
En-12
SW
1
SW
2
SW
3
SW
4
ON
OFF
DIP switch “SET3”
DIP switch
SET3
Custom code
A (Factory
setting)
B
C
D
SW1
OFF
ON
OFF
ON
SW2
OFF
OFF
ON
ON
7.3. Function
setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address.” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter indica-
tor interval
11
00 standard
Adjust the filter cleaning interval
notification. If the notification
is too early, change to setting
01. If the notification is too late,
change to setting 02.
01 Longer
02 Shorter
Filter indica-
tor action
13
00 Enable
Enable or disable the filter indi-
cator. Setting 02 is for use with a
central remote controller.
01 Disable
02
Display only
on central
remote con-
troller
Ceiling
airflow
20
00 standard
Regulate the airflow according
to the needs of the installation
location. When set to 01, the air
flow will be stronger. (Cassette
type only)
01 High Ceiling
Vertical
airflow direc-
tion
23
00 standard
Adjust the vertical airflow direc-
tion. All airflow direction louvers
are adjusted together.
(Cassette type only)
01 Raise
Cool air
temperature
trigger
30
00 standard
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature,
use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 standard
Adjust the heat air trigger tempera-
ture. To lower the trigger tempera-
ture by 11 degrees F (6 degrees
C), use setting 01. To lower the
trigger temperature by 7 degrees
F (4 degrees C), use setting 02. To
raise the trigger temperature, use
setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart
40
00 Enable
Enable or disable automatic
system restart after a power
outage.
01 Disable
Cool Air
Prevention
43
00 Super low
Restrain the cold airflow with
making the airflow lower when
starting heating operation. To
correspond to the ventilation,
set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant sys-
tems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the exter-
nal input terminals, and Start/
Stop by a remote controller is
restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the
central remote controller.
01
Display only
on central
remote con-
troller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection
of the wired remote controller
(2-wire type or 3-wire type)
and switching its thermistor are
necessary.
01 Stop
Function
Function
number
Setting number
Default
Details
Switching
functions
for external
inputs and
external
outputs
terminals
60
00 Mode 0
• Set this function when connect-
ing the VRF system to a venti-
lator, economizer, humidifier, or
other external device.
• The connection terminal
functions can be changed
depending on the type of ex-
ternal device. For details of the
connection terminal functions,
see the Design & Technical
Manual.
01 Mode 1
02 Mode 2
03 Mode 3
04 Mode 4
05 Mode 5
06 Mode 6
07 Mode 7
08 Mode 8
Control
switching
of external
heaters
61
00
Auxiliary heat-
er control 1
Sets the control method for the
external heater being used. For
details of the control method,
see the Design & Technical
Manual.
01
Auxiliary heat-
er control 2
02
Heat pump
prohibition
control
03
Heater selec-
tion control
using outdoor
temperature 1
04
Heater selec-
tion control
using outdoor
temperature 2
Operating
temperature
switching
of external
heaters
62
00 Setting 0
• Sets the temperature condi-
tions when the external heater
is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is
ON". For a more detailed
explanation, see the Design &
Technical Manual.
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
(Forbidden)
70
00
Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON= Room temperature - set temperature
Set value of function: 61
00
01
02
03
04
Set value of func-
tion: 62
00
t < -5.4°F (-3°C)
t
≤
-0.9°F (-0.5°C)
01
t < -3.6°F (-2°C)
t
≤
-1.8°F (-1°C)
02
t < -3.6°F (-2°C)
t
≤
-3.6°F (-2°C)
03
t < -5.4°F (-3°C)
t
≤
-5.4°F (-3°C)
04
t < -7.2°F (-4°C)
t
≤
-7.2°F (-4°C)
05
t < -9.0°F (-5°C)
t
≤
-9.0°F (-5°C)
7.3.1. Button name and function
(1) Filter indicator lamp (Red)
(2) Timer indicator lamp (Orange)
(3) Operation indicator lamp (Green)
(4) Manual auto button
7.3.2. Checking the function settings
• Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indication pattern
Indoor unit
address
Refrigerant address
OPERATION indicator lamp
(Green)
ON
Flash (1.0s ON/1.0s OFF)
TIMER indicator lamp (Orange)
Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Address: ones place (0.5s ON/0.5s OFF)
9371022581-02_IM.indb Sec1:12
9371022581-02_IM.indb Sec1:12
2018/1/23 11:17:12
2018/1/23 11:17:12