En-7

6.2.  Wiring  method

Example

*2

*2

*2

Outdoor unit or RB unit *1

Transmission

Transmission

Indoor unit

Remote controller 

(master)

Power supply

Indoor unit

Indoor unit

Power supply

Remote 

 control

Breaker

Breaker

Breaker

Remote controller 

(slave)

Remote controller

*1:  When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit.

*2:  Earth (Ground) the remote controller if it has an earth (ground) cable.

(Crossover wiring of power supply)

Indoor unit

Pull box

Pull box

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

Breaker

Power supply

6.3.  Unit  wiring

Before attaching the cable to terminal block.

6.3.1.  Cable  specifications

Adjust the length of power supply cable to avoid excessive tension with referring figure 

below.

20 mm

30 mm

Earth (Ground) 

cable

A.  For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable. 

(2)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. 

 

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam

-

aged and prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.

(5)  Refer to the table for the terminal screw tightening torques.

(6)  Please do not fix 2 power supply cables with 1 screw.

Strip 25 mm

Screw with 

 

special washer

Screw with 

 

special washer

Cable end (loop)

Loop

Terminal block

Cable end (loop)

Cable

Cable

Do not apply branch wiring. It may result electric shock or fire.

 WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 

cables with the ring terminal, the ring terminal's pressure bonding may malfunction and 

cause the cables to abnormally heat up.

B.  For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw

-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 

screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  Refer to the table for the terminal screw tightening torques.

(7)  Please do not fix 2 power supply cables with 1 screw.

Strip 10 mm

Ring terminal

Sleeve

Screw with 

 

special washer

Screw with 

 

special washer

Ring terminal

Terminal block

Ring terminal

Cable

Cable

 WARNING

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 

unit.

Tightening torque

M4 screw (Power supply/L, N, GND)

1.2 to 1.8 N·m (12 to 18 kgf·cm)

6.3.2.  Transmission and Remote controller cable

Transmission cable

Remote controller cable

Shield cable 

(no film)

25 mm

40 mm

20 mm

• Connect remote controller and transmission cables as shown in following figure.

GOOD

PROHIBITED

Different diameter

Connect to 1 side

 WARNING

Tighten the terminal screws to the specified torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Terminal number

Tightening torque

M3 screw (Transmission/X1, X2) 

 

(Remote controller/ Y1, Y2)

0.5 to 0.6 N·m 

 

(5 to 6 kgf·cm)

 CAUTION

To peel the film from the lead cable, use a dedicated tool that will not damage the 

conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening the 

screw. On the other hand, an undertightened screw can cause faulty contact, which will 

lead to a communication failure.

6.4.  Connection of wiring

(1)  Remove the control box cover.

Control box cover

Screw

9384723017_IM.indb   7

14-Oct-20   13:29:53

Summary of Contents for Airstage AUXV004GLEH

Page 1: ...a cassetta flusso a 1 via A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Τύπος κασέτας ροής 1 δρόμου Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR tipo de cassete de fluxo 1 via Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙМОДУЛЬ 1 стороннийкассетноготипасвоздушны...

Page 2: ...g consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture ...

Page 3: ...te metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes...

Page 4: ...lp you install the indoor unit The template helps you determine the appropriate locations for suspension bolts and pipe openings drain pipe and connection cable 3 4 1 Indoor unit dimensions Top view Unit mm A Hanger bolt pitch C Ceiling opening D Cassette grille size 590 Ceiling opening 295 Hanger bolt pitch 620 Cassette grille size B Indoor unit size 570 Indoor unit size Model AUXV004 007 009 012...

Page 5: ...and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units or RB unit respectiv...

Page 6: ... accessories around the gas pipe and liquid pipe of indoor side After installing the coupler heat insula tion wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation accessories Cover this portion with he...

Page 7: ...AUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the product Never bundle the power supply cable and transmission cable remote controller cable togeth...

Page 8: ...iring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal s...

Page 9: ...n Fast flashing every 0 1 second There is a fault with the communication board or the main board Blinking repeat 3 seconds ON and 1 second OFF The indoor unit is turned off and power is supplied from the External power supply unit optional to the indoor unit PCB 6 5 3 Connection methods Wire modification for External input output wire 1 Remove insulation from wire at tached to wire kit connector 2...

Page 10: ...t DC 12 V DC 1 mA or less d The wiring is different from apply voltage terminals Be sufficiently careful when wir ing When connected to dry contact terminals of multiple indoor units with a connected unit insulate each indoor unit with relay etc as shown on below example K1 CNA02 CNA02 CNA02 K2 K3 K4 K5 K6 Power supply for relay Indoor unit Indoor unit Indoor unit Input device 2 Input device 1 K1 ...

Page 11: ...al for detailed setting informa tion Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing the field setting 7 1 Setting the address 7 1 1 Manual address setting method If the receiver unit is attached the indoor unit address and the refrigerant circuit address can also be set up through the wireless remote controller CAUTION Use an insulated screwdriver to set the DIP s...

Page 12: ...aise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage 01 Disable Cool Air Prevention 43 00 Super low Restrain the cold airflow with making the airflow lower when starting heat ing operation To correspond to the ventilation set to 01 01 Follow the setting on the remote controller Exte...

Page 13: ...vice No operation After installation is completed has the proper operation and handling been explained to the user 12 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns Refer to the following table for lamp blink ...

Reviews: