EXTERNAL INPUT & OUTPUT
11.
Connector
INPUT
OUTPUT
REMARKS
CN102
Control input
—
See external
input/output settings for
details.
CN103
—
Operation status output
CN6
—
Fresh air control output
EXTERNAL INPUT
11-1.
CONTROL INPUT (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
"Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Unit operation
Initial starting after turned power on
Other than initial starting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24°C
Temperature at previous operation
Air
fl
ow mode
AUTO
Mode at previous operation
Up-down air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Left-right air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
Indoor unit
control PC board
Connected unit
Ex.) Switch
Connector
1
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
*10 m
Contact capacity : 5VDC or more, 15mA or more.
Please use the non-polar relays and switches.
When function setting is "Operation/Stop" mode
●
Input signal
Indoor unit
Operation
Stop
ON
OFF
When function setting is "Forced stop" mode
●
ON
ON
ON
Remote control
operation invalidity
Remote controller
Input signal
Indoor unit
Command
ON
OFF
Operation
Stop
Forced stop
Normal
Parts (Optional)
Model name
UTY-XWZX
Wire (External input)
Summary of Contents for AB G30LRTE Series
Page 2: ...1 INDOOR UNIT CEILING TYPE AB G30LRTE AB G36LRTE DTR_AB037E_01 2013 02 28 ...
Page 34: ...DTR_AO135E_01 2013 02 28 SINGLE TYPE AO G30LETL AO G36LETL 2 OUTDOOR UNIT ...
Page 40: ... 02 05 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL MODEL AO G36LETL ...
Page 45: ... 02 10 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL SOUND LEVEL CHECK POINT 8 2 ...