En-2

3. 2.  External Output

3. 2. 1. Operation Status Output

• An air conditioner operation status signal can be output.

Circuit diagram example

Indoor unit

PC board of 

communication kit

Connector

Blue

Purple

Connected unit

Ex.) Relay unit

~24V DC

Ex.) Display

Relay 

Power 

supply

10m *

Signal

Field supply

* Make the distance from the PC board to the connected unit within 10m. 

Relay spec.

 

: Max.24V DC, 10mA to less than 500mA.

Indoor unit

Output signal

Stop

OFF

Operation

ON

NOTE

• Only operation and stop signals will be output. 

Use the remote controller to check the operation mode, temperature, and airflow.

3. 2. 2. Error Status Output

• An air conditioner condition normal/error status signal can be output.

Circuit diagram example

Indoor unit

PC board of 

communication kit

Connector

Red

White

Connected unit

Ex.) Relay unit

~24V DC

Ex.) Display

Relay 

Power 

supply

10m *

Signal

Field supply

* Make the distance from the PC board to the connected unit within 10m. 

Relay spec.

 

: Max.24V DC, 10mA to less than 500mA

Error status

Output signal

Normal

OFF

Error

ON

NOTE

• Only error signals will be output. 

Check the error information on the display area of the main unit.

4.  CONNECTING TO INDOOR UNIT

• Connect the connector to the board of the air-conditioner. 

To connect to the air-conditioner, refer to the installation manual of the air-conditioner.

• Connect the tip of the wire to the external equipment. 

If necessary, extend it with locally procured wire.

• Ensure that the connecting part is insulated for protection.

9319446004_UTY-XWZXZ5_IM.indd   2