background image

Temperature Controller MODBUS SIO Driver    

GP-Pro EX Device/PLC Connection Manual

20

„

External Device Settings

For External Device communication settings, use the SEL key, UP key, or DOWN key located in the operation 

area on the front of the controller.

Refer to your External Device manual for details.

1

Press and hold SEL key to display the 3rd block parameter.

2

Press UP key or DOWN key to display setting parameter.

3

Press SEL key.

4

Press UP key or DOWN key to display setting value.

5

Press SEL key.

6

Press and hold SEL key.

‹

Setting Value

Setting Parameter

Setting Value

Setup Description

STno

1

Station No.

CoM

0

Parity setting

PCoL

1

Communication protocol

Summary of Contents for PUM Series

Page 1: ...ture Controller MODBUS SIO Driver 1 System Configuration 3 2 External Device Selection 8 3 Communication Settings 9 4 Setup Items 25 5 Cable Diagrams 30 6 Supported Devices 71 7 Device Code and Addres...

Page 2: ...3 2 External Device Selection Select a model series of the External Device and its connection method 2 External Device Selection page 8 3 Communication Settings This section shows setting examples for...

Page 3: ...U RS 485 Digital input No 1 2 3 PC Loader Port on CPU Unit RS 232C Setting Example 3 page 13 Cable Diagram 1 page 30 Port on CPU Unit RS 422 485 2 wire Setting Example 4 page 15 Cable Diagram 3 page...

Page 4: ...US SIO Driver GP Pro EX Device PLC Connection Manual 4 Connection Configuration 1 1 Connection 1 n Connection Display External Device Display External Device External Device External Device Maximum nu...

Page 5: ...PS 3711A COM1 1 COM2 2 COM2 2 COM2 2 PS4000 3 3 When making communication between an External Device and COM port on the Expansion slot only RS 232C is supported However ER DTR CTS control cannot be e...

Page 6: ...DIP Switch The BOX Atom has not a switch to set the RS 232C RS 422 485 mode Use the BIOS for the setting 8 For the connection with the External Device on the user created cable read as if the connect...

Page 7: ...None 7 OFF Short circuit of SDA TXA and RDA RXA Not available 8 OFF Short circuit of SDB TXB and RDB RXB Not available 9 OFF RS RTS Auto control mode Disabled 10 OFF DIP Switch Setting Description 1 O...

Page 8: ...connect to the display Manufacturer Select the manufacturer of the External Device to connect Select Fuji Electric Co Ltd Series Select the External Device model series and the connection method Sele...

Page 9: ...GP Pro EX Settings Communication Settings To display the setup screen from the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dia...

Page 10: ...our External Device manual for details 1 Press SEL key 2 Press UP key or DOWN key to display COM 3 Press SEL key 4 Press UP key or DOWN key to display the setting parameter 5 Press SEL key to switch t...

Page 11: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 12: ...Device manual for details 1 Press SEL key 2 Press UP key or DOWN key to display COM 3 Press SEL key 4 Press UP key or DOWN key to display the setting parameter 5 Press SEL key to switch to setting mo...

Page 13: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 14: ...Driver GP Pro EX Device PLC Connection Manual 14 External Device Settings External Device communication settings are fixed as indicated below Setting Items Setting Value Communication speed 9600 Data...

Page 15: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 16: ...d hold SEL key to switch to Monitor Mode 2 Press and hold SEL key to switch to Setup Mode 3 Press UP key or DOWN key to display CoM Ch 9 4 Press and hold SEL key 5 Press UP key or DOWN key to display...

Page 17: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 18: ...t of the controller Refer to your External Device manual for details 1 Press and hold SEL key to display the 3rd block parameter 2 Press UP key or DOWN key to display setting parameter 3 Press SEL key...

Page 19: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 20: ...t of the controller Refer to your External Device manual for details 1 Press and hold SEL key to display the 3rd block parameter 2 Press UP key or DOWN key to display setting parameter 3 Press SEL key...

Page 21: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 22: ...ation switch on the front of the controller Refer to your External Device manual for details 1 Set 0 to Station No Configuration switch Other communication settings are fixed as below The Station Numb...

Page 23: ...rom the Project menu point to System Settings and select Device PLC Device Setting To display the Individual Device Settings dialog box from Device Specific Settings in the Device PLC window select th...

Page 24: ...dialog box 4 Click OK 5 Select the any mode in the Startup mode dialog box 6 Click OK 7 Select Control module Parameter Communication in the tree view of the main window 8 Click the setting item to di...

Page 25: ...ct Device PLC Setup Items Setup Description SIO Type Select the SIO type to communicate with the External Device In the communication setting confirm the serial interface specifications of the Display...

Page 26: ...y In case of no response from the External Device use an integer from 0 to 255 to enter how many times the Display retransmits the command Wait To Send Use an integer from 0 to 255 to enter standby ti...

Page 27: ...for 1 page in the off line mode depends on the Display in use Please refer to the Reference manual for details Setup Items Setup Description SIO Type Select the SIO type to communicate with the Exter...

Page 28: ...aits for the response from the External Device Retry In case of no response from the External Device use an integer from 0 to 255 to enter how many times the Display retransmits the command Wait To Se...

Page 29: ...to set from the displayed list and touch Option Setup Items Setup Description RI VCC You can switch RI VCC of the 9th pin when you select RS232C for SIO type It is necessary to change RI 5V by change...

Page 30: ...m to avoid short circuit loops Connect an isolation unit if the communication is not stable due to noise or other factors Cable Diagram 1 Display Connection Port Cable Notes GP3000 COM1 GP4000 1 COM1...

Page 31: ...ternal Device Display Display side D Sub 9pin External Device side 2 5 triple pole miniature jack Loader connecting cable Display side D Sub 9pin External Device side 2 5 triple pole miniature jack Lo...

Page 32: ...ble Cable length 500m or less 2D Online adapter by Pro face CA4 ADPONL 01 User created cable IPC 4 2E COM port conversion adapter by Pro face CA3 ADPCOM 01 Terminal block conversion adapter by Pro fac...

Page 33: ...OM Port page 5 5 Except GP 4203T 6 All GP4000 models except GP 4100 Series GP 4 01TM GP Rear Module GP 4201T and GP 4 03T 7 Except SP 5B00 8 When using a Terminal Block Conversion Adapter CA3 ADPTRM 0...

Page 34: ...name Display side Terminal Block CA3 ADPTRM 01 CA3 ADPCOM 01 Display Termination resistance 100 User created cable Shield SG External Device side Terminal Block Signal name 14 16 15 Pin TERMRX RDA RD...

Page 35: ...nal Device side Terminal Block RDA RDB SDA SDB SG ERA CSA ERB CSB FG Termination resistance 100 Termination resistance 100 Shield Shield Display Signal name 1 2 3 7 5 4 8 9 6 Shell Pin Display side D...

Page 36: ...Termination resistance 100 CA3 ADPTRM 01 CA4 ADPONL 01 Display TERMRX RDA RDB SDA SDB SG FG Signal name User created cable Shield Shield Display side Terminal Block SG Signal name 14 16 15 Pin Externa...

Page 37: ...01 Display Display side D Sub 9pin plug TERMRX RDA RDB SDA SDB SG FG Signal name 1 2 7 3 8 5 Shell Pin User created cable Shield Shield SG Signal name 14 16 15 Pin External Device side Terminal Block...

Page 38: ...splay SG External Device side Terminal Block Signal name 14 16 15 Pin Termination resistance 100 User created cable Shield SG External Device side Terminal Block Signal name 14 16 15 Pin TERMRX RDA RD...

Page 39: ...B FG Termination resistance 100 SG Signal name 14 16 15 Pin External Device side Terminal Block Termination resistance 100 Shield Shield Display Signal name 1 2 3 7 5 4 8 9 6 Shell Pin Display side D...

Page 40: ...F 2 OFF 3 ON 4 ON Shield Display Signal name SG Signal name 14 16 15 Pin External Device side Terminal Block RDA RDB SDA SDB SG ERA CSA ERB CSB Termination resistance 1 Termination resistance 100 Disp...

Page 41: ...tance 100 SG Signal name 14 16 15 Pin External Device side Terminal Block Termination resistance 100 Pin Signal name NC NC GND SG RS RTS 5V NC NC FG LINE LINE 3 8 1 2 5 4 6 7 9 Shell Display side D Su...

Page 42: ...SDB SG FG Signal name Display side Terminal Block PFXZCBADTM1 Display Termination resistance 100 User created cable Shield SG External Device side Terminal Block Signal name 14 16 15 Pin TERMRX RDA RD...

Page 43: ...ce PFXZLMCBRJR81 Display GND D0 D1 1 SG Signal name 14 16 15 Pin External Device side Terminal Block Termination resistance 100 Shield Display Termination resistance 220 1 4W GND D0 D1 1 User created...

Page 44: ...C FG Termination resistance 100 SG Signal name 14 16 15 Pin External Device side Terminal Block Termination resistance 100 Shield Shield Display Signal name 2 1 3 7 5 4 8 9 6 Shell Pin Display side D...

Page 45: ...ble Cable length 500m or less 3D Online adapter by Pro face CA4 ADPONL 01 User created cable IPC 4 3E COM port conversion adapter by Pro face CA3 ADPCOM 01 Terminal block conversion adapter by Pro fac...

Page 46: ...Terminal Block Conversion Adapter CA3 ADPTRM 01 instead of the RS 422 Terminal Block Conversion Adapter refer to Cable Diagram 3A 9 Only the COM port which can communicate by RS 422 485 2 wire can be...

Page 47: ...al Device side Terminal Block Signal name CA3 ADPTRM 01 CA3 ADPCOM 01 Display Termination resistance 100 User created cable Shield External Device side Terminal Block Signal name TERMRX RDA RDB SDA SD...

Page 48: ...DA SDB SG ERA CSA ERB CSB FG Termination resistance 100 External Device side Terminal Block Signal name Termination resistance 100 Shield Display Signal name 1 2 3 7 5 4 8 9 6 Shell Pin Display side D...

Page 49: ...RX RDA RDB SDA SDB SG FG Signal name User created cable External Device side Terminal Block Signal name Termination resistance 100 Shield Display side Terminal Block CA3 ADPTRM 01 CA4 ADPONL 01 Displa...

Page 50: ...FG Signal name 1 2 7 3 8 5 Shell Pin User created cable External Device side Terminal Block Signal name Termination resistance 100 Shield CA4 ADPONL 01 Display Display side D Sub 9pin plug TERMRX RDA...

Page 51: ...al Device side Terminal Block Signal name CA3 ADPTRM 01 CA3 ADPCOM 01 Display Termination resistance 100 User created cable Shield External Device side Terminal Block Signal name TERMRX RDA RDB SDA SD...

Page 52: ...ce side Terminal Block DATA DATA NC NC GND SG ERA CSA ERB CSB FG Termination resistance 100 Signal name Termination resistance 100 Shield Display Signal name 1 2 3 7 5 4 8 9 6 Shell Pin Display side D...

Page 53: ...Switch No Set Value 1 OFF 2 OFF 3 ON 4 ON Shield Display Signal name RDA RDB SDA SDB SG ERA CSA ERB CSB Termination resistance 1 External Device side Terminal Block Signal name Termination resistance...

Page 54: ...isplay Pin Signal name NC NC GND SG RS RTS 5V NC NC FG LINE LINE 3 8 1 2 4 6 7 9 Shell Display side D Sub 9pin plug 5 External Device side Terminal Block Termination resistance 100 Signal name Termina...

Page 55: ...nal Block External Device side Terminal Block Signal name PFXZCBADTM1 Display Termination resistance 100 User created cable Shield External Device side Terminal Block Signal name TERMRX RDA RDB SDA SD...

Page 56: ...45 RS 485 Cable 5m by Pro face PFXZLMCBRJR81 Display D0 D1 1 External Device side Terminal Block Signal name Termination resistance 100 Display Termination resistance 220 1 4W D0 D1 1 External Device...

Page 57: ...al Device side Terminal Block DATA DATA NC NC GND NC NC NC NC FG Termination resistance 100 Signal name Termination resistance 100 Shield Display Signal name 2 1 3 7 5 4 8 9 6 Shell Pin Display side D...

Page 58: ...ble Cable length 500m or less 4D Online adapter by Pro face CA4 ADPONL 01 User created cable IPC 4 4E COM port conversion adapter by Pro face CA3 ADPCOM 01 Terminal block conversion adapter by Pro fac...

Page 59: ...sed Except PE 4000B PS5000 IPC COM Port page 5 5 Except GP 4203T 6 All GP4000 models except GP 4100 Series GP 4 01TM GP Rear Module GP 4201T and GP 4 03T 7 Except SP 5B00 8 When using a Terminal Block...

Page 60: ...nal Block A B SG External Device side Terminal Block Signal name CA3 ADPTRM 01 CA3 ADPCOM 01 Display Termination resistance 100 User created cable Shield A B SG External Device side Terminal Block Sig...

Page 61: ...socket RDA RDB SDA SDB SG ERA CSA ERB CSB FG Termination resistance 100 A B SG External Device side Terminal Block Signal name Termination resistance 100 Shield Display Signal name 1 2 3 7 5 4 8 9 6 S...

Page 62: ...01 Display TERMRX RDA RDB SDA SDB SG FG Signal name User created cable A B SG External Device side Terminal Block Signal name Termination resistance 100 Shield Display side Terminal Block CA3 ADPTRM...

Page 63: ...RDB SDA SDB SG FG Signal name 1 2 7 3 8 5 Shell Pin User created cable A B SG External Device side Terminal Block Signal name Termination resistance 100 Shield CA4 ADPONL 01 Display Display side D Su...

Page 64: ...nal Block A B SG External Device side Terminal Block Signal name CA3 ADPTRM 01 CA3 ADPCOM 01 Display Termination resistance 100 User created cable Shield A B SG External Device side Terminal Block Sig...

Page 65: ...et DATA DATA NC NC GND SG ERA CSA ERB CSB FG Termination resistance 100 A B SG External Device side Terminal Block Signal name Termination resistance 100 Shield Display Signal name 1 2 3 7 5 4 8 9 6 S...

Page 66: ...e connectors DIP Switch No Set Value 1 OFF 2 OFF 3 ON 4 ON Shield Display Signal name RDA RDB SDA SDB SG ERA CSA ERB CSB Termination resistance 1 A B SG External Device side Terminal Block Signal name...

Page 67: ...isolated Shield Display Pin Signal name NC NC GND SG RS RTS 5V NC NC FG LINE LINE 3 8 1 2 5 4 6 7 9 Shell Display side D Sub 9pin plug Termination resistance 100 A B SG External Device side Terminal B...

Page 68: ...ck A B SG External Device side Terminal Block Signal name PFXZCBADTM1 Display Termination resistance 100 User created cable Shield A B SG External Device side Terminal Block Signal name TERMRX RDA RDB...

Page 69: ...face PFXZLMCBRJR81 Connect External Devices using side connectors Display GND D0 D1 1 A B SG External Device side Terminal Block Signal name Termination resistance 100 Display Termination resistance...

Page 70: ...in socket DATA DATA NC NC GND NC NC NC NC FG Termination resistance 100 A B SG External Device side Terminal Block Signal name Termination resistance 100 Shield Display Signal name 2 1 3 7 5 4 8 9 6 S...

Page 71: ...the Display s designated address is as follows Use the first digit of the Coil No 00001 10001 to designate the device 1 Device Set Device 2 Reference The list of available identifiers is displayed Cli...

Page 72: ...with without a decimal point about data item setting value ranges Device Bit Address Word Address 32bits Notes Read Only Word Data 30257 31407 1 2 1 Write disabled 2 This device is 32 bits in length...

Page 73: ...dress the Display reads the entire word sets the defined bit then returns the new word value to the External Device If the ladder program writes data to this word address during the bit write process...

Page 74: ...ata may be incorrect Word Data Engineering Unit 41001 00 41120 15 41001 41120 1 3 You can only set the Read Area Size for the system area available to use in the External Device Please refer to the GP...

Page 75: ...o the GP Pro EX Reference Manual for Read Area Size Cf GP Pro EX Reference Manual LS Area Direct Access Method Area Refer to the precautions on manual notation for icons in the table Manual Symbols an...

Page 76: ...Name Device Code HEX Address Code Read Only Word Data Internal 30 0001 Value of word address 1 Read Only Word Data Engineering Unit 31 0003 Value of word address 1 Word Data Internal 40 0000 Value of...

Page 77: ...rnal Device set with GP Pro EX Initial value PLC1 Error Message Displays messages related to an error that has occurred Error Occurrence Area Displays the IP address or device address of the External...

Reviews: