4. INSTALLATION DIAGRAM

4” (10 cm) or over

24” (60 cm) or over

4” (10 cm) or over

8” (20 cm) or over

10” (25 cm) 
or over

[OUTDOOR UNIT]

Outdoor unit to be fasten with bolts at the four places without fail.

21

9/32”(54 cm)

11

13/32 (29 cm)

•  

Do not directly install it on the ground, otherwise it will cause failure.

•  

To obtain better operation ef

fi

 ciency, when the outdoor unit is installed, be sure to open 

the front and left side.

 CAUTION

In places where the outdoor temperature drops to 32 °F (0 °C) or lower, the drain water 
may freeze and may stop up the drain or cause other outdoor unit trouble. Therefore 
take measures so that the drain water will not freeze and clog the drain.

Please set up the outdoor unit in a high place and please do not arrange the frame of 
installed stand under the drain port, because the water dropped from the drain port repeats 
freezing and accumulating, and may block the drain port.

In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with snow, 
it might become dif

fi

 cult to get warm and it is likely to because of the breakdown. Please 

construct a canopy or baf

fl

 e board. (local con

fi

 gured).

5. INSTALLATION 

5.1. Connector cover remove

Connector cover removal

•  Remove the tapping screw.

Installing the connector cover

(1)  After inserting the 

fi

 ve hooks, then push upward.

(2)  Tighten the tapping screw.

Always use the screws as shown above.

Tapping screw

Connector cover

Hooks

Hook

2.5. Additional charge

Refrigerant suitable for a piping length of 49ft (15m) is charged in the outdoor unit at the 
factory.
When the piping is longer than 49ft (15m), additional charging is necessary.
For the additional amount, see the table below.

Pipe length

49 ft (15 m)

66 ft (20 m)

Rate

Additional refrigerant

None

+3.5 oz (+100 g) 0.2 oz/ft (20 g/m)

 CAUTION

When adding refrigerant, add the refrigerant from the charging port at the completion 
of work.

2.6. Operating range

Outdoor temperature

Cooling/Dry Mode 

About 14 to 115 °F 

Heating Mode

About -15 to 75 °F

2.7. Accessories

Installation manual

1

One set of following parts are necessary installation of this product.

Name

Connection pipe assembly

Decorative tape

Saddle

Tapping screws

Connection cable

Vinyl tape

M10 bold, nut

Sealant

Wall pipe

Wall cap

3.  SELECTING THE MOUNTING POSITION

•  Decide the mounting position with the customer as follows.
•  Do not set to a place where there is oily smoke, oil is used in the factory, the unit can 

contact sea breeze, sul

fi

 de gases will be generated in the hot spring area, corrosive 

gases will be generated, animal may urine on the unit and ammonia will be generated 
and a dusty place.

3.1. Outdoor unit

(1) If possible, do not install the unit where it will be exposed to direct sunlight. 

(If necessary, Install a blind that does not interfere with the air 

fl

 ow.)

(2)  Do not install the unit where a strong wind blows or where it is very dusty.
(3) Do not install in an area that has heat sources, vapors, or the risk of leakage or 

accumulation of 

fl

 ammable gas.

(4)  Do not install the unit where people pass.
(5)  Take you neighbors into consideration so that they are not disturbed by air blowing 

into their windows or by noise.

(6)  Provide the space shown in 

fi

 gure so that the air

fl

 ow is not blocked. Also for ef

fi

 cient 

operation, leave open three of the four directions front, rear, and both sides.

(7)  Install the unit where keep away more than 3 m from the antenna of TV set and Radio.
(8)  Outdoor unit should be set to a place where both drainage and itself will not be 

affected when heating.

 WARNING

Install at a place that can withstand the weight of the outdoor units and install positively 
so that the units will not topple or fall.

Install the unit where it will not be tilted by more than 5°.

When installing the outdoor unit where it may exposed to strong wind, fasten it 
securely.

 CAUTION

Do not install where there is the danger of combustible gas leakage.
Do not install near heat sources.
If children may approach the unit, take preventive measures so that they cannot reach 
the unit.

9379069649_IM.indb   3

9379069649_IM.indb   3

12/8/2014   2:04:44 PM

12/8/2014   2:04:44 PM

Summary of Contents for 9RLS3H

Page 1: ...rvicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct operation to the customer using th...

Page 2: ...r for HFC refrigerant R410A Copper pipes It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg 10 m Do not use copper pipes having a collapsed deformed or discolored portion especially on the interior surface Otherwise the expansion value or capillary tube may become blocked with contaminants As an air conditioner using R410A incurs pre...

Page 3: ...door temperature Cooling Dry Mode About 14 to 115 F Heating Mode About 15 to 75 F 2 7 Accessories Installation manual 1 One set of following parts are necessary installation of this product Name Connection pipe assembly Decorative tape Saddle Tapping screws Connection cable Vinyl tape M10 bold nut Sealant Wall pipe Wall cap 3 SELECTING THE MOUNTING POSITION Decide the mounting position with the cu...

Page 4: ...will not be able to compress 1 Remove the tapping screw then remove the control box cover 2 Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut 3 Connect inter unit wire harness and power supply to the terminal 4 Use the tapping screw to install the control box cover NOTE Connector trade size for this unit is 1 2 12 7 mm The connector can be bought at a har...

Page 5: ...ation in order to ensure compressor protection BENDING PIPES 1 When bending the pipe be careful not to crush it 2 To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 70 mm or over 3 If the copper pipe is bend the pipe or pulled to often it will become stiff Do not bend the pipes more than three times at one place Holding spanner 90 Body side Torque wrench ...

Page 6: ...nnot start if the MANUAL AUTO button is not kept on pressing for more than 10 sec onds 2 Close the valve stem of 2 way valve completely 3 Continue the forced cooling operation for 2 to 3 minutes then close all the valve stems on the 3 way valves 4 Stop the operation Press the START STOP button of the remote controller to stop the operation Press the MANUAL AUTO button when stopping the operation f...

Reviews: