(UURU,QGLFDWLRQV
'LVSOD\'XULQJ(TXLSPHQW(UURU
7KLVFRQWUROOHUKDVDGLVSOD\IXQFWLRQWRLQGLFDWHVHYHUDOW\SHVRIHUURUFRGHVKRZQEHORZ,IDQ\RIWKH
error code is displayed, please eliminate the cause of error immediately. After the cause is eliminated,
WXUQRIIWKHSRZHURQFHDQGWKHQUHVWDUWWKHFRQWUROOHU
Display
Possible cause
Control output
"
"
(1) Thermocouple burnout.
(2) Resistance bulb sensor (A) burnout.
39H[FHHGVXSSHUOLPLWRIWKHUDQJH
by 5%FS.
7KHFRQWUROOHURXWSXWVWKHVSHFL¿HG
value for an error. (The value can be
set in parameter Flo1 or Flo2)
"
"
5HVLVWDQFHEXOEVHQVRU%RU&ZLUH
burnout.
5HVLVWDQFHEXOEVHQVRUEHWZHHQ$
& B or A & C) short.
39LVEHORZORZHUOLPLWRIWKHUDQJH
by 5%FS.
(4) Burnout or short in the voltage
input.
"
"
39
Control operation is continued
Note) Control operation is continued
as long as the accuracy is above
-5%FS.
When the accuracy declines
WR EH ORZHU WKDQ )6 WKH
controller outputs the specified
value for an error.
"
69ÀLFNHUV
Incorrect setting (Pvb/PvF)
The controller outputs the specified
value for an error. (The value can be
set in parameter Flo1 or Flo2)
PV is not displayed
Check the set value of DSPT.
Normal control
* The controller does not have to be
restarted
SV is not displayed
Check the set value of DSPT.
Normal control
* The controller does not have to be
restarted
Parameters may not be displayed
Check the settings of Ch11 DSP.
Normal control
* The controller does not have to be
restarted
"
", "
", "
"
Alarm 1, alarm 2, or alarm 3 is occurred
XQGHUWKHFRQGLWLRQWKDW$/0)LVVHWWR
1 or 3.
Normal control
"
"
The number that relay has operated
UHDFKHG WKH 5<&1 UHOD\ FRQWDFW OLIH
OLPLWXQGHUWKHFRQGLWLRQWKDW$/0)LV
set to 1 or 3.
Normal control
"
"
The number of days that the device
has operated reached the oPtM (upper
limit of operating days) under the
FRQGLWLRQWKDW$/0)LVVHWWRRU
Normal control
,QSXW5DQJHDQG&RGHVVWDQGDUGUDQJH
Input type
Input code
(PVT)
Measurement
range
(°C) (PVb, PVF)
Minimum
input
increment
(°C)
Measurement
range
(°F) (PVb, PVF)
Minimum
input
increment
(°F)
RTD
JIS (IEC)
JPt 100
JPT1
0.0 to 150.0
0.1
32.0 to 302.0
0.1
JPT2
0.0 to 300.0
0.1
32.0 to 572.0
0.1
JPT3
0.0 to 500.0
0.1
32.0 to 932.0
0.1
JPT4
0.0 to 600.0
0.1
32 to 1112
1
JPT5
-50.0 to 100.0
0.1
-58.0 to 212.0
0.1
JPT6
-100.0 to 200.0
0.1
-148.0 to 392.0
0.1
JPT7
-199.9 to 600.0
0.1
-328 to 1112
1
Pt 100
PT1
0.0 to 150.0
0.1
32.0 to 302.0
0.1
PT2
0.0 to 300.0
0.1
32.0 to 572.0
0.1
PT3
0.0 to 500.0
0.1
32.0 to 932.0
0.1
PT4
0.0 to 600.0
0.1
32 to 1112
1
PT5
-50.0 to 100.0
0.1
-58.0 to 212.0
0.1
PT6
-100.0 to 200.0
0.1
-148.0 to 392.0
0.1
PT7
-199.9 to 600.0
0.1
-328 to 1112
1
PT8
-200 to 850
1
-328 to 1562
1
Thermocouple
J
J1
0.0 to 400.0
0.1
32.0 to 752.0
0.1
J2
-20.0 to 400.0
0.1
-4.0 to 752.0
0.1
J3
0.0 to 800.0
0.1
32 to 1472
1
J4
-100 to 1000
1
-148 to 1832
1
K
K1
0 to 400
0.1
32 to 752
0.1
K2
-20.0 to 500.0
0.1
-4.0 to 932.0
0.1
K3
0.0 to 800.0
0.1
32 to 1472
1
K4
-200 to 1300
1
-328 to 2372
1
R
R
0 to 1700
1
32 to 3092
1
B
B
0 to 1800
1
32 to 3272
1
S
S
0 to 1700
1
32 to 3092
1
T
T1
-199.9 to 200.0
0.1
-199.9 to 392.0
0.1
T2
-199.9 to 400.0
0.1
-199.9 to 752.0
0.1
E
E1
0.0 to 800.0
0.1
32 to 1472
1
E2
-150.0 to 800.0
0.1
-238 to 1472
1
E3
-200 to 800
1
-328 to 1472
1
/
/
-100 to 850
1
-148 to 1562
1
U
U1
-199.9 to 400.0
0.1
-199.9 to 752.0
0.1
U2
-200 to 400
1
-328 to 752
1
N
N
-200 to 1300
1
-328 to 2372
1
W
W
0 to 2300
1
32 to 4172
1
3/,,
3/
0 to 1300
1
32 to 2372
1
DC voltage
0 to 5 V DC
0-5V
-1999 to 9999
5DQJHZKHUH
scaling is
DOORZHG
—
-1999 to 9999
5DQJHZKHUH
scaling is
DOORZHG
—
1 to 5 V DC
1-5V
0 to 10V DC
0-10
2 to 10V DC
2-10
0 to 100mV DC
MV
DC current
0 to 20 mA DC
0-20
4 to 20 mA DC
4-20
6HWWLQJWKH7HPSHUDWXUH&RQWUROOHU
,QSXW6HWWLQJ
Set the type and the range for input sensor. Input can be set in the setup menu ("
"].
For more on input types, input scaling, decimal point location, and input codes, see "10 Input Range
and Codes (standard range)". (page 19)
1.
Choose an input type ("
")
Check the type of the thermocouple or resistance bulb which is used.
2.
Set the PV scaling (input range) ("
"/"
")
Set Pvb to the lower limit of the temperature range and PvF to the upper limit. It is recommended
to set the values at the standard range, even though they can be set at values beyond of it.
There is no standard range for DC voltage or DC current input. (-1999 to 9999, lower limit<upper limit)
3.
Set the decimal point location ("
")
Sets whether or not to display digits after the decimal point. Two digits can also be dis-
played after the decimal point when using 1 to 5V DC, and 4 to 20mA DC.
Point
39VFDOLQJDQGGHFLPDOSRLQWORFDWLRQFDQEHXVHGZLWKWKHIDFWRU\VHWWLQJV
2XWSXW6HWWLQJ
6HWVWKHFRQWURORXWSXW2QO\ZKHQWKHRXWSXWLVFXUUHQWRUYROWDJH
1.
Sets the range of the control output (OUT1, OUT2) ("
"
")
"
Choose any of 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V, 0 to 20mA or 4 to 20mA DC.
&RQWURO6HWWLQJ
Sets controls to normal operation or reverse operation.
Ɣ5HYHUVHRSHUDWLRQ$VWKHSURFHVVYDOXH39ULVHVWKHFRQWURORXWSXW09EHFRPHVVPDOOHU8VHG
WRKHDWWKHFRQWUROREMHFW
Ɣ1RUPDORSHUDWLRQ$VWKHSURFHVVYDOXH39ULVHVWKHFRQWURORXWSXW09EHFRPHVODUJHU8VHGWR
FRROWKHFRQWUROREMHFW
1.
Set the normal or reverse operation ("
")
Choose any of the following combinations of heat and cool to suit your system.
rEv
Control
output 1
Control
output 2
rv--
Reverse
–
no--
Normal
–
rvno
Reverse
Normal
norv
Normal
Reverse
rvrv
Reverse
Reverse
nono
Normal
Normal
- 19 -