En-11
Function
Function
number
Setting number
Default
Details
Cool Air
Prevention
43
00 Super low
Restrain the cold airflow with
making the airflow lower when
starting heating operation. To
correspond to the ventilation,
set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant sys-
tems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the exter-
nal input terminals, and Start/
Stop by a remote controller is
restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
Change the target for reporting
errors. Errors can either be re-
ported in all locations, or only on
the central remote controller.
01
Display only
on central
remote con-
troller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection
of the wired remote controller
(2-wire type) and switching its
thermistor are necessary.
01 Stop
Switching
functions
for external
inputs and
external
outputs
terminals
(*2)
60
00 Mode 0
• Set this function when connect-
ing the VRF system to a venti-
lator, economizer, humidifier, or
other external device.
• The connection terminal
functions can be changed
depending on the type of ex-
ternal device. For details of the
connection terminal functions,
see the Design & Technical
Manual.
01 Mode 1
02 Mode 2
03 Mode 3
04 Mode 4
05 Mode 5
06 Mode 6
07 Mode 7
08 Mode 8
Control
switching
of external
heaters
61
00
Auxiliary
heater con-
trol 1
Sets the control method for the
external heater being used. For
details of the control method,
see the Design & Technical
Manual.
01
Auxiliary
heater con-
trol 2
02
Heat pump
prohibition
control
03
Heater selec-
tion control
using outdoor
temperature 1
04
Heater selec-
tion control
using outdoor
temperature 2
05
Auxiliary
heater control
by outdoor
temperature 3
06
Auxiliary heat
pump control
07
Auxiliary heat
pump control
by outdoor
temperature 1
08
Auxiliary heat
pump control
by outdoor
temperature 2
09
Auxiliary heat
pump control
by outdoor
temperature 3
7.2. Custom code setting
• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Code change
Indoor unit
Remote
controller
Confusion
A B C D
A B C D
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the
figure and table below.
IU AD
REF AD
RC AD
×10 ×1
×10 ×1
SET3
SET4
DIP switch “SET3”
SW
1
SW
2
SW
3
SW
4
ON
OFF
DIP switch “SET3”
DIP switch
SET3
Custom code
A (Factory
setting)
B
C
D
SW1
OFF
ON
OFF
ON
SW2
OFF
OFF
ON
ON
7.3. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address.” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
Default
Details
Filter indica-
tor interval
11
00 Standard
Adjust the filter cleaning interval
notification. If the notification
is too early, change to setting
01. If the notification is too late,
change to setting 02.
01 Longer
02 Shorter
Filter indica-
tor action
13
00 Enable
Enable or disable the filter indi-
cator. Setting 02 is for use with a
central remote controller.
01 Disable
02
Display only
on central
remote con-
troller
Ceiling
airflow
20
00 Standard
Regulate the airflow according
to the needs of the installation
location. When set to 01, the air
flow will be stronger. (Cassette
type only)
01 High Ceiling
Vertical
airflow direc-
tion
23
00 Standard
Adjust the vertical airflow direc-
tion. All airflow direction louvers
are adjusted together.
(Cassette type only)
01 Raise
(Forbidden)
24
00
(Forbidden)
26
31
Cool air
temperature
trigger
30
00 Standard
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature,
use setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00 Standard
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 11 degrees F (6
degrees C), use setting 01. To
lower the trigger temperature by
7 degrees F (4 degrees C), use
setting 02. To raise the trigger
temperature, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart
(*1)
40
00 Enable
Enable or disable automatic
system restart after a power
outage.
01 Disable
9371022659-02_L3.indb Sec1:11
9371022659-02_L3.indb Sec1:11
9/24/2019 11:10:56 AM
9/24/2019 11:10:56 AM