2.3.3
Ventilation of boiler room
The openings for the supply air and the exhaust air should be arranged
as close to opposite each other as possible to achieve a good thermal
draught effect.
The supply air must be drawn in directly from outside. Exhaust air
must be discharged directly outside.
Provided they are not contradicted by the relevant building regulations
room where the boiler is to be installed, the following standards apply:
Applicable Standards:
- TRVB H 118
- ÖNORM H 5170
Provide a supply air cross-section of 2 cm
2
per kW of boiler rated output,
as per ÖNORM H 5170, but a total cross-section of at least 200 cm
2
2.3.4
Installing the heating system / Standards
The following standards govern the installation of heating systems:
Applicable standards:
ÖNORM / DIN EN 12828 Heating Systems in Buildings
Storage tank
NOTICE
A storage tank with the proper dimensions will guarantee the best boiler
operating values during the entire heating period.
Please contact your installer or Fröling directly for the right measurements for
the storage tank.
§
§