Generator-Powered Operation
Generator-
powered opera-
tion
The power source is generator-compatible.
The maximum apparent power S
1max
of the power source must be known in order to
select the correct generator output.
The maximum apparent power S
1max
of the power source is calculated for 3-phase
devices as follows:
S
1max
= I
1max
x U
1
x √3
I
1max
and U
1
according to the device rating plate and technical data
The generator apparent power S
GEN
needed is calculated using the following rule of
thumb:
S
GEN
= S
1max
x 1.35
A smaller generator can be used when not welding at full power.
IMPORTANT!
The generator apparent power S
GEN
must not be less than the maximum
apparent power S
1max
of the power source!
NOTE!
The voltage delivered by the generator must never fall outside of the mains
voltage tolerance range.
The mains voltage tolerance is specified in the "Technical data" section.
47
EN-US
Summary of Contents for TransSteel 3000c Pulse
Page 2: ......
Page 18: ...18...
Page 19: ...General information 19...
Page 20: ...20...
Page 27: ...Operating controls and connections 27...
Page 28: ...28...
Page 39: ...Installation and Startup 39...
Page 40: ...40...
Page 46: ...3 4 IMPORTANT Tie the phase conductors near the block terminal using cable ties 46...
Page 58: ...58...
Page 59: ...MIG MAG welding 59...
Page 60: ...60...
Page 79: ...TIG welding 79...
Page 80: ...80...
Page 86: ...86...
Page 87: ...Manual Metal Arc Welding 87...
Page 88: ...88...
Page 92: ...92...
Page 93: ...Easy Documentation 93...
Page 94: ...94...
Page 99: ...Setup Settings 99...
Page 100: ...100...
Page 115: ...Troubleshooting and Maintenance 115...
Page 116: ...116...
Page 125: ...Appendix 125...
Page 126: ...126...
Page 137: ...137 EN US...
Page 138: ...138...
Page 139: ...139 EN US...