![Fuji Electric ROG07KMTA Design & Technical Manual Download Page 62](http://html.mh-extra.com/html/fuji-electric/rog07kmta/rog07kmta_design-and-technical-manual_2341725062.webp)
11. Safety devices
Type of
protection
Protection form
Model
ROG07KMTA
ROG09KMTA
Circuit protection
Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor
protection
Terminal protection
program
Activate
85—122 °C
Fan motor stop
Reset
77—114 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Type of
protection
Protection form
Model
ROG12KMTA
ROG14KMTA
Circuit protection
Current fuse (Main PCB)
250 V, 20 A
250 V, 5 A
Fan motor
protection
Terminal protection
program
Activate
85—122 °C
Fan motor stop
Reset
77—114 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
DESIGN & TECHNICAL MANUAL
- 58 -
OUTDOOR UNIT
ROG07-14KMTA