2-3. E: 12. Wired remote controller communication error (Indoor
unit)
Indicator
Wired remote
controller
Error code
E: 12
Detective actuator
Indoor unit
Main PCB
When the indoor unit cannot receive the signal from
Wired remote controller more than 1 minute during
normal operation.
Wired remote control
Forecast of cause
Terminal connection abnormal
Wired remote control failure
Main PCB failure
Check point 1. Check the connection of terminal
After turning off the power, check & correct the followings.
•
Check the connection of terminal between wired remote controller and indoor unit, and check if
there is a disconnection of the cable.
↓
Check Point 1-2 : Check Wired remote controller
and main PCB
•
If it is DC 12 V, remote controller is failure.
(Main PCB is normal)
–
Replace remote control
•
If it is DC 0 V, main PCB is failure. (Check
remote controller once again)
–
Replace main PCB
Check voltage at CN14 of main PCB
(terminal 1—3, terminal 1—2). (Power
supply to the remote controller)
Upon correcting the removed connec-
tor or mis-wiring, reset the power.
↓
End
Check Point 2 : Wire installation wrong remote controller group setting
•
Wrong wire connection in remote controller group (Please refer to the installation manual)
•
The number of connecting indoor unit and remote controller in one remote controller group
were less than 32 units.
↓
Check Point 2-1 : Check Indoor unit main PCB
•
Check if main PCB damage
•
Change main PCB and check the error after setting remote controller address
↓
End
2-3. E: 12. Wired remote controller communication error (Indoor unit)
- (03-7) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Page 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Page 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Page 74: ......
Page 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Page 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Page 142: ......
Page 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...