![Fuji Electric PXF4 Instruction Manual Download Page 11](http://html1.mh-extra.com/html/fuji-electric/pxf4/pxf4_instruction-manual_2341808011.webp)
&+6(7VHWXSSDUDPHWHUV
3DUDPHWHU
)XQFWLRQ
6HWWLQJUDQJH
,QLWLDOYDOXH
5HPDUNV
ʋ
'LVSOD\
1DPH
530
PV input type
Sets the type of input sensor
JPT1: 0.0 to 150.0°C
JPT2: 0.0 to 300.0°C
JPT3: 0.0 to 500.0°C
JPT4: 0.0 to 600.0°C
JPT5: -50.0 to 100.0°C
JPT6: -100.0 to 200.0°C
JPT7: -199.9 to 600.0°C
PT1: 0.0 to 150.0°C
PT2: 0.0 to 300.0°C
PT3: 0.0 to 500.0°C
PT4: 0.0 to 600.0°C
PT5: -50.0 to 100.0°C
PT6: -100.0 to 200.0°C
PT7: -199.9 to 600.0°C
PT8: -200 to 850°C
J1: 0.0 to 400.0°C
J2: -20.0 to 400.0°C
J3: 0.0 to 800.0°C
J4: -100 to 1000°C
K1: 0 to 400°C
K2: -20.0 to 500.0°C
K3: 0.0 to 800.0°C
K4: -200 to 1300°C
R: 0 to 1700°C
B: 0 to 1800°C
S: 0 to 1700°C
T1: -199.9 to 200.0°C
PT2: -199.9 to 400.0°C
E1: 0.0 to 740.0°C
E2: -150.0 to 740.0°C
E3: -200 to 740°C
/WR&
U1: -199.9 to 400.0°C
U2: -200 to 400°C
N: -200 to 1300°C
W: 0 to 2300°C
3/WR&
0-5 V: 0 to 5 V
1-5 V: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
MV: 0 to 100 mV
0-20: 0 to 20 mA
4-20: 4 to 20 mA
K1
[RESET]
Refer to section 10 for the detail.
531
39LQSXWORZHUOLPLW
6HWVWKHORZHUOLPLWRI39LQSXW
-1999 to 9999
0
[RESET]
532
PV input upper limit
Sets the upper limit of PV input
-1999 to 9999
400
[RESET]
533
Decimal point position
Sets the decimal point position for the PV/SV
0: No digit after decimal point
1: 1 digit after decimal point
2: 2 digit after decimal point
3: 3 digit after decimal point
0
[RESET]
535
6TXDUHURRWH[WUDFWRUFXWSRLQW
Sets the cut point for square root calculation.
-0.1 to 105.0(%)
-0.1%
536
PV input shift
Sets the amount of shift for PV input
-10 to 10%FS
0.00%FS
538
39LQSXW¿OWHU
6HWVWKHWLPHFRQVWDQWIRUWKH39LQSXW¿OWHU
0.0 to 120.0 sec
5.0 sec
543
5HPRWH69]HURDGMXVWPHQW
$GMXVWVWKH]HURVLGHRIUHPRWH69
-50 to 50%FS
0.00%FS
544
5HPRWH69VSDQDGMXVWPHQW
$GMXVWVWKHVSDQVLGHRIUHPRWH69
-50 to 50%FS
0.00%FS
545
Remote SV input range
Sets the range for remote SV input.
0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
1-5V
546
5HPRWH69LQSXW¿OWHU
6HWVWKHWLPHFRQVWDQWIRUWKH569LQSXW¿OWHU
0.0 to 120.0 s
0.0 s
547
OUT1 range
Sets the range of the control output 1(OUT1)
0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
0-20: 0 to 20 mA
4-20: 4 to 20 mA
0-10 (voltage)
4-20 (current)
'LVSOD\HGZKHQ287LVFXUUHQWRUYROWDJHRXWSXW
548
OUT2 range
Sets the range of the control output 2(OUT2)
0-5v: 0 to 5 V
1-5v: 1 to 5 V
0-10: 0 to 10 V
2-10: 2 to 10 V
0-20: 0 to 20 mA
4-20: 4 to 20 mA
0-10 (voltage)
4-20 (current)
'LVSOD\HGZKHQ287LVFXUUHQWRUYROWDJHRXWSXW
549
09GXULQJ)$/7
Sets the output value for the control output (MV1) during
)$/7
-5.0 to 105.0%
-5.0%
550
09GXULQJ)$/7
Sets the output value for the control output (MV2) during
)$/7
-5.0 to 105.0%
-5.0%
551
MV1 during Soft Start
Sets the value for the control output (MV1) during soft start
-5.0 to 105.0%
105.0%
553
Soft Start set time
6HWVWKHWLPHIURPVWDUWXSWRWKH¿QLVKRIVRIWVWDUW
00:00 to 99:59 (hour:min)
00:00
Be sure to set 0.00 during dual control.
554
MV1 during standby
Sets the value for the control output (MV1) during standby
-5.0 to 105.0%
-5.0%
555
MV2 during standby
Sets the value for the control output (MV2) during standby
-5.0 to 105.0%
-5.0%
556
Standby mode
Sets on/off of the alarm output during standby
$/0 2))$2 21
$/0 21$2 21
$/0 2))$2 2))
$/0 21$2 2))
0
[RESET]
557
AO
6HOHFWVZKDWWRWUDQVIHUWRWKHDQDORJRXWSXW
PV
SV
MV
DV
PFb: Not for use.
PV
558
$2ORZHUVFDOLQJ
6HWVWKH$2ORZHUVFDOLQJ
-100.0 to 100.0%
0.0%
559
AO upper scaling
Sets the AO upper scaling
-100.0 to 100.0%
100.0%
561
)L[HGYROWDJHYDOXH
6HWVWKHYROWDJHIRUFDOFXODWLQJHOHFWULFSRZHU
1 to 500V
100 (100 V)
562
&XUUHQWYDOXHIRUVLPSOHSRZHU
calculation
6HWVWKHFXUUHQWYDOXHIRUVLPSOHSRZHUFDOFXODWLRQ
0.0 to 100.0A
0 (0.0A)
564
'HFLDOSRLQWSRVLWLRQIRUHOHFWULFSRZHU
6HWVWKHSRVLWLRQRIGHFLPDOSRLQWIRUFDOFXODWLRQHGSRZHU
consumption.
0 : 0
1 : 0.1
2 : 0.01
3 : 0.001
1 : 0.1
Do not change it during calculation.
565
3RZHUIDFWRUIRUVLPSOHFDOFXODWLRQ
6HWVWKHSRZHUIDFWRUIRUVLPSOHFDOFXODWLRQ
0.00 to 1.00
1.00
566
Upper limit of relay contact operation
Sets the upper limit on the number of times a relay contact
FDQRSHUDWH,I\RXVHWLWWRQRDODUPZLOOEHJHQHUDWHG
0 to 9999
100
(100,000 times)
567
Upper limit of operating days
Sets the upper limit on the number of days the device
RSHUDWHV,I\RXVHWLWWRQRDODUPZLOOEHJHQHUDWHG
0 to 5000
3650 (3650 days)
- 11 -