Fujitsu Airstage AUUA4TLAV1 Installation Manual Download Page 6

En-5

Pipe outside diameter 

[in (mm)]

Dimension A [in (mm)]

Dimension B

 0 (0)

 -0.015 (-0.4) 

 

[in (mm)]

Flare tool for R410A, 

clutch type

1/4 (6.35)

0 to 0.020

(0 to 0.5)

3/8 (9.1)

3/8 (9.52)

1/2 (13.2)

1/2 (12.70)

5/8 (16.6)

5/8 (15.88)

3/4 (19.7)

3/4 (19.05)

15/16 (24.0)

When using conventional (R22) flare tools to flare R410A pipes, the dimension A should 
be approximately 0.020 in (0.5 mm) more than indicated in the table (for flaring with 
R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the 
dimension A. It is recommended that a R410A flaring tool is used.

Width across 

fl

 ats

Pipe outside diameter 

[in (mm)]

Width across flats of Flare 

nut [in (mm)]

1/4 (6.35)

11/16 (17)

3/8 (9.52)

7/8 (22)

1/2 (12.70)

1 (26)

5/8 (15.88)

1-1/8 (29)

3/4 (19.05)

1-7/16 (36)

4.3.2. Bending pipes

• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bent or stretched, the material will harden, making it difficult 

to bend or stretch them anymore.

• Do not bend or stretch the pipes more than 3 times.

 CAUTION

To prevent breaking of the pipe, avoid sharp bends. 
If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

When the flare nut is tightened 
properly by your hand, hold the 
body side coupling with a separate 
spanner, then tighten with a torque 
wrench. (See the table below for the 
flare nut tightening torques.)

Connection pipe

Flare nut

Tighten with 2 
wrenches.

Torque wrench

Indoor unit pipe 
(Body side)

Holding 
wrench

 CAUTION

Hold the torque wrench at its grip, 
keeping it at a right angle with the 
pipe, in order to tighten the flare 
nut correctly.

Flare nut [in (mm)]

Tightening torque [lbf·ft (N·m)]

1/4 (6.35) dia.

11.8 to 13.3 (16 to 18)

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

1/2 (12.70) dia.

36.1 to 45.0 (49 to 61)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

3/4 (19.05) dia.

66.4 to 81.1 (90 to 110)

4.4.  Installing heat insulation

Install the heat insulation material after performing a refrigerant leak check (see the Instal-
lation Manual for the outdoor unit for details).

Coupler heat insulation

• Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid pipe 

of indoor side.

• After installing the coupler heat insulation, wrap both end with vinyl tape so that there is 

no gap.

• After affixing the coupler heat insulation, secure it with 2 cable ties (large), one on each 

end of the insulation.

• Make sure that the cable ties overlap the heat insulation pipe.

Coupler heat insulation 
(Accessories)

Cable tie (Large) 
(Accessories)

Heat insulation

Heat insulation

Cover this portion with 
heat insulation.

 CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), per-
form this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

5.  INSTALLING DRAIN PIPES

 WARNING

Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat ex-
change erosion may occur)

Insulate the parts properly so that water will not drip from the connection parts.

Check for proper drainage after the construction by using the visible portion of transpar-
ent drain port and the drain piping final outlet on the body.

 CAUTION

Do not apply adhesive agent on the drain port of the body. (Use the attached drain hose 
and connect the drain piping)

• Install the drain pipe with downward gradient (1/100 to 1/50) and so there are no rises or 

traps in the pipe. Unsmooth draining caused by accumulated water flow in the pipe may 
cause clogged drain.

• Use general hard polyvinyl chloride pipe (Ø 3/4 in [I.D.]; Ø 1-1/16 in [O.D.]).
• When the pipe is long, install supporters.
• Do not perform air bleeding. Drainage may be blown out.
• Always heat insulate the indoor side of the drain pipe.
• If it is impossible to have sufficient gradient of pipe, perform drain lift-up.

Pipe size

Drain pipe

Ø 3/4 in [I.D.]; Ø 1-1/16 in [O.D.]

Hanging 

fi

 ttings

Ø 3/4 in [I.D.]; Ø 1-1/16 in [O.D.]
Downward gradient 1/100 to 1/50

60 to 78 in (1.5 to 2.0 m)

Rise

PROHIBITED:

Trap

Air bleeding

When lifting up drain:

• Height of inclined pipe should be less than 27 in (700 mm) from the ceiling. A rise dimen-

sion over this range will cause leakage.

• Lift up the pipe vertically at the position of 11 in (300 mm) or less from the unit.

Ø 3/4 in [I.D.]; 
Ø 1-1/16 in [O.D.] 
local arrangement

Ø 1 in [I.D.]; Ø 1-5/16 in [O.D.] or more 
Downward gradient 1/100 to 1/50

Downward gradient 
1/100 to 1/50

11 in (300 mm) 
or less

27 in (700 mm) 
or less

27 in (700 mm) 
or less

Horizontal or 
upward gradient

9371022581-02_IM.indb   Sec1:5

9371022581-02_IM.indb   Sec1:5

2018/1/23   11:17:07

2018/1/23   11:17:07

Summary of Contents for Airstage AUUA4TLAV1

Page 1: ...4TLAV1 AUUA7TLAV AUUA9TLAV AUUA12TLAV AUUA14TLAV AUUA18TLAV AUUA24TLAV INSTALLATION MANUAL For authorized service personnel only MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado 9371022581 02_IM indb 1 9371022581 02_IM indb 1 2018 1 23 11 17 06 2018 1 23 11 17 06 ...

Page 2: ...s and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical components immediately after the power supply has been turned off Elec...

Page 3: ...s be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non prescribed parts can cause serious accidents such as the unit to fall water leakage electric shock or fire The following installation parts are furnished Use them as required Keep the Installation Manual in a safe place and do not discard any other accessories until the installation work has been compl...

Page 4: ...unit where the drain pipe can be easily installed 8 Install the unit where noise and vibrations are not amplified 9 Take servicing etc into consideration and leave the spaces Also install the unit where the filter can be removed 3 2 Installation dimensions Leave the space specified in Fig A so that the air from the blower will cover the entire room Install the indoor unit on a place having a suffi...

Page 5: ...ses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the table even if they are avail able on the market Thicknesses of Annealed Copper Pipes R410A Pipe outside diameter in mm Thickness in mm 1 4 6 35 0 032 0 80 3 8 9 52 0 032 0 80 1 2 12 70 0 032 0 80 5 8 15 88 0 039 1 00 3 4 19 05 0 039 1 20 4 2 Pipe requirement CAUTION Refer to the...

Page 6: ...er heat insulation wrap both end with vinyl tape so that there is no gap After affixing the coupler heat insulation secure it with 2 cable ties large one on each end of the insulation Make sure that the cable ties overlap the heat insulation pipe Coupler heat insulation Accessories Cable tie Large Accessories Heat insulation Heat insulation Cover this portion with heat insulation CAUTION After che...

Page 7: ...ic parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur We suggest installing GFEB...

Page 8: ...switch shall be installed between indoor unit and pull box 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring figure below Conduit connector Earth ground wire 2 3 4 in 70 mm 1 3 4 in 45 mm A For solid core wiring 1 To connect the electrical terminal follow the below diagram and conn...

Page 9: ... of the indoor unit may be damaged Do not bundle the remote controller cable or wire the remote controller cable in paral lel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 1 Remove the control box cover and install each connection cable Screw Control box cover 2 Connect the connection cable with the cable tie Conduit connector...

Page 10: ...ternal dimension depending on the number of cables to be installed The wire connection should be separate from the power cable line Input select Use either one of these types of terminal according to the application Both types of terminals cannot be used simultaneously Apply voltage terminal CNA01 CNA03 When a power supply must be provided at the input device you want to connect use the Apply volt...

Page 11: ...roller is restricted When forced stop function is used with forming a remote controller group connect the same equipment to each indoor unit within the group Selection method of functions Operation Stop mode or Emergency stop mode Forced stop mode can be selected with function setting of indoor unit Forced thermostat off function Edge input only Connector Input signal Command Ch3 of CNA03 or CNA04...

Page 12: ...ibed 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU AD REF AD SW to 0 3 Automatic address settings Refer to the outdoor unit manual for detailed setting information Set IU AD REF AD SW to 0 CAUTION Be sure to turn OFF the power before performing...

Page 13: ...rt Stop by a remote controller is restricted 01 Emergency stop 02 Forced stop Error report target 47 00 All Change the target for reporting er rors Errors can either be reported in all locations or only on the central remote controller 01 Display only on central remote con troller Fan set ting when cooling thermostat OFF 49 00 Follow the setting on the remote controller When set to 01 the fan stop...

Page 14: ... FILTER indicator lamp Red Setting number 0 to 9 0 5s ON 0 5s OFF Example Function 31 Setting number 2 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 11 sec 10 sec 9 sec 1 cycle 12 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF 8 CASSETTE GRILLE INSTALLATION 8 1 Remove the intake grille 1 Slide the 2 grille hook Grille hoo...

Page 15: ...stallation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote controller the lamp on the photodetector unit will output error codes by way of blinking patterns See the lamp blinking patterns and error codes in the table below Erro...

Reviews: