- 1 -
Instruction Manual
PG Interface Card "OPC-G1-PG"
Thank you for purchasing this PG interface card "OPC-G1-PG." Installing this card to your FRENIC-MEGA enables speed control with
speed sensor and pulse train input.
Installing this card disables pulse train inputs to the inverter's terminal [X7].
The FRENIC-MEGA has three option connection ports--A-, B-, and C-ports. Connect this PG interface card to the C-port.
Do not connect it to any other port.
1. Check that:
(1) A PG interface card and two screws (M3
×
8) are contained
in the package.
(2) The
PG
interface
card
is
not
damaged
during
transportation--no defective devices, dents or warps.
(3) The model name "OPC-G1-PG/SY" is printed on the back of
the PG interface card as shown in Figure 2. (The "PG/SY"
on the front is a short name, as shown in Figure 1.)
If you suspect the product is not working properly or if you
have any questions about your product, contact the shop
where you bought the product or your local Fuji branch office.
Figure 1 Front of Card
Figure 2 Back of Card
2. Installation
Before starting installation and wiring, turn OFF the power and wait at least five minutes for inverters with a capacity of 22 kW or
below, or at least ten minutes for inverters with a capacity of 30 kW or above. Make sure that the LED monitor and charging lamp are
turned OFF. Further, make sure, using a multimeter or a similar instrument, that the DC link bus voltage between the terminals P(+)
and N(-) has dropped to the safe level (+25 VDC or below).
Otherwise, electric shock could occur.
(1) Remove the front cover from the inverter and expose the control printed circuit board (control PCB). As shown in Figure 3, the
PG interface card can be connected to the C-port (CN6) only.
To remove the front cover, refer to the FRENIC-MEGA Instruction Manual, Section 2.3. For inverters with a capacity of 30
kW or above, open also the keypad enclosure.
(2) Insert connector CN1 on the back of the PG interface card (Figure 2) into the C-port (CN6) on the inverter's control PCB. Then
tighten the two screws that come with the card. (Figure 4)
Check that the positioning cutout (Figure 1) is fitted on the tab (
in Figure 4) and connector CN1 is fully inserted (
in
Figure 4). Figure 5 shows the PG interface card correctly mounted. Do not connect the PG interface card to the ports other
than C-port. Doing so may damage the card.
(3) Perform wiring on the PG interface card.
Refer to Section 3 "Wiring."
(4) Put the front cover back into place.
To put back the front cover, refer to the FRENIC-MEGA Instruction Manual, Section 2.3. For inverters with a capacity of 30
kW or above, close also the keypad enclosure.
Fit the positioning cutout of the card over the
tab on the inverter to determine the
mounting position.
Insert connector CN1 on the card into the
C-port (CN6) on the inverter's control PCB.
Figure 3 In the case of 0.4 kW
Figure 4 Mounting PG Interface Card
Figure 5 Mounting Completed
Screw hole (left)
Short name
Screw hole (right)
J1
CN1
Model name
Positioning cutout
Release knob
Tab