CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
MODELS
:AO G30LETL, AO G36LETL
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is lower than outdoor unit.
H
Indoor unit
Outdoor unit
Connection pipe
1 Indoor unit is higher than outdoor unit.
H
Height difference H
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
Height
difference H
(m)
1
Indoor unit is higher
than outdoor unit
30
-
-
-
-
0.908
0.894
0.876
20
-
-
-
0.935 0.923 0.909 0.891
10
-
-
0.968 0.951 0.938 0.924 0.906
7.5
-
0.982 0.972 0.954 0.942 0.928 0.909
5
0.992 0.986 0.976 0.958 0.946 0.932 0.913
0
1.000 0.994 0.983 0.966 0.954 0.939 0.920
2
Indoor unit is lower
than outdoor unit
-5
1.000 0.994 0.983 0.966 0.954 0.939 0.920
-7.5
-
0.994 0.983 0.966 0.954 0.939 0.920
-10
-
-
0.983 0.966 0.954 0.939 0.920
-20
-
-
-
0.966 0.954 0.939 0.920
-30
-
-
-
-
0.954
0.939
0.920
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
Height
difference H
(m)
1
Indoor unit is higher
than outdoor unit
30
-
-
-
-
0.931
0.914
0.899
20
-
-
-
0.954 0.931 0.914 0.899
10
-
-
0.990 0.954 0.931 0.914 0.899
7.5
-
0.991 0.990 0.954 0.931 0.914 0.899
5
1.000 0.991 0.990 0.954 0.931 0.914 0.899
0
1.000 0.991 0.990 0.954 0.931 0.914 0.899
2
Indoor unit is lower
than outdoor unit
-5
0.995 0.986 0.986 0.949 0.926 0.909 0.895
-7.5
-
0.983 0.983 0.946 0.924 0.907 0.892
-10
-
-
0.981 0.944 0.921 0.904 0.890
-20
-
-
-
0.935 0.912 0.895 0.881
-30
-
-
-
-
0.903 0.886 0.872
Summary of Contents for AB G30LRTE Series
Page 2: ...1 INDOOR UNIT CEILING TYPE AB G30LRTE AB G36LRTE DTR_AB037E_01 2013 02 28 ...
Page 34: ...DTR_AO135E_01 2013 02 28 SINGLE TYPE AO G30LETL AO G36LETL 2 OUTDOOR UNIT ...
Page 40: ... 02 05 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL MODEL AO G36LETL ...
Page 45: ... 02 10 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL SOUND LEVEL CHECK POINT 8 2 ...