Notes regarding DC connection

General com-
ments regarding 
solar modules

To enable suitable solar modules to be chosen and to use the inverter as efficiently as pos-
sible, it is important to bear the following points in mind:
-

If insolation is constant and the temperature is falling, the open circuit voltage of the 
solar modules will increase. The open circuit voltage must not exceed 950 V.
If the open circuit voltage exceeds 950 V, the inverter will be destroyed and no war-
ranty claims will be entertained.

-

More exact values for dimensioning the solar modules can be provided by suitable cal-
culation programs, like the Fronius Solar.configurator (which can be downloaded from 
www.fronius.com).

DC connection 
area

The DC connection area is located on the 
lower area at the front of the inverter.

The DC cable is connected via a V-type ter-
minal or alternatively using an M12 cable 
lug.

IMPORTANT!

 Only the following cables 

may be connected to V-type terminals:
-

RE (round single-wire)

-

RM (round multi-strand)

-

SE (sector-shaped single-wire)

-

SM (sector-shaped multi-strand)

-

Fine-core cables, in conjunction with 
ferrules only

When connecting the DC cable using an 
M12 cable lug, fine-core cables are permit-
ted.

Connecting alu-
minium cables

Aluminium cables can also be connected to the DC connections.

Max. cross-sec-
tion of DC cables

When cabling from below, the max. cable cross-section of DC cables is 240 mm².

NOTE! 

Before connecting up the solar modules, check that the voltage for the so-

lar modules specified by the manufacturer corresponds to the actual measured 
voltage.

NOTE! 

After removing the lower 

cover, unplug the grounding cable 
from the cover.

NOTE! 

When connecting aluminium cables:

-

observe national and international guidelines regarding the connection of al-
uminium cables

-

follow the instructions of the cable manufacturer

-

Once a year, make sure that the cables are securely connected according to 
the specified torque.

Summary of Contents for Agilo TL

Page 1: ...g Perfect Welding Solar Energy 42 0426 0177 EN 001 18112014 Fronius Agilo TL Explanation of symbols and choice of location Notes regarding installation and connection Operating Instructions Grid conne...

Page 2: ...0...

Page 3: ...ction area 8 Connecting aluminium cables 8 Max cross section of AC cables 8 Fuse protection on alternating current side 8 Notes regarding DC connection 9 General comments regarding solar modules 9 DC...

Page 4: ...2...

Page 5: ...ided minor injury and or damage to property may result NOTE Indicates a risk of flawed results and possible damage to the equipment IMPORTANT Indicates tips for correct operation and other particularl...

Page 6: ...in places where there is an increased risk of damage from farm ani mals horses cattle sheep pigs etc in stables or adjoining areas in storage areas for hay straw chaff animal feed fertilisers etc Do n...

Page 7: ...are operated within their permitted operating ranges at all times Observe all the measures recommended by the solar module manufacturer to ensure long term retention of the solar module s properties...

Page 8: ...the AC DC cables and the data communication cables The maximum cable cross section for AC and DC cables is 240 mm In total 6 DC cables 6 DC cables and 6 AC cables 2x L1 2x L2 2x L3 can be fed into th...

Page 9: ...ixed to the base after placing it in the final position Fix the inverter in place on the base using at least 4 screws The fixing materials needed for this such as screws or wall plugs are not included...

Page 10: ...of the alternating current on the medium voltage side depends on the transformer available and is to be designed accordingly by the installation engineer IMPORTANT The resistance in the leads to the A...

Page 11: ...tively using an M12 cable lug IMPORTANT Only the following cables may be connected to V type terminals RE round single wire RM round multi strand SE sector shaped single wire SM sector shaped multi st...

Page 12: ...uses the following DC fuses Littelfuse SPFJ 125 160 200 A 1000 V According to national guidelines and standards the DC fuses can only be fitted in the DC string Tightening torque of the DC fuses 7 Nm...

Page 13: ...e protection for the DC side and the DC side as standard AC side 3 x Raycap Strikesorb 40 C 1 x Raycap Strikesorb 40 F in a Y circuit SPD Class I according to IEC 61643 1 SPD Type 2 according to UL 14...

Page 14: ...ontact 1 SC1 Relay contact 1 NO1 NO for relay contact 1 NC2 NC for relay contact 2 SC2 Relay contact 2 NO2 NO for relay contact 2 The relay outputs are not fuse protected Relay contacts can be assigne...

Page 15: ...on air conditioning can be activated 40 C max internal tem perature 40 C max internal tem perature 30 C 50 C max internal tem perature 50 C max internal tem perature 40 C Sig Rel NO alarm contact trip...

Page 16: ...DBY AC contactor is activated IN4 TOTAL SHUT DOWN AC and DC side shut down 4 Contact monitor ing IN5 IN6 IN7 External auxiliary contacts 24 V 10 mA IN5 Pre wired for DC overvoltage protection IN6 Exte...

Page 17: ...15 EN...

Page 18: ...d all addresses of our sales branches and partner firms Fronius International GmbH 4600 Wels Froniusplatz 1 Austria E Mail pv sales fronius com http www fronius com Fronius USA LLC Solar Electronics D...

Reviews: