Fujitsu Airstage UTY-RNRYZ3 Installation Manual Download Page 2

En-2

4.  SELECTING AN INSTALLATION 

LOCATION

4.1.  Dimensions and Name of parts

Remote controller unit

Unit: mm (in)

Hole: 9 × 4.5

(3/8 × 3/16)

Hole: 6 × 4.5

(1/4 × 3/16)

Hole: 12.5 × 4.5

(1/2 × 3/16)

20.4 (13/16)

(a) (b) (c) (d)

120 (4-3/4)

30 (1-3/16) 33 (1-5/16)

23

(7/8)

15

.3

 (

5

/8

)

83

.5

 (

3

-5

/1

6)

12

0 (

4

-4

/3

)

45

.3

 (1

-1

3/

16

)

63

.5

 (

2-

1/2

)

(a)  Room temperature sensor (inside)
(b) On/Off button:

It is possible to operate only while displaying the Monitor Mode screen.

(c)  LED lamp (Operation indicator)
(d)  Touch panel display

Monitor mode screen

The home screen of this unit. Ex-
cept for in the following cases, the 
screen will return to this screen 
if there is no operation for over 
10 min. (Unsaved settings will be 
cancelled.)
• In Emergency Stop.
• In Transferring data.
• In checking the indoor unit 

position

• In Function Setting

26.0

26.0

°C

°C

Cool

Auto

Office

Set Temp.

26.0°C

26.0°C

Mode

Menu

Status

Fan

Fri 10:00AM

Room Temp.

(a)

(d)
(e)

(f)

(g)
(h)

(i)

(b)

(d)
(c)

(d)

(a)  Set Temp.: Set the operating temperature. Refer to operating manual.
(b)  R.C. Group name: Refer to 6.3.4.
(c)  Mode: Set the operation mode. Refer to operating manual.
(d)  Status icons: Refer to operating manual.
(e)  Clock: Refer to 6.2.4.
(f)  Fan: Set the fun speed. Refer to operating manual.
(g)  Room Temp.: Refer to 4.2. and 6.3.5.
(h)  Menu: Set the various settings.
(i)  Status: Check the status of indoor unit and error.

For the screen display other than Chinese, this product uses a Bitmap font 
made and developed by Ricoh Company, Ltd.

4.2.  Setting the room temperature detection 

location

 CAUTION

As the temperature sensor of remote controller detects the temperature 
near the wall, when there is a certain difference between the room 
temperature and the wall temperature, the sensor will not detect the 
room temperature correctly sometimes. Especially when the outer side 
of the wall on which the sensor is positioned is exposed to the open air, 
it is recommended to use the temperature sensor of the indoor unit to 
detect the room temperature when the indoor and outdoor temperature 
difference is signi

fi

 cant.

The detection location of the room tempera-
ture can be selected from the following 2 
methods. The temperature sensor of the 
indoor unit or the remote controller can be 
used to detect the room temperature.
Choose the detection location that is best for 
the installation location.

A sensor of the indoor 

unit (inside)

A sensor of the remote 

controller (inside)

If using the remote control sensor, setting is required. 

Refer to 6.3.5. 

RC (Remote Controller) Sensor Setting.

4.3. Installation space

• Do not embed this remote controller in a wall.
• Recommendation installation height of the remote controller is 1.4 m (55 

in) (from the 

fl

 oor surface to the bottom of the remote controller).

• Even when you install a remote controller to one of a switch box and the 

surface of a wall, secure the space shown in following 

fi

 gure. When there 

is insuf

fi

 cient space, there may be remote controller sensor misdetec-

tions and remote controller removal may be dif

fi

 cult.

30 (2) or 

more

Unit: mm (in)

220 (9) 

or more*

30 (2) 

or more

30 (2) 

or more

* Please secure enough space where a 

fl

 at-blade screwdriver to take off a 

case can be inserted.

5.  

INSTALLING THE REMOTE 

CONTROLLER

 WARNING

Always use the accessories and speci

fi

 ed installation work parts. Check 

the state of the installation parts. Not using the speci

fi

 ed parts will cause 

units to fall off, water leakage, electric shock, 

fi

 re, etc.

Install at a place that can withstand the weight of the unit and install 

fi

 rmly so that the unit will not topple or fall.

When installing this unit, make sure that there are no children nearby. 
Otherwise, injury or electric shock could result.

Before starting installation work, turn off the power of this unit and the 
connection destination. Do not turn on the power again until installation 
is completed. Otherwise, it will cause electric shock or 

fi

 re.

Use the accessories or speci

fi

 ed connection cables. Do not modify con-

nection cables other than those speci

fi

 ed, do not use extension cords, 

and do not use independent branch wiring. The allowable current will be 
exceeded and cause electric shock or 

fi

 re.

Install the remote controller cables securely to the terminal block. Con-

fi

 rm that external force is not applied to the cable. Use remote controller 

cables made of the speci

fi

 ed wire. If intermediate connection or inser-

tion 

fi

 xing are imperfect, it will cause electric shock, 

fi

 re, etc.

When connecting the remote controller cable, route the cables so that 
the rear case of this unit is securely 

fi

 xed. If the rear case is imperfectly 

fi

 xed, it may cause 

fi

 re or overheating of the terminals.

Perform functional earthing work positively. Do not connect the func-
tional earthing wire to a telephone earth (Ground) wire, water pipe, or 
conductor rod.

Always fasten the cable sheath of the connection cable with the cable 
tie. If the cable sheath is chafed, electric discharge may occur.

Summary of Contents for Airstage UTY-RNRYZ3

Page 1: ...328445 For authorized service personnel only Original instructions Installation by endusers or not qualified persons can cause harm to personal safety can cause severe damage to building and product can lead to improper function or reduced lifetime of the equipment Do not install the unit in the following areas Do not install the unit near a source of heat steam or flammable gas Otherwise fire cou...

Page 2: ...remote controller inside If using the remote control sensor setting is required Refer to 6 3 5 RC Remote Controller Sensor Setting 4 3 Installation space Do not embed this remote controller in a wall Recommendation installation height of the remote controller is 1 4 m 55 in from the floor surface to the bottom of the remote controller Even when you install a remote controller to one of a switch bo...

Page 3: ...mbine 3 Wired type with 2 Wired Type When there is a functional earthing Indoor unit Remote controller Remote controller Group control and multiple remote control can be used together 5 2 Preparing for Installation 5 2 1 Strip of the remote controller cable Sheathed cable A 7 mm 1 4 in B 7 mm 1 4 in C 25 mm 1 in Functional earthing Shielded cable A A B B C 5 2 2 Remove the front case When opening ...

Page 4: ...te controller cable to the indoor unit One is the connection using connecting cable Included in the indoor unit and the other is the connection the remote controller cable is con nected to the exclusive terminal block of the indoor unit For the details refer to the installation manual of the indoor unit to be used 5 4 1 When connecting to the connector 1 Use a tool to cut off the terminal on the e...

Page 5: ... and Time Setting screen The Time screen is displayed 1 2 3 Date and Time Setting Date 01 01 2015 Time 12 00 AM Thu 12 00AM Cancel OK Date Format Day Month Year Time Format 12 00 11 59AM PM Summer Time Setting Disable 2015 01 01 Thu 12 00AM Date Cancel OK Year Month Day Date and Time Setting Date 01 01 2015 Time 12 00 AM Thu 12 00AM Cancel OK Date Format Day Month Year Time Format 12 00 11 59AM PM...

Page 6: ...t Day Month Year 12 00 11 59AM PM Month Dat Year Year Month Day Date Format Cancel OK Day Month Year Fri 10 00AM Display Format Setting Cancel OK Fri 10 00AM Date Format Time Format Day Month Year 12 00 11 59AM PM 4 Select and touch the data display format Touch OK on the Time Format to return to the Display Format Setting screen 5 Touch OK on the Display Format Setting screen to return to the Dat...

Page 7: ...r Sign Visible Display Item Setting Cancel OK Room Temp Visible 6 3 9 RC Master Slave Setting If multiple remote controllers are set for a remote control group or for a single indoor unit it is necessary to set the remote controller master This setting will be required at the time of initial start up during installa tion However this setting can be changed afterwards No master remote controllers w...

Page 8: ...te controller address 1 Touch the R C Address Setting on the Maintenance screen The R C Address Setting screen is displayed The Current Address is displayed as System Unit The value for Unit refers to the remote controller address 001 01 R C Address Setting Current Address Back Manual Addressing Address Reset Touch Back to return to the Maintenance screen When the address is set manually this mark...

Page 9: ...gits 2 The Installer Password Change screen is displayed Enter the new password then touch the OK It returns to the Maintenance screen 1 2 0 0 CL 5 1 6 2 7 3 8 4 9 Cancel OK Installer Password Verification Enter Current Password 0 CL 5 1 6 2 7 3 8 4 9 Cancel OK Installer Password Change Enter New Password 6 4 10 Initialization Require an Installer password 1 Touch the Initialization on the Main te...

Reviews: