42
Optional
As an option, you can also install a commercially-available overvoltage protection in the
Fronius DC Box 60/12.
Technical Data
Abbreviations
and Descriptions
Used
Max. input voltage in no-load operation
850 V
Max. input current
60 A
Max. input current per fuse holder
20 A
Max. number of strings (with integrated module fuse)
12
Max. cable cross section for terminals on the solar module side
6 mm²
Max. cable cross section for terminals on the inverter side
95 mm²
Screw joint for cable attachment to the solar module side
M16
Screw joint for cable attachment to the inverter side
M32
Protection type
IP 55
Protection class
II
Ambient conditions
-25 °C - +60 °C
-13 °F - +140 °F
Dimensions (without screw joints)
500 x 350 x 145 mm
19.7 x 13.8 x 5.7 in.
Weight
5,9 kg
13.01 lbs.
DC cable ‘OUT’
DC output cable from Fronius DC Box 60/12 to inverter.
The polarity of the DC cable ‘OUT’ depends on how the solar
module strings are connected to the Fronius DC Box 60/12..
DC cable ‘IN’
Solar module strings from the solar modules to the Fronius DC
Box 60/12.
Each solar module string has one DC+ cable and one
DC- cable.