En-14
(1) External input terminals
• Indoor unit can be Start/Stop or Emergency stop, Forced
stop by using indoor unit PCB CN6 or CN17.
Wiring methods and speci
fi
cations
• A twisted pair cable (22AWG) should be used. Maximum
length of cable is 150 m.
* Use an external input and output cable with appropriate
external dimension, depending on the number of cables to
be installed.
• The wire connection should be separate from the power
cable line.
• Input selection
Use either one of these types of terminal according to the
application. (Both types of terminals cannot be used
simultaneously.)
• Voltage terminal ([CN6])
When a power supply must be provided at the input device
you want to connect, use the voltage terminal ([CN6]).
1
2
3
+
+
-
-
-
In
pu
t d
ev
ic
e 1
In
pu
t d
ev
ic
e 2
Load
resistance
Load
resistance
*1
DC power supply
12 - 24V
connected unit
*a
*a
P.C.B
CN6
*b
*1 Make the power supply DC12 to 24V. Select a power supply
capacity with an ample surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and
1-3.
*a The allowable current is DC5~10mA. (Recommended:
DC5mA)
Provide a load resistance such that the current becomes
DC10mA or less.
Select very low current use contacts (usable at DC12V,
DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3.
Connect
correctly.
When connected to voltage terminals of multiple indoor units
with a connected unit, be sure to make a branch outside the
indoor unit using a pull box, etc. as shown on below example.
DC power
supply 12-24V
connected unit
Load
resistance
P.C.B
P.C.B
CN6
CN6
CN6
P.C.B
In
pu
t d
ev
ic
e 1
In
pu
t d
ev
ic
e 2
Indo
or
unit
Indo
or
unit
Indo
or
unit
Load
resistance
• No voltage terminal ([CN17])
When a power supply is unnecessary at the input device you
want to connect, use the no voltage terminal ([CN17]).
1
2
3
P.C.B
GND
Ch 1
*c
*c
*d
Ch 2
CN17
connected unit
*c Select very low current use contacts (usable at DC12V,
DC1mA or less).
*d The wiring is different from voltage terminals. Be suf
fi
ciently
careful when wiring.
When connected to no voltage terminals of multiple indoor
units with a connected unit, insulate each indoor unit with
relay, etc. as shown on below example.
When connected to multiple indoor units directly, it will cause
breakdown.
Po
w
e
r s
u
p
p
ly
f
o
r r
e
la
y
Indo
or
unit
Indo
or
unit
Indo
or
unit
Input device 2
Input device 1
K1~K6:
Relay
P.C.B
K1
P.C.B
P.C.B
CN17
CN17
CN17
K2
K3
K4
K5
K6
Operation behavior
• Input signal type
The input signal type can be selected.
Pulse
Edge
The width of pulse
must be longer than
200msec.
It is switched by Dip-sw on the indoor
unit PCB.
Dip-sw [Set 2-2]
Input signal type
OFF
Edge
ON
Pulse
• When function setting is “Start/Stop” mode
In the case of “Edge” input
Connector
Input signal
Command
Ch1 of
CN6 or CN17
OFF
→
ON
Operation
ON
→
OFF
Stop
In the case of “Pulse” input
Connector
Input signal
Command
CN6 or CN17
Ch1
OFF
→
ON
Operation
Ch2
OFF
→
ON
Stop
(Device for DC Current)