3.2.  Installation dimensions

Ceiling height is as shown in the figure.

Side view

Strong and durable ceiling

2,100 to 3,200 mm

Floor

150 mm or more

260 mm

Front view

150 mm 
or more

Distance between the indoor unit (bottom) and the ceiling board

50 mm

*  Be sure to make the function settings with the remote controller according to the 

installed ceiling height.

3.3.  Installing the unit

 WARNING

Install the air conditioner in a location which can withstand a load of at least 5 times the 
weight of the indoor unit and which will not amplify sound or vibration. If the installation 
location is not strong enough, the indoor unit may fall and cause injuries.

If the job is done with the panel frame only, there is a risk that the unit will come loose. 
Please take care.

3.3.1.  Position the ceiling hole and hanging bolts

(1)  Positions of the ceiling opening, hanging bolt pitch, indoor unit frame and panel 

frame.

• Ceiling opening and hanging bolt pitch. (unit: mm)

1,300 to 1,320 

(Ceiling opening)

1,222  (Hanging bolt pitch)

460 (Hanging 

bolt pitch)

580 

(Panel frame)

530 to 550

(Ceiling opening)

500 

(Body frame)

1,182  (Body frame)

58 (Control box)

1,350  (Panel frame)

• Refrigerant piping and drain piping positions. (unit: mm)

Gas pipe

Liquid pipe

Drain pipe

50

150

227

204

250

85

120

Drain pipe
(Connect the attached 
drain hose)

435

105

65

(2) Hanging 

structure.

• Select a strong structure for the hanging location.
• If necessary, reinforce the hanging bolt with quakeproof columnar support material to 

prevent shaking.

• Use hanging bolts of M8 to M10.

3.3.2. Hanging preparations

• Firmly fasten the hanging bolts as shown 

in the figure or by another method.

• Install the hanging bolts at a place 

where they would be capable of holding 
a weight of at least 490 N per bolt.

Hole-in anchor
Hole-in plug

Concrete

Insert

Hanging bolt M10 
(locally purchased)

3.3.3. Body installation

 WARNING

Perform final tightening by tightening the double nut firmly.

Be sure to install the indoor unit horizontally and adjust the height below the indoor unit 
and the ceiling surface properly.

(1)  Install the attached washer and nut (prepared on site) onto the hanging bolt.
(2)  Hook the indoor unit onto the hanging bolt.
(3)  Adjust the dimensions of the ceiling surface from the indoor unit.

After installing the grille, you can make fine adjustment of the height of the indoor 
unit. For details, refer to the installation manual of the grille.

Hanging bolt (locally purchased)

Nut A (locally purchased)

Nut B (Double Nut) 
(locally purchased)

30 mm or more

After installing the indoor 
unit, tighten the nuts.

Washer (accessories)

Washer (accessories)

9383489013_IM.indb   3

9383489013_IM.indb   3

08-Feb-19   17:11:21

08-Feb-19   17:11:21

Summary of Contents for AIRSTAGE AUXS018GLEH

Page 1: ...n flusso 3D A uso esclusivo del personale tecnico autorizzato Ελληνικά Português ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ τύπος κασέτας με ροή 3D Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE INTERIOR tipo de cassete de fluxo 3D Apenas para técnicos autorizados Русский Türkçe РУКОВОДСТВО ПО УСТАНОВКЕ ВНУТРЕННИЙ МОДУЛЬ кассетный тип с 3D потоком Только для авторизованного ...

Page 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using the R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally...

Page 3: ...unit to leak water Area filled with mineral oil or containing a large amount of splashed oil or steam such as a kitchen It will deteriorate plastic parts causing the parts to fail or the unit to leak water Area that generates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause re...

Page 4: ... pipe 50 150 227 204 250 85 120 Drain pipe Connect the attached drain hose 435 105 65 2 Hanging structure Select a strong structure for the hanging location If necessary reinforce the hanging bolt with quakeproof columnar support material to prevent shaking Use hanging bolts of M8 to M10 3 3 2 Hanging preparations Firmly fasten the hanging bolts as shown in the figure or by another method Install ...

Page 5: ...addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 3 Flare connection pipe connection WARNING Tighten the flare nuts with a torque wrench using the specified tightening method Other wise the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use spe...

Page 6: ...by using the visible portion of transpar ent drain port and the drain piping final outlet on the indoor unit CAUTION Do not apply adhesive agent on the drain port of the indoor unit Use the attached drain hose and connect the drain piping Install the drain pipe with downward gradient 1 100 to 1 50 and so there are no rises or traps in the pipe Unsmooth draining caused by accumulated water flow in ...

Page 7: ...sufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneo...

Page 8: ...manual of the RB unit 2 Earth Ground the remote controller if it has an earth ground cable 3 The 3 wire type remote controller is not used Crossover wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Earth Ground cable 20 mm 30 ...

Page 9: ...d Then loosen one screw and remove the sheet metal Connector 3 After wiring is complete secure the cables with the cable clamps Cable clamp Earth ground Power supply cable 4 Connect the transmission and remote controller cables by passing the cables through the hole shown in the diagram below Once all cables are connected tie the power cable using a push mount cable tie and tie the transmission an...

Page 10: ...er supply unit Cable of the IR receiver unit Cable clamp Cable clamp Once all connectors required for connection are connected push up the circuit board that was pulled down and endure that the hooks are in place Fix the connected cables by passing them through the hole using the grille accessory cable tie as shown in the following figure Cable tie accessory of the grille 6 6 External input and ex...

Page 11: ...ergency stop ON OFF Normal Pulse CNA01 or CNA02 Ch1 OFF ON Emergency stop Ch2 OFF ON Normal All indoor units of same refrigerant system stops when Emergency stop operates When function setting is Forced stop mode Input signal type Connector Input signal Command Edge Ch1 of CNA01 or CNA02 OFF ON Forced stop ON OFF Normal Pulse CNA01 or CNA02 Ch1 OFF ON Forced stop Ch2 OFF ON Normal When the forced ...

Page 12: ...g for indoor unit Set the DIP switch SET3 SW1 2 referring to the figure and table below SET3 10 IU AD 1 10 REF AD 1 SET4 DIP switch SET3 SW 1 SW 2 SW 3 SW 4 ON OFF DIP switch SET3 DIP switch SET3 Custom code A Factory setting B C D SW1 OFF ON OFF ON SW2 OFF OFF ON ON 7 3 Function setting FUNCTION SETTING can be performed with the wired or wireless remote controller The remote controller is optiona...

Page 13: ...9 4 5 C Forbidden 71 00 Forbidden 72 00 Forbidden 73 00 Forbidden 74 00 Forbidden 75 00 8 GRILLE INSTALLATION Operate according to the installation manual of the grille Be sure to confirm there is no gap between the grille and indoor unit after installing the grille 9 TEST RUN 9 1 Test run using Outdoor unit PCB Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit ...

Page 14: ...r error 3 10 Indoor unit communication circuit wired remote control ler error 4 1 Indoor unit room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5 s ON 0 5 s...

Reviews: