Fujitsu Airstage ARUM24TLAV2 Installation Manual Download Page 9

En-8

6.2. Wiring method

EXAMPLE

*2

*2

*2

Outdoor unit or RB unit *1

Breaker 1:  Ground Fault Equipment 

Breaker (GFEB)

Breaker 2:  Maximum Circuit Breaker 

(MAX. CKT. BKR)

Transmission

Transmission

Indoor unit

Remote controller 

(Master)

Power supply

Indoor unit

Indoor unit

Power supply

Remote 
 control

Breaker 2

Breaker 2

Breaker 2

Breaker 1

Breaker 1

Breaker 1

Remote controller 

(Slave)

Remote 

controller

*1:  When connecting to the Heat Recovery System, refer to the installation manual of the 

RB unit.

*2:  The 3-wire type remote controller is not used.

(Crossover wiring of power supply)

Breaker2

Breaker1

Indoor unit

Power supply

Pull box

Pull box

Power supply

: Disconnect switch

Power supply

Power supply

Indoor unit

Indoor unit

Disconnect switch shall be installed between indoor unit and pull box.

6.3. Unit wiring

Before attaching the cable to terminal block.

6.3.1. Power supply cable

Adjust the length of power supply cable to avoid excessive tension with referring figure 
below.

Earth 
(Ground) wire

Conduit connector

2-3/4 in

(70 mm)

2-3/4 in

(70 mm)

A.  For solid core wiring

(1)  To connect the electrical terminal, follow the below diagram and connect after looping 

it around the end of the cable. 

(2)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(3)  Use an appropriate screwdriver to tighten the terminal screws. 

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-
aged and prevent the screws from being properly tightened.

(4)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(5)  See the table for the terminal screw tightening torques.
(6)  Please do not fix 2 power supply cables with 1 screw.

Strip 1 in
(25 mm)

Screw with spe-
cial washer

Terminal block

Cable end (Loop)

Cable end (Loop)

Loop

Screw with spe-
cial washer

Cable

Cable

 

WARNING

When using solid core cables, do not use the ring terminal. If you use the solid core 
cables with the ring terminal, the ring terminal's pressure bonding may malfunction and 
cause the cables to abnormally heat up.

B.  For strand wiring

(1)  Use ring terminals with insulating sleeves as shown in the figure below to connect to 

the terminal block.

(2)  Securely clamp the ring terminals to the cables using an appropriate tool so that the 

cables do not come loose.

(3)  Use the specified cables, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws. 

Do not use a screwdriver that is too small, otherwise, the screw heads may be dam-
aged and prevent the screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break. 
(6)  See the table for the terminal screw tightening torques.
(7)  Please do not fix 2 power supply cables with 1 screw.

Strip 3/8 in 
(10 mm)

Ring terminal

Screw with special 
washer

Ring terminal

Terminal block

Cable

Screw with 
special washer

 Sleeve

Ring terminal

Cable

 

WARNING

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, 
abnormal overheating may be produced and possibly cause heavy damage inside the 
unit.

Tightening torque

M4 screw
(Power supply/L1, L2 (N), GND)

11 to 16 lbf·in

(1.2 to 1.8 N·m)

6.3.2. Transmission and Remote controller cable

Transmission cable

Remote controller cable

Shield 
cable 
(no film)

1 in (25 mm)

1-3/8 in 

(35 mm)

1 in (25 mm)

• When the 2 cables are attached:

GOOD

PROHIBITED

Different diameter

Connect to 1 side

 

WARNING

Tighten the terminal screws to the specified torques, otherwise, abnormal overheating 
may be produced and possibly cause heavy damage inside the unit.

Tightening torque

M3 screw
(Transmission /X1, X2)
(Remote controller /Y1, Y2)

4.4 to 5.3 lbf·in

(0.5 to 0.6 N·m)

 

CAUTION

To peel the film from the lead cable, use a dedicated tool that will not damage the 
conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening the 
screw. On the other hand, an under tightened screw can cause faulty contact, which will 
lead to a communication failure.

9373385264-02_IM_L3.indb   Sec1:8

9373385264-02_IM_L3.indb   Sec1:8

9/24/2019   11:06:29 AM

9/24/2019   11:06:29 AM

Summary of Contents for Airstage ARUM24TLAV2

Page 1: ...e For authorized service personnel only MANUEL D INSTALLATION UNITÉ INTÉRIEURE type conduit Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN UNIDAD INTERIOR Tipo conducto Únicamente para personal de servicio autorizado 9373385264 02_IM_L3 indb 1 9373385264 02_IM_L3 indb 1 9 24 2019 11 06 28 AM 9 24 2019 11 06 28 AM ...

Page 2: ...ng Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using the operating manual DANGER Never touch electrical components immediately after the power supply has been turned off Electrical shock ...

Page 3: ...acuum pump can be used by installing a vacuum pump adapter Be sure that the pump oil does not backflow into the system Use one capable for vacuum suction of 500 microns 100 7 kPa Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 2 3 Accessories WARNING For installation purposes be sure to use the parts supplied by the manufacturer or other prescribed parts The use of non ...

Page 4: ...as Install the unit where drainage does not cause any trouble Install the indoor unit power supply cable transmission cable and remote controller cable at least 40 in 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 40 in 1 m apart you could still receive noise under some signal conditions ...

Page 5: ... exchanger may be clogged and its performance may decrease WARNING When fastening the hangers make the bolt positions uniform The distance of is adjustable according to the place of the hanging bolts MAX 21 5 8 in 550 mm MIN 16 1 8 in 410 mm Slide the unit in the arrow direction and fasten it Hanging bolt M10 locally purchased Special nut A accessories Washer locally purchased Special nut B access...

Page 6: ...the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 9 16 in 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 13 16 in 20 mm or thicker If heat insulation is used that is not as thick as specif...

Page 7: ... pipes Failure to do so may cause water leaks 5 INSTALLING DRAIN PIPES Use general hard polyvinyl chloride pipe and connect it with adhesive polyvinyl chloride so that there is no leakage Always heat insulate the indoor side of the drain hose Use a drain hose that matches the size of the drain pipe Do not perform a rise trap and air bleeding Provide a downward gradient 1 100 or more Provide suppor...

Page 8: ...by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard CAUTION Earth Ground the unit Do not connect the earth ground cable to a gas pipe water pipe lightning rod or a telephone earth ground cable Improper earthing grounding may cause electric shock Do not connect power supply cables to the transmission or remote controller terminals as this will damage the ...

Page 9: ... pressure bonding may malfunction and cause the cables to abnormally heat up B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is n...

Page 10: ...tact terminal CNA04 DIP switch SET 2 SW2 Input signal type switching CNB01 Output terminal For external output CN8 For Remote sensor unit 1 CN48 For IR receiver unit 1 CN65 For one of the following MODBUS convertor 1 Wireless LAN adapter 1 CNA05 For Drain pump unit 1 CN106 CN820 For External power supply unit 1 1 For details refer to each installation manual 6 5 2 Power indicator lamp status Power...

Page 11: ...CNA03 When a power supply must be provided at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 a b 1 CNA01 CNA03 a a Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance DC power supply 12 to 24 V Connected unit P C B 1 Make the power supply DC 12 to 24 V Select a power supply capacity with an ample surplus for the connected lo...

Page 12: ...nected unit P C B When connecting with unit equipped with a power supply CNB 01 P C B Connected device 1 Connected device 2 Connected device 3 Connected device 4 Connected unit Relay locally purchased Operation behavior If function setting 60 is set to 00 Connector Output voltage Status CNB01 External output 1 Pins 1 2 0 V Stop DC 12 V Operation External output 2 Pins 1 3 0 V Normal DC 12 V Error ...

Page 13: ...Rotary switch setting Address Rotary switch setting Refrigerant circuit REF AD SW Indoor unit IU AD SW 10 1 10 1 0 0 0 0 0 0 1 0 1 1 0 1 2 0 2 2 0 2 3 0 3 3 0 3 4 0 4 4 0 4 5 0 5 5 0 5 10 1 0 10 1 0 11 1 1 11 1 1 99 9 9 63 6 3 7 2 Custom code setting Selecting the custom code prevents the indoor unit mix up Up to 4 codes can be set Perform the setting for both the indoor unit and the remote contro...

Page 14: ... filter cleaning interval notification If the notification is too early change to setting 01 If the notification is too late change to setting 02 01 Longer 02 Shorter Filter indica tor action 13 00 Enable Enable or disable the filter indica tor Setting 02 is for use with a central remote controller 01 Disable 02 Display only on central remote controller Forbidden 20 00 Forbidden 23 00 Forbidden 24...

Page 15: ... F 0 5 C t 1 8 F 1 C t 0 F 0 C 08 t 3 6 F 2 C t 0 9 F 0 5 C t 3 6 F 2 C t 0 F 0 C 09 t 5 4 F 3 C t 0 9 F 0 5 C t 5 4 F 3 C t 0 F 0 C 10 t 7 2 F 4 C t 0 9 F 0 5 C t 7 2 F 4 C t 0 F 0 C 11 t 9 0 F 5 C t 0 9 F 0 5 C t 9 0 F 5 C t 0 F 0 C 12 t 5 4 F 3 C t 0 F 0 C t 0 9 F 0 5 C t 0 9 F 0 5 C 13 t 3 6 F 2 C t 0 F 0 C t 1 8 F 1 C t 0 9 F 0 5 C 14 t 3 6 F 2 C t 0 F 0 C t 3 6 F 2 C t 0 9 F 0 5 C 15 t 5 4 F...

Page 16: ...or 4 1 Indoor unit room temp therm istor error 4 2 Indoor unit heat ex temp thermistor error 5 1 Indoor unit fan motor 1 error 5 2 Indoor unit coil expansion valve error 5 3 Indoor unit water drain abnormal 9 15 Outdoor unit miscellaneous error 10 8 Poor refrigerant circulation 13 1 RB unit error Display mode 0 5 s ON 0 5 s OFF 0 1 s ON 0 1 s OFF Number of flashing Wired Remote Controller Display ...

Reviews: