background image

Section 2 

– Functional Description

 

 

                      FT742-DM (4-20mA) 

– Sensors

 - User Manual

 

2.2  Current Loops  

2.2.1 

Current Loop Characteristics  

The wind sensor incorporates two galvanically isolated 4-20mA current loop outputs, one loop for wind speed 
and one loop for wind direction. These current loop outputs can be converted into measurable output voltages 
with the addition of external resistors.  
 
Each loop should be powered from a DC supply in the range 12V to 30V. A positive supply must be provided to 
one of the current loop wires. The other wire must then be connected through a current meter to ground. This is 
because the current loops 

sink 

current, they do 

not

 source it. A common supply can be used if required. Loop 

connections are polarity insensitive so that the +ve or 

–ve loop supply connection can be made to either of the 

current loop connection pins. See example wiring in Section 4.4. 
 
The current loops are able to operate over long cable distances; however the overall loop resistance should not 
exceed the values given in Figure 2. It is recommended that twisted pair interconnection cabling should be 
used. The cable should also include an overall braided screen. 
 

Loop Supply  

Maximum Loop Resistance  

12V 

100 

Ω 

20V 

500 

Ω  

24V 

700 

Ω 

30V 

1000 

Ω 

Figure 2: Maximum Current Loop Resistance 

 
The 

wind sensor’s current loop outputs are updated at a rate of 10 times per second. An average of several 

readings should always be used for any calculations because single readings can accidentally become 
corrupted (see Section 2.2.6).  
 

2.2.2 

Using the Averaging Filter 

The sensor has an internal averaging filter enabled by default, which dampens the speed and wind direction 
outputs by averaging previous data values. By default this feature averages the last 16 readings (1.6s), this can 
be factory configured to values 0.1-6.4s in 0.1s increments. It is possible to disable the internal filter (but not 
recommended) via the Acu-Test Analogue test software. Contact FT technologies for further details. 
 
Selective Filter 
 
In addition to the averaging filter described above, the sensor has an optional feature called the Selective Filter 
that may improve data 

quality. The scheme allows the user to set a “validity period”, during which the sensor will 

exclude invalid readings from entering the averaging filter. The output will freeze on the last previous “good” 
reading and only raise an error flag (see Section 2.2.6) once the number of bad readings exceeds the validity 
period. This scheme can be enabled by factory configuration. The filter is turned off by default. 
 
 

2.2.3 

Wind Speed Loop 

The default wind speed scaling is such that a change from 4 to 20mA represents 0-75m/s. This corresponds to 
a scaling factor of 0.2133mA per m/s. The wind speed scaling factor can be factory programmed to the 
customer requirements, contact FT for further details. Figure 3 shows the available wind speed scalings. 
 
 
 
 
 
 
 
 

Summary of Contents for FT742

Page 1: ...7DX TEL 44 0 20 8943 0801 FAX 44 0 20 8943 3283 WEB www fttechnologies com E MAIL info fttechnologies com A4277 3 EN November 2017 The FT and Acu Res logos are registered trademarks of FT Technologies...

Page 2: ...aracteristics 9 2 2 2 Using the Averaging Filter 9 2 2 3 Wind Speed Loop 9 2 2 4 Wind Direction Loop 10 2 2 5 Changing the Wind Datum Direction 11 2 2 6 Error Conditions 12 2 3 Heater Operation 13 2 4...

Page 3: ...This product complies with the RoHS2 2011 65 EU directive limination du produit Conform ment la directive europ enne 2012 19 EU relative aux d chets d quipements lectriques et lectroniques DEEE ces co...

Page 4: ...1 Standards it must be o Connected to an appropriately approved isolated power supply for example UL CSA IEC 60950 1 2005 A1 2009 A2 2013 rated 12 30VDC and be current limited 6A Max o Protected by U...

Page 5: ...nnect une alimentation agr e convenablement isol e par exemple UL CSA IEC 60950 1 2005 A1 2009 A2 2013 de tension nominale 12 30 VCC et avec courant limit 6 A max o Prot g par des dispositifs de prote...

Page 6: ...trol applications The FT742 FF and FT742 PM ranges are designed for this application The standard FT742 DM when installed to FT Technologies recommendations is electrically isolated from the mounting...

Page 7: ...design The Purchaser assumes all risks and liability in conjunction with the use of the information given Any warranty given by FT Technologies in respect of the equipment is conditional upon the sens...

Page 8: ...for the sensor 2x current loops 4 20mA Supply Current Heater on 6A max 5 The heater is thermostatically controlled Heater power consumption will depend on the heater energy required to keep the senso...

Page 9: ...te of 10 times per second An average of several readings should always be used for any calculations because single readings can accidentally become corrupted see Section 2 2 6 2 2 2 Using the Averagin...

Page 10: ...lent to the maximum speed The wind speed loop can also be calibrated with non linear scaling functions For further information on this advanced feature contact FT Technologies If a wind sensor is repl...

Page 11: ...ion crosses the datum In the 12mA datum current mode the output current varies linearly about the 12mA value as the wind direction moves around the datum 2 2 5 Changing the Wind Datum Direction The da...

Page 12: ...cable or wind sensor It is important that error flags are not ignored The datalogger should be able to recognise and interpret error codes within the data If errors are ongoing more than several secon...

Page 13: ...e length FT recommends cable types in Section 3 2 Since the heater circuit is thermostatically controlled the actual power being drawn from the supply will depend on the programmed set point and the e...

Page 14: ...alignment marking and the alignment flat The magnetic North marking indicates 0 and rotates clockwise when viewed from above Figure 10 The alignment flat is used with a square sided compass for rotati...

Page 15: ...the annual inspection of the sensor as detailed in Section 4 2 The FT035 grounding accessory can be fitted within the connector chamber and can provide a low resistance grounding path to the outer ed...

Page 16: ...Chapter 3 Mechanical Electrical Installation 16 FT742 DM 4 20mA Sensors User Manual...

Page 17: ...Chapter 3 Mechanical Electrical Installation 17 FT742 DM 4 20mA Sensors User Manual Figure 9 Direct Mount Wind Sensor mm...

Page 18: ...DM 4 20mA Sensors User Manual The sensor measures the wind direction relative to the central datum feature When the wind sensor is correctly aligned the wind direction measurements will be as shown i...

Page 19: ...self locking fasteners 4x part FT034 ensuring an even distribution of pressure and firm contact with the mounting pipe The fixings use a thread locking insert and will provide resistance before they a...

Page 20: ...Chapter 3 Mechanical Electrical Installation 20 FT742 DM 4 20mA Sensors User Manual Figure 12 Direct Mount Compass Alignment...

Page 21: ...1 8 0mm ODU 4 20mA Cable Side Connector 8 way plug SX2F1C P08NJH9 0001 9 2mm Figure 14 Cable Connector Sourcing Options 3 2 Cable Details The mating connectors for the sensors are suitable for use wit...

Page 22: ...or is a minimum of 30x diameter of the interceptor material The standard FT742 DM sensor has a hard anodised top surface within the connector column housing see Figure 9 When used with the plastic pip...

Page 23: ...nclosure chassis All connections from the sensor to the data acquisition system and to power should pass through the SPD s This will suppress any unwanted overvoltage transients present on the signal...

Page 24: ...hydrophobic cavity coating for wear corrosion and damage Corrosion Inspect the mounting surface of the sensor and the surfaces of other mounting parts for signs of corrosion If corrosion is present o...

Page 25: ...FT031 Size Adaptor 25mm 1 for FT742 DM includes a FT033 tapered pipe insert 4x FT034 self locking fasteners FT032 Size Adaptor 50mm 2 for FT742 DM includes a FT033 tapered pipe insert 4x FT034 self lo...

Page 26: ...ocessed in accordance with guidelines in Sections 2 2 1 and 2 2 6 Check that the measurement cavity s special coating is in a satisfactory condition Debris can be blown out or washed out with distille...

Page 27: ...lied on a CD and will work on PCs running Windows XP Vista 7 8 8 1 and 10 The sensors can be easily tested by connecting a DC ammeter in series with each current loop A positive supply must be provide...

Page 28: ...Connect the green wire wind speed 4 20mA output to an ammeter and then connect the other terminal on the ammeter to the 0V terminal on the DC power supply 6 Connect the purple wire wind direction 4 2...