 3
Maintenance
Error History
Setting
Status List
Version
Filter Sign
Reset
Previous
Page
Back
Next
Page
Page 2/ 3
Maintenance
Test Run
R.C. Address
Setting
Function Setting
I.U. Address
Verification
Back
Previous
Page
Page 3/ 3
Maintenance
Initialization
Installer Password
Change
6.4.1. Error History
1.
Touch the [Error History] on the “Maintenance” screen. The “Error
History” screen is displayed.
If there are 7 or more errors, you can switch between pages by
touching [Next Page] or [Previous Page] Up to a maximum of 32 er-
rors can be saved. Once there are more than 32 errors, the oldest
one will be deleted.
Touch [Back] to return to the “Maintenance” screen.
2.
To delete the error history, touch [Erase All] and then [Yes] on the
con
fi
rmation screen.
1.
2.
11:00
2:53
8:53
11:00
11:00
11:00
1
2015/ 8/ 1
002-01
141
2
2015/ 7/30
002-02
143
3
2015/ 7/25
002-02
143
4
2015/ 7/22
002-01
141
5
2015/ 7/22
002-01
141
6
2015/ 7/21
002-01
141
Page 1/ 2
Error History
No. Date
Time
Address
Code
Back
Next
Page
Erase
All
AM
AM
AM
AM
AM
AM
Delete entire error history?
Error History
No
Yes
6.4.2. Setting Status List
1.
Touch the [Setting Status List] on the
“Maintenance” screen. The “Setting Status
List” screen is displayed.
Touch [Next Page] or [Previous Page] to
switch between screens.
Touch [Back] to return to the “Maintenance”
screen.
On Timer
– Operation Start Time
Off Timer
– Operation Stop Time
Auto Off Timer
– Operation Stop Time
– Time Range
[Disable]
[0.5hr]
[Disable]
[0.5hr]
[Disable]
[30min.]
[ – ]
Back
Next
Page
Page 1/ 5
Setting Status List
6.4.3. Filter Sign Reset
1.
Touch the [Filter Sign Reset] on the
“Maintenance” screen. The “Filter Sign
Reset” screen is displayed.
Touch [OK] to reset the
fi
lter sign, and
return to the “Maintenance” screen.
Cancel
OK
Filter Sign Reset
The filter sign will be reset. OK?
6.4.4. Version
1.
Touch the [Version] on the “Maintenance”
screen. The “Version” screen is displayed.
Touch [Back] to return to the “Maintenance”
screen.
E000V00P00L00
Version
Back
6.4.5. Test Run
Carry out a test run after completing con
fi
guration.
1.
Touch the [Test Run] on the “Maintenance”
screen. The “Test Run” screen is
displayed.
Touch [OK] to return to the “Maintenance”
screen, and start the test run. The test run
will automatically end in approximately 60
min.
Cancel
OK
Test Run
The test run will be performed. OK?
If you wish to cancel the test run before it is complete, return to the
“Monitor Mode screen”, and touch the On/Off button.
6.4.6. R.C. Address Setting
Addresses will be automatically set when initially starting up this unit. In
such a case, do not change the remote controller address for the indoor
unit, and keep it at the initial setting of 0.
• Checking the remote controller address
1.
Touch the [R.C. Address Setting] on the
“Maintenance” screen. The “R.C. Address
Setting” screen is displayed.
The “Current Address” is displayed as
[System-Unit]. The value for “Unit” refers
to the remote controller address.
[001–01]
R.C.Address Setting
Current Address
Back
Manual Addressing
Address Reset
Touch [Back] to return to the “Maintenance” screen.
When the address is set manually, this mark
is displayed.
• Manual Address Setting
Only set addresses manually when using different numbers for
addresses.
A remote-controller address for the indoor unit needs to be set.
Set the remote-control addresses for the indoor units which are
connected using the same remote-control cable with a range from 1 to
9 and from A (10) to F(15), without any duplicates. (Do not use “0” for
con
fi
guration.)
For how to con
fi
gure the remote control addresses for the indoor unit,
refer to its installation manual.
1.
Touch the [RC Address Setting] on the “Maintenance” screen. The
“R.C. Address Setting” screen is displayed.
Touch the [Manual Addressing]. The “Manual Addressing” screen is
displayed.
2.
Touch [ ] or [ ] to set the addresses of this unit. Touch [OK] to
display the con
fi
rmation screen, and touch [Yes] to return to the RC
Address setting screen.
If you wish to carry out con
fi
guration again, touch [Address Reset] on
the “R.C. Address Setting”.
1.
2.
[001–01]
R.C.Address Setting
Current Address
Back
Manual Addressing
Address Reset
01
001
Manual Addressing
Cancel
OK
System
Unit
The address for this unit can be set from 1 to 32. However, do not set
the same number as that for the remote-control address of an indoor
unit connected using the same remote-control cable.
6.4.7. I.U. Address Veri
fi
cation
Check the address and position of the indoor unit.
1.
Touch the [I.U. Address Veri
fi
cation] on the “Maintenance” screen.
The “I.U. Address Veri
fi
cation” screen is displayed.
If there are multiple pages, you can switch between them by
touching [Next Page] or [Previous Page].
Touch [Check] to display the indoor unit address checking start
screen.
2.
Touch [Yes] to display the con
fi
rmation screen.
3.
Select the indoor unit to be checked. If there are multiple pages,
you can switch between them by touching [Next Page] or [Previous
Page]. The selected indoor unit will start to blow air and
fl
ash a
LED*. (*Only when the indoor unit has the relevant functions)
Touch [Back] on the con
fi
rmation screen to return to the previous
screen.
1.
2.
3.
1 002–01
01–01
/
002–02
01–02
/
2
002–03
01–03
/
3
002–04
01–04
/
4
002–05
01–05
/
5
002–06
01–06
/
6
/
Page 1/ 2
I.U. Address Verification
No. System–Unit
Ref.–In.
Back
Check
Next
Page
No
Yes
I.U. Address Verification
Indoor unit position will be checked. OK?
1 002–01
01–01
/
2 002–02
01–02
/
3 002–03
01–03
/
/
End
Next
Page
Page 1/ 2
I.U. Address Verification
No.
System–Unit
Ref.–In.
4.
Touch [Back] on the “IU Address
Veri
fi
cation” Screen to return to the
“Maintenance” Screen.
1 002–01
01–01
/
002–02
01–02
/
2
002–03
01–03
/
3
002–04
01–04
/
4
002–05
01–05
/
5
002–06
01–06
/
6
/
Page 1/ 2
I.U. Address Verification
No. System–Unit
Ref.–In.
Back
Check
Next
Page