8-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢
Model: AOYG09KVCBN
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
4.5 A
4.0 A
46°C ≤ Ta < 50°C
4.5 A
4.0 A
40°C ≤ Ta < 46°C
6.0 A
5.5 A
12°C ≤ Ta < 40°C
8.0 A
7.5 A
2°C ≤ Ta < 12°C
8.0 A
7.5 A
Ta < 2°C
8.0 A
7.5 A
Heating
17°C ≤ Ta
7.0 A
6.5 A
12°C ≤ Ta < 17°C
9.0 A
8.5 A
5°C ≤ Ta < 12°C
9.0 A
8.5 A
Ta < 5°C
9.0 A
8.5 A
¢
Models: AOYG12KVCBN and AOYG14KVCBN
Operation mode
Outdoor temp. (Ta)
Trigger condition
Release condition
Cooling
50°C ≤ Ta
4.5 A
4.0 A
46°C ≤ Ta < 50°C
4.5 A
4.0 A
40°C ≤ Ta < 46°C
6.0 A
5.5 A
12°C ≤ Ta < 40°C
10.0A
9.5 A
2°C ≤ Ta < 12°C
10.0 A
9.5 A
Ta < 2°C
10.0 A
9.5 A
Heating
17°C ≤ Ta
7.0 A
6.5 A
12°C ≤ Ta < 17°C
9.0 A
8.5 A
5°C ≤ Ta < 12°C
11.5 A
11.0 A
Ta < 5°C
11.5 A
11.0 A
8-4. Cooling pressure over-rise protection
When the outdoor unit heat exchanger temperature reaches trigger condition below, the compressor
is stopped and trouble display is performed.
Trigger condition
65°C
8-3. Current release control
- (04-30) -
8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Summary of Contents for AGYG09KVCB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 10 05 SR_CH01_AG002EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 25 SR_CH02_AG002EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 11 11 SR_CH03_AG002EF_01 ...
Page 39: ...5 1 Indoor unit 03 44 5 2 Outdoor unit 03 45 CONTENTS continued ...
Page 40: ......
Page 87: ...4 CONTROL AND FUNCTIONS 2020 11 11 SR_CH04_AG002EF_01 ...
Page 121: ...5 FILED WORKING 2020 11 11 SR_CH05_AG002EF_01 ...