LON INTERFACE KEY
Kele • RUT-G Manual 2005 • www.kele.com • USA 888-397-5353 • International 901-382-6084
27
To enter data into a Plug-in screen:
1. Select the screen (NVI, NVO, etc.) to which the desired changes are to be made.
2. To change a value, click on the value window.
3. From the keyboard, enter a new value. The value will be entered in red.
4. The first value that is entered will enable the "Apply" button. It is not necessary to click the "Apply" button until
all desired value changes to the screen have been entered.
5.
If the "Apply" button is active, do not change screens or proceed to another NV. Doing so will lose all
new data entered on that screen. Always click the "Apply" button (if enabled) before changing screens
or NVs.
6. When all value changes to the screen have been made, click the "Apply" button. Or, if the changes are to be
discarded, click "Cancel."
7. The "Download" button will become visible. It is not necessary to click the "Download" button until all changes
have been made to all screens.
8. When all changes have been made and the "Apply" button used, click the "Download" button. All changes will
be transferred to the local processor in the Gateway.
9. Note that the NVI "Current Value" (data value) can be changed. If a value is entered for an NVI, the "Apply"
button will be enabled but the "Download" button is not required and is not displayed. The user-entered "Cur-
rent Value" will override the last network value until the next network value is received.
ENTERING DATA ON PLUG-IN SCREENS