En-8

7.2. Electrical requirement

Voltage rating

208/230 V

Operating range

187 to 253 V

• Select the power cable type and size in accordance with relevant local and national 

regulations.

• Speci

fi

 cations for local wiring power cord and branch wiring are in compliance with 

local code.

• Select the correct cable type and size according to the country or region’s regulations.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the 

wire diameter when the wire length is long.

Breaker should be installed at every refrigerant system. Do not use a breaker in a 
different refrigerant system.
Refer to the table for the breaker speci

fi

 cations of each installation condition. Perform the 

power crossover wiring within the range of the same refrigerant system. When the crossover 
wiring is done, make a connection for RB units to satisfy conditions A and B below.

A. Current breaker requirements

Model

MCA

MAX. CKT. BKR (Fuse capacity)

UTP-RU01AH

0.25 A

15 A

UTP-RU01BH

0.25 A

UTP-RU01CH

0.38 A

MCA: Minimum Circuit Ampacity
MAX. CKT. BKR : Maximum Circuit Breaker

When the power crossover wiring is done, make it so that the total of the MCA of the 
connected RB units and indoor units does not exceed the 11 A. For indoor unit MCA, 
refer to the indoor unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either 
add breakers or use a breaker with a greater capacity.

B. Ground Fault Equipment Breaker requirements

Breaker capacity

Connectable RB units and indoor units

30 mA, 0.1 sec or less

36 or less *

100 mA, 0.1 sec or less

37 to 121

*  If the total number of units connected to the breaker exceeds 36, either add a 30mA 

breaker, or use breakers with a greater capacity.

7.2.1. Cable speci

fi

 cations

Follow the speci

fi

 cations below for the power supply and transmission cable.

Recommended 

cable size (mm

2

)

Cable type

Remark

Transmission 
cable

22 AWG 

(0.33 mm²)

LONWORKS 
compatible cable

22 AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted 
pair solid core diameter 
0.026 in (0.65 mm)

7.3. Wiring

• Before attaching the cable to terminal block.

7.3.1. Power supply cable

Conduit connector

Earth (ground) wire

4-5/16 in (110 mm)

4-15/16 in (125 mm)

A.  For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after 

looping it around the end of the cable. 

(2)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is 

no stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. 
 

Do not use a screwdriver that is too small, otherwise, the screw heads may be 
damaged and prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Strip 1 in 
(25 mm)

Screw with 
special washer

Screw with 
special washer

Cable end (Loop)

Cable end (Loop)

Terminal block

Cable

Loop

Cable

Do not apply branch wiring. It may result electric shock or 

fi

 re.

 

WARNING

When using solid core cables, do not use the ring terminal. If you use the solid 
core cables with the ring terminal, the ring terminal's pressure bonding may 
malfunction and cause the cables to abnormally heat up.

B.  For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the 

fi

 gure below to connect 

to the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that 

the cables do not come loose.

(3)  Use the speci

fi

 ed cables, connect them securely, and fasten them so that there is 

no stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws.

 

Do not use a screwdriver that is too small, otherwise, the screw heads may be 
damaged and prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  See the table for the terminal screw tightening torques.

(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

Screw with 
special washer

Screw with 
special washer

Terminal block

Cable

Cable

Ring terminal

Ring terminal

 Sleeve

Strip 3/8 in
(10 mm)

Ring terminal

 WARNING

Use ring terminals and tighten the terminal screws to the specified torques, 
otherwise, abnormal overheating may be produced and possibly cause heavy 
damage inside the unit.

Tightening torque

M4 screw 
(Power supply / L1, L2 (N), GND)

11 to 16 lbf·in

(1.2 to 1.8 N·m)

7.3.2. Transmission cable

Shielded wire 

(no 

fi

 lm)

1-9/16 in (40 mm)

1-3/16 in (30 mm)

• When the 2 cables are attached:

GOOD

PROHIBITED

Different diameter

Connect to 1 side

 WARNING

Tighten the terminal screws to the specified torques, otherwise, abnormal 
overheating may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3 screw 
(Transmission / X1, X2) 

4 to 5 lbf·in

(0.5 to 0.6 N·m)

 CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by 
overtightening the screw. On the other hand, an under tightened screw can cause 
faulty contact, which will lead to a communication failure.

9366249030-05_IM.indb   Sec1:8

9366249030-05_IM.indb   Sec1:8

2015/2/26   13:11:33

2015/2/26   13:11:33

Summary of Contents for Airstage UTP-RU01AH

Page 1: ...tage Parts for the Fujitsu LonWorks cables are the following Cable Type Pairs Details Catalog Number Level 4 NEMA 22AWG 1 250ft LonWorks Shielded cable K00250LW 1 500ft LonWorks Shielded cable K00500LW This addendum information shall supersede any LonWorks cable requirements listed in any of the Airstage Design Technical Manuals or Installation Manuals Design Technical Manual for Airstage V II 208...

Page 2: ...service personnel only TM Français Español MANUEL D INSTALLATION MANUAL DE INSTALACIÓN UNITÉ DE DÉRIVATION DE RÉFRIGÉRANT UNIDAD DE DERIVACIÓN DE REFRIGERANTE Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado UTP RU01AH UTP RU01BH UTP RU01CH ...

Page 3: ... and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle In a Snowy Area for Heat Pump type Systems Install the outdoor unit on a raised platform that is higher than drifting snow When Connecting Refrigerant Tubing Keep all tubing runs as short as possible Use the flare method for connecting tubing Apply refrigerant lub...

Page 4: ...t breaker operating on all wires with a distance between contact of 1 8 in 3 mm for this unit The unit must be correctly grounded and the supply line must be equipped with a dif ferential breaker in order to protect the persons The units are not explosion proof and therefore should not be installed in explosive atmosphere Do not turn on the power until all installation work is complete This unit c...

Page 5: ...nstallation manual 5 INSTALLATION WORK 5 1 Selecting an installation location WARNING Take into consideration whether the place you install the main unit can fully with stand its weight For hanger bolts use embedded inserts or embedded foundation bolts in the case of new installation and use a hole in anchor if already installed and attach in a way so that the unit s weight can be supported CAUTIO...

Page 6: ...unit side Product mass lbs kg UTP RU01AH 15 7 UTP RU01BH 17 7 5 UTP RU01CH 18 8 A A B B C C 20 500 or more 20 500 or more 1 20 or more 1 20 or more Ceiling hanging Installation limit Unit in mm 5 2 2 Wall hanging 13 1 8 333 11 16 18 9 16 15 7 13 16 198 10 9 16 268 198 7 13 16 7 1 4 Unit in mm service space grille 1 20 or more Installation limit 1 20 or more 12 300 or more E g If installing a duct ...

Page 7: ...s 1 1 1 2 4 4 5 5 5 5 3 Cover B Cover A Control box Control box cover Cable clamp 6 8 9 10 11 11 8 8 10 10 10 8 7 Cable clamp Accessory Cover B Cover A Control box Control box cover 6 Change the control box attachment position 7 Attach the cable clamp accessory Thereafter put the cable in the cable clamp 8 Fix the control box position 4 screws 9 Attach Cover B to Cover A 1 screw 10 Attach Cover A ...

Page 8: ...ndoor unit capacity Btu h Suction gas pipe in mm Discharge gas pipe in mm Gas pipe in mm 7 500 9 500 12 000 14 000 1 2 12 7 Reducer 3 8 9 52 Reducer 1 2 12 7 Reducer 18 000 24 000 30 000 5 8 15 88 Reducer 1 2 12 7 5 8 15 88 Reducer 36 000 48 000 3 4 19 05 1 2 12 7 3 4 19 05 60 000 3 4 19 05 5 8 15 88 Reducer 3 4 19 05 Table 3 Connection pipe selection for when 2 to 8 indoor units are connected Tot...

Page 9: ...ns for electrical wiring WARNING Electrical work must be performed in accordance with this Manual by a person certified under the national or regional regulations Be sure to use a dedicated circuit for the unit An insufficient power supply circuit or improperly performed electrical work can cause serious accidents such as electric shock or fire Before starting work check that power is not being su...

Page 10: ...river to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 4 Do not tighten the terminal screws too much otherwise the screws may break 5 See the table for the terminal screw tightening torques 6 Please do not fix 2 power supply cables with 1 screw Strip 1 in 25 mm Screw with special ...

Page 11: ...rcuit Breaker MAX CKT BKR Disconnect switch shall be installed between RB unit and pull box The transmission cable connects indoor units belonging to the same RB group The transmission cable cannot be used to connect indoor units belonging to different RB groups GOOD PROHIBITED Refrigerant pipe RB group 1 RB group 1 RB group 2 RB group 2 Transmission line Transmission line Crossover wiring of powe...

Page 12: ...etting 1 RB unit address When connecting multiple RB units to 1 refrigerant system set the address at RB AD SW Rotary switch RB AD 1 Factory setting 0 Rotary switch RB AD 10 Factory setting 0 2 Refrigerant circuit address In the case of multiple refrigerant systems set REF AD SW for each refrigerant system Set to the same refrigerant circuit address as the outdoor unit Rotary switch REF AD 1 Facto...

Page 13: ...ing 24V across pins 1 3 c The allowable current is DC 5mA to 10 mA Recommended DC 5mA Provide a load resistance such that the current becomes DC 10mA or less Select very low current use contacts usable at DC 12V DC 1mA or less d The polarity is for pin 1 and for pin 3 Connect correctly When connected to Apply voltage terminals of multiple RB units with a connected unit be sure to make a branch out...

Page 14: ...er is turned on Lit Lit The wiring is incorrect The IN U terminal of RB unit and outdoor unit transmission terminal are connected with the transmission cable Correctly connect the wiring When re wiring you must turn off the power Lit Flashing There is a fault with the communication board or the main board 0 1s ON 0 1s OFF ...