PTAC - Heat Pump and Electric Heat models_Full Back

Rearward Slope 

Front Panel 

Outside Wall 

1/4" Slope

Inside Wall 

Chassis

Acccessory 

Wall Sleeve 

Acccessory 

Outdoor Grille

16"

42"

PTAC Specifications

 Product Shipping Weight (approx.) – 132 Lbs.

 An electrical supply with grounded three-prong receptacle is 

required. The power supply circuit must be installed in accordance 

with current edition of National Electrical Code (ANSI/NFPA 70)  

and local codes & ordinances.  

 Voltage Rating – 230V / 208V / 60 Hz / 20 Amps

 Amps @ 230/208V Volts =  

(Cool) 5.1 / 5.3 Amps / (Electric Heater) 13.2 / 12.2 Amps

 Always consult local and national electric codes.

 Recommended Circuit Breaker – 20 Amps

 Unit equipped with 230/208V 3-wire power supply cord, NEMA plug 

type 6-20P, approximately 66" long.

 In order for condensate water to drain properly inside the unit, the 

sleeve must be installed properly: Level from right to left with a slight 

1/4" rearward pitch from the indoor side to the outdoor side as shown 

in the illustration above. Refer to the Installation Instructions on the 

web. 

New Installation

 For new installation, Frigidaire® PTAC Sleeves are available and 

recommended for proper installation. See accessories pages for 

sleeve options.*

 PTAC installation requires 13-13/16" maximum wall thickness.

Replacement Installation

 When replacing existing PTAC with new unit, refer to Product 

Installation Guide on web to identify existing wall-sleeve manufacturer 

and size compatibility. If proper installation and slope are suspect, 

then correct installation of Frigidaire® PTAC Sleeve options 

recommended. 

 For any sleeve retrofit application, be sure that the foam seals 

(factory-installed on the tube sheets) provide a good seal between 

the grille and the outdoor coil tube sheets. These foam seals provide 

a barrier that stops air from the inside mixing with air on the outside 

(known as air recirculation).

 Using Frigidaire® wall sleeve with Non-Frigidaire grille requires 

installation of an Accessory Baffle Kit, which ensures a good seal 

between the unit and exterior grille to prevent air recirculation. Air 

recirculation is a large contributor to performance loss and premature 

damage to major components. 

Note:  For planning purposes only. Refer to Product Installation Guide  

on the web at frigidaire.com for detailed instructions.

*See accessories pages attached for optional accessories. 

Specifications  

subject to change.

Plug Type (NEMA)

6-20P

Product Dimensions

Height
Width
Depth
Max. Wall Thickness

Manufacturer 

Wall Sleeve Part Number

General Electric

Amana
Trane

Friedrich

16"
42"
13-13/16"
13-13/16"

Metal Sleeve RAB71

Plastic Sleeve RAB77
Metal Sleeve WS900B
Metal Sleeve SLV149
T-Series Metal 11-1/2-in. Deep 

Wall Sleeve 
Standard-Depth Wall Sleeve 

16 X 42 X 13-3/4-in. PXWS

Wall Cutout Dimensions

Height 
Width

16-5/16"
42-3/16"

USA

 • 

10200 David Taylor Drive

 • 

Charlotte, NC 28262

 • 

1-866-942-1567

 • 

frigidaire.com

 

CANADA

 • 

5855 Terry Fox Way

 • 

Mississauga, ON L5V 3E4

 • 

1-866-942-1567

 • 

frigidaire.ca

FRP12ETT2R 06/11 

© 2011 Electrolux Home Products, Inc. 

Printed in the U.S.A.

PTAC

FRP12ETT2R    

Air Conditioner / Electric Heater 

Summary of Contents for PTAC FRP12ETT2R

Page 1: ...on Agency requirements Effortless Operation Simple intuitive room controls are easy for guests to operate ensuring a relaxing more comfortable stay Features like Effortless Restart and Ready Select controls reduce maintenance calls Effortless Temperature Control Frigidaire air conditioners maintain the preset room temperature so the room remains comfortable at all times and helps control energy le...

Page 2: ...electric codes Refer to Product Installation Guide for detailed installation instructions on the web at frigidaire com RAC P TAC Models Frigidaire Baseline B A C Accessories information available on the web at frigidaire com Plug Type NEMA 6 20P 1 Warranty 5 year sealed system 1 year full parts and labor Frigidaire R Normal no accessories A Seacoast no accessories S Normal w accessories B Seacoast...

Page 3: ...ility If proper installation and slope are suspect then correct installation of Frigidaire PTAC Sleeve options recommended For any sleeve retrofit application be sure that the foam seals factory installed on the tube sheets provide a good seal between the grille and the outdoor coil tube sheets These foam seals provide a barrier that stops air from the inside mixing with air on the outside known a...

Page 4: ...ir Volume CFM High Med Low Motor RPM High Med Low Air Direction Control UPC Code FEATURES Fin Coating Air Intake Low Voltage Start up Auto Fan Energy Saver 24 Hour On Off Timer Room Freeze Protection Random Restart Protection Quiet Start up Indoor Fan Speeds LED Display R410A 26 8 53 52 51 315 295 276 1100 1000 920 Auxiliary 2 way 0 12505 27602 6 Normal Fresh or Recycled Yes Yes Yes Yes Yes Yes Ye...

Reviews: