En-11
]1
6.1. Electrical requirement
Voltage rating
230 V
Operating range
198 - 264 V
Recom-
mended cable
size (mm
2
)
Cable type
Remark
Power
supply cable
2.5
Type245 IEC57
or equivalent
1ø 50 Hz
198 - 264 V
2 Cable + ground
Transmission
cable
0.33
LONWORKS
compatible cable
22 AWG
LEVEL 4 (NEMA)
non-polar 2 core,
twisted pair solid
core diameter
0.65 mm
Remote
controller
cable
0.33
Sheathed
PVC cable*
Polar 3 core
Twisted pair
*: Use shielded cable in accordance with local rules for
remote controller cable.
Fuse capacity (A)
Breaker for leakage current
15
30 mA 0.1 sec. or less
]1
6.2. Wiring method
(EXAMPLE)
POWER SUPPLY
OUTDOOR UNIT
BREAKER
POWER SUPPLY
TRANSMISSION
TRANSMISSION
POWER
SUPPLY
POWER
SUPPLY
REMOTE
CONTROLLER
(Primary)
REMOTE
CONTROLLER
POWER
SUPPLY
REMOTE
CONTROL
TRANSMISSION
TRANSMISSION
POWER
SUPPLY
POWER
SUPPLY
REMOTE
CONTROL
REMOTE
CONTROL
INDOOR UNIT
POWER
SUPPLY
REMOTE
CONTROLLER
(Secondary)
INDOOR UNIT
INDOOR UNIT
BREAKER
BREAKER
BREAKER
*Ground the remote controller if it has a ground wire.
]1
6.3. Unit wiring
• Before attaching the cable to terminal block.
6.3.1. Power supply cable
Power supply
cable
15 mm
Earth
cable
70 mm
A. For solid core wiring
(1) To connect the electrical terminal, follow the below
diagram and connect after looping it around the end of the
cable.
(2) Use the speci
fi
ed cables, connect them securely, and
fasten them so that there is no stress placed on the
terminals.
(3) Use an appropriate screwdriver to tighten the terminal
screws. Do not use a screwdriver that is too small,
otherwise, the screw heads may be damaged and prevent
the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise,
the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not
fi
x 2 power supply cables with 1 screw.
Strip 25 mm
Loop
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
Screw with
special
washer
Cable end
(Loop)
Cable
WARNING
• When using solid core cables, do not use the ring
terminal. If you use the solid core cables with the ring
terminal, the ring terminal’s pressure bonding may
malfunction and cause the cables to abnormally heat up.