En-2

Transportation of the unit

21 41 

 WARNING

Do not touch the fins. Otherwise, personal injury could result.

 CAUTION

When carrying the unit, hold the handles on the right and left sides and be careful.

 

If the outdoor unit is carried from the bottom, hands or fingers may be pinched.

Be sure to hold the handles on the sides of the unit. Otherwise, holding the suction 

 

grille on the sides of the unit may cause deformation.

Handle

Handle

Installation of the unit

21 21 

Install 4 anchor bolts at the locations indicated with arrows in the figure.

 

To reduce vibration, do not install the unit directly on the ground. Install it on a secure 

 

base (such as concrete blocks).

The foundation shall support the legs of the unit and have a width of 50mm (2 in.) or 

 

more.

Depending on the installation conditions, the outdoor unit may spread its vibration 

 

during operation, which may cause noise and vibration. Therefore, attach damping 

materials (such as damping pads) to the outdoor unit during installation.

Install the foundation, making sure that there is enough space for installing the 

 

connection pipes.

Secure the unit to a solid block using foundation bolts. (Use 4 sets of commercially 

 

available M10 bolts, nuts, and washers.)

The bolts should protrude 20 mm (0.78 in). (Refer to the figure.)

 

If overturning prevention is required, purchase the necessary commercially available 

 

items.

(Unit : mm (in.))

650

(25-19/32)

370 

(14- 9/16)

Bottom side

4-ø12 (1-15/32) hole

Fix securely with bolts on a solid block. (Use 4 sets of commercially available M10 bolt, 

nut and washer.)

Bolt

Nut 

Block

• When there are obstacles at the back and front sides.

AIR

100 mm (4 in.)

or more

600 mm(24 in.)

 

or more

When an obstruction is present also in the upward area

 

• When there are obstacles at the back, side(s), and top.

100-300 mm*

(4 in.-12 in.)

250 mm (10 in.)

or more

(Service space)

300 mm (12 in.)

or more

600-1000 mm* (24 in.- 40 in.)

* If the space is larger than that is stated, the condition will be the same as that there 

are no obstacles.

• When there are obstacles at the back side with the installation of more than one unit.

250 m

m (

10 in.)

or mor

e

250 m

m (

10 in.)

or mor

e

300

 mm (

12 

in.)

or mor

e

No more than 3 units must be installed side by side. 

 

When 3 units or more are arranged in a line, provide the space as shown in the 

following example 

when an obstruction is present also in the upward area.

9374747122_IM_En.indd   6

20/12/2553   13:09:09

Summary of Contents for AIR CONDITIONER

Page 1: ...TIONER OUTDOOR UNIT PART NO 9374747122 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado 9374747122_IM_En indd 1 20 12 2553 13 09 04 ...

Page 2: ...ly refrigeration compressor oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigeran...

Page 3: ... water etc does not enter the piping than with refrigerant models Also when storing the piping securely seal the openings by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Special tools for R410A 222222 Tool name Contents of change Gauge ma...

Page 4: ...capacity type 222222222 CAUTION The total capacity of the indoor units connected must be between 14 000 and 27 000 BTU Connection patterns are restricted Normal operation is not guaranteed if connected pattern in the combination not listed below The product may be damaged Surely connect in accordance with the combination in the following connection pattern To install an indoor unit refer to the in...

Page 5: ...ng is neces sary For more information refer to 6 2 Additional charging Selecting pipe sizes 222222222 The diameters of the connection pipes differ according to the capacity of the indoor unit Refer to the following table for the proper diameters of the connection pipes between the indoor and outdoor units Capacity of indoor unit Gas pipe size thickness mm in Liquid pipe size thickness mm in 7 12 ø...

Page 6: ...topple or fall or other accidents Do not install the outdoor unit near the edge of a balcony Otherwise children may climb onto the outdoor unit and fall off of the balcony CAUTION Do not install the outdoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled with mineral oil o...

Page 7: ...pipes Secure the unit to a solid block using foundation bolts Use 4 sets of commercially available M10 bolts nuts and washers The bolts should protrude 20 mm 0 78 in Refer to the figure If overturning prevention is required purchase the necessary commercially available items Unit mm in 650 25 19 32 370 14 9 16 Bottom side 4 ø12 1 15 32 hole Fix securely with bolts on a solid block Use 4 sets of co...

Page 8: ...er and flare tool exclusive for R410A 1 Cut the connection pipe to the necessary length with a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result i...

Page 9: ...ngth may lead to erroneous operation The static electricity that is charged to the human body can damage the control PC Board when handling the control PC Board for address setting etc Please keep caution to the following points Provide the grounding of Indoor unit Outdoor unit and Option equipment Cut off the power supply breaker Touch the metal section such as the unpainted control box section o...

Page 10: ... UNIT A DISCONNECT SWITCH FIELD SUPPLY DISCONNECT SWITCH FIELD SUPPLY WARNING Disconnect switch and for over current protection given in the table below is to be installed between the indoor unit and the outdoor unit Disconnect switch 15A CAUTION Be sure to refer the above diagram and do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical codes and also any spec...

Page 11: ...ps and charging port cap of the 2 way valve and 3 way valve to the specified torque Checking gas leaks with nitrogen gas Check if the piping connections are secure Remove the cap of 3 way valve and connect the gauge manifold charge hoses to the charging port of the 3 way valve Pressurize with nitrogen gas using the 3 way valve charging port Do not pressurize up to the specified pressure all at onc...

Page 12: ...ng the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Gas Liquid R410A Add refrigerant from the charging valve after the completion of the work If the units are further apart than the maximum pipe length correct operation cannot be guaranteed POWER 777 WARNING The rated voltage...

Page 13: ...D2 LED1 Hole LED is on a reverse side of the board Confirming the operation of indoor unit 888888 Run the unit in a normal way and confirm its operation Please end the test run first before confirmation 1 Cold air or warm air must be discharged from the indoor unit 2 The indoor unit operates normally when air direction or air volume adjustment buttons pressed PUMP DOWN 999 PUMP DOWN OPERATION To a...

Page 14: ...9374747122_IM_Es indd 13 20 12 2553 13 13 45 ...

Page 15: ...9374747122_IM_Es indd 14 20 12 2553 13 13 45 ...

Page 16: ...9374747122_IM_Es indd 15 20 12 2553 13 13 45 ...

Reviews: