18
Operation of auxiliary switches(W) and alarm switches(K)
Molded Case Circuit Breakers
BW0 series
Internal accessories
Accessory
Auxiliary switch
Alarm switch
SPDT:
W
SPDT:
K
2PDT:
J
2PDT:
V
Handle position
ON
OFF
Trip
11/AXcL
12/AXbL
14/AXaL
11/AXcL
12/AXbL
14/AXaL
21/AXcR
22/AXbR
24/AXaR
91/ALcL
94/ALaL
92/ALbL
91/ALcL
94/ALaL
92/ALbL
01/ALcR
04/ALaR
02/ALbR
91/ALcL
94/ALaL
92/ALbL
91/ALcL
94ALaL
92/ALbL
01/ALcL
04/ALaL
02/ALbL
11/AXcL
12/AXbL
14/AXaL
11/AXcL
12/AXbL
14/AXaL
21/AXcR
22/AXbR
24/AXaR
Note: Ring mark indication
Ratings of auxiliary switches(W) and alarm switches(K)
Rated thermal
current (A)
Rated operational current (A)
Minimum load
current
AC
DC
Rated operational
Voltage (V)
Res. load
Ind. load
Rated operational
Voltage (V)
Res. load
Ind. load
5
24
5
5
24
4
3
5VDC 160mA
30VDC 30mA
48
5
5
48
2.5
1
125
5
3
125
0.4
0.4
250
3
2
250
0.2
0.2