En-16
(6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
44
00
A
♦
01
B
02
C
03
D
(7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
46
00
Operation/Stop mode
♦
01
(Setting prohibited)
02
Forced stop mode
(8) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller
only, change the setting to "Wired remote controller" (01). This
function will only work if the function setting 42 is set at "Both"
(01)
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
48
00
Both
♦
01
Wired remote controller
Setting record
Record any changes to the settings in the following table.
Setting
Setting value
(1) Filter sign
(2) Ceiling height
(3) Outlet directions
(4) Auto restart
(5) Room temperature sensor switching
(6) Remote controller custom code
(7) External input control
(8) Room temperature sensor switching (Aux.)
After completing the Function Setting, be sure to turn off the
power and turn it on again.
• Temperature Correction
NOTE:
When changing Function 95, perform this setting before other
Room temp. control settings (Function 30, 31, 92, 93).
If Function 95 is not set first, Room temperature control
settings (Function 30, 31, 92, 93) will be reset and you must
re-do them again.
(1) Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed
environment.
Standard insulation "00" allows system to rapidly respond to
the cooling or heating load changes.
High insulation "01" is when the heat insulation structure of
the building is high and does not require system to rapidly
respond to cooling or heating load changes.
When High insulation "01" is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 92, 93) will
reset to No correction [0.0°F (0.0°C)].
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
95
00
Standard insulation
♦
01
High insulation
(2) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the
room temperature sensor may be required.
Select the appropriate control setting according to the installed
environment.
The temperature correction values show the difference from
the Standard setting "00" (manufacturer's recommended
value).
* When Function 95-01(High insulation) is set, the Standard
setting "00" will be the same as No correction "01" [0.0°F
(0.0°C)].
(
♦
... Factory setting)
Function
number
Setting
value
Setting description
30
(For
cooling)
31
(For
heating)
00
Standard setting*
♦
01
No correction 0.0°F (0.0°C)
02
-1°F (-0.5°C)
More
Cooling
Less
Heating
03
-2°F (-1.0°C)
04
-3°F (-1.5°C)
05
-4°F (-2.0°C)
06
-5°F (-2.5°C)
07
-6°F (-3.0°C)
08
-7°F (-3.5°C)
09
-8°F (-4.0°C)
10
+1°F (+0.5°C)
Less
Cooling
More
Heating
11
+2°F (+1.0°C)
12
+3°F (+1.5°C)
13
+4°F (+2.0°C)
14
+5°F (+2.5°C)
15
+6°F (+3.0°C)
16
+7°F (+3.5°C)
17
+8°F (+4.0°C)
In case of Slim duct type and Floor/Ceiling type models:
In
fl
oor console installations, select “01”.
9374318599-02_IM.indb 16
9374318599-02_IM.indb 16
9/26/2018 11:04:20 AM
9/26/2018 11:04:20 AM