background image

Summary of Contents for FRS09PYC1

Page 1: ...84YW2 FRS184YC2 FRS18PYW2 FRS18PYC2 FRS224YW2 FRS224YC2 FRS22PYW2 FRS22PYC2 a c e r i a d i g i r f w w w m o c e r i a d i g i r f w w w All about the Installation of your Split Type Room Air Conditioner 7 6 5 1 2 4 9 6 6 8 1 a d a n a C 7 6 5 1 2 4 9 6 6 8 1 A S U ...

Page 2: ...smell etc immediately stop the operation disconnect the power cord and call an authorized Electrolux servicer 10 Do not operate the air conditioners with wet hands 11 Do not pull on the power cord 12 Do not drink any water that is drained from the air conditioners 1 Provide occasional ventilation during use Do not direct airflow at fireplaces or other heat related sources as this could cause flare...

Page 3: ...ric shock electric parts It may cause failure of 05 Safety precautions 3 Disconnect the power if strange machine electric shock or fire 2 Always ensure effective grounding No grounding may cause electric 4 Do not operate or stop the unit by 5 Do not operate with wet hands or in 6 Do not allow water to run into heating appliances It may cause fire and electric shock unspecified power cord It may ca...

Page 4: ... washed with a cloth dampened in a solution of warm water and mild dishwashing detergent Rinse thoroughly and wipe dry Wring excess water from cloth before wiping around controls Clean filter once every two weeks inlets or inside of air outlet It may cause failure of appliance or accident concern of damage due to falling of unit due to prolonged exposure If bracket damages there will be the outdoo...

Page 5: ...cial environmental conditions 7 Laundry rooms Choosing the installation site the unit at one of these sites please consult your local distributor beforehand 1 Sites with machine oil Choosing the installation site 06 07 1 Carefully read the installation manual before beginning 2 Follow each step as shown 3 Observe all local state and national electric codes This appliance must be installed by a qua...

Page 6: ...oosing the installation site 08 8 The site must allow for the easy removal of the connector pipe and drain hose 9 The unit must be installed at a site protected from direct sunlight Indoor Unit 1 The unit must be installed at a site that does not obstruct the flow of air 2 The site must support the weight of the indoor unit 3 The site must be easily accessible for maintenance and replacement of th...

Page 7: ......

Page 8: ...explanation purposes only 4 3 1 Indoor unit Outdoor unit 5 6 Air filter More A B C 2 Copper tubes must be insulated independently More than 6 6 More than 1 More than 1 65 than 1 65 More than 6 More than 6 More than 6 2 6 8 7 Parts list 10 ...

Page 9: ...6 or more hole right Ø 2 56 6 or more 3 39 4 21 12000 Btu s Indoor unit installation Installation plates and dimensions 3 39 4 21 Refrigerant pipe hole right Ø 2 56 Refrigerant pipe hole right Ø 2 56 from the wall 6 or more Installation plate the ceiling 6 or more from Refrigerant pipe hole right Ø 2 56 Indoor unit outline from the wall 6 or more A B Indoor unit installation 11 ...

Page 10: ...it the Installation Plate and drill holes in the wall according to the wall structure and corresponding mounting points on the installation plate Dimensions are in mm unless otherwise stated Wall Indoor unit Outdoor unit in the figures above A type screws wall with eight hole for the pipes using the pipe hole so that it is tilted slightly opening when drilling similar walls create 0 2 0 2 0 28 4 A...

Page 11: ...at the back of the indoor unit on the upper hook of the installation plate move the indoor unit from side to side to see that it is securely hooked Upper hook Lower hook Fastening the Indoor Unit Do not put the end of drain hose into water Do not block water flow by a rise Do not block water flow by a rise piping Pipe cover left Pipe holder Pipe cover right Right piping Connective pipe Indoor unit...

Page 12: ... wiring 7 Run the drain hose sloped downward to drain out the condensed water smoothly Cushioning material 3 Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping 4 Push the lower part of the indoor unit up on the wall Then move the indoor unit from side to side up and down to check if it is hooked secure...

Page 13: ... windy 4 If the installation site is exposed to heavy winds such as in coastal areas place the unit along the widest part of the wall or use protective plates Outdoor unit installation Strong wind Outdoor unit installation 3 Install the unit at the site where it is exposed to as little wind as possible schrubs or bushes blocks radiating air including 15 5 Be sure there is no obstacle which ...

Page 14: ...on Drainage Plug Condensate drainage of outdoor unit no for cooling only The condensate and defrosting water formd during heating in the outdoor unit can be properly discharged by drainage pipe Installation method Insert the drain connection into one of the 25 holes of the chassis and then connect drainage pipe with drain nozzle Insert drainage plugs into the other holes Only for 12000Btu s Chassi...

Page 15: ...rs from the cut cross section of pipe tube tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing indoor and outdoor unit then put them on pipe tube having possible to put them on after flaring work Refrigerant piping connection Refrigerant piping connection Pipe Correct Wrong Oblique Roughness Burr Pipe Reamer Point down Flare nut Cooper tube Remove...

Page 16: ... Bar pipe Handle Clamp handle Yoke Red arrow mark Flare nut Pipings Indoor unit tubing Copper A inch Max Min DIAMETER inch 0 051 0 063 0 071 0 095 0 028 0 039 0 039 0 087 2 Screw the flare nut with your fingers and then tighten it with a spanner and torque wrench as shown in the following figure ADDITIONAL TIGHTENING DIAMETER inch Firmly hold copper pipe in a 1 4 3 8 1 2 5 8 1 4 3 8 1 2 5 8 TORQUE...

Page 17: ... Breaker Amps MOCP Connecting Power and Control Cable The main power is supplied to the outdoor unit The field supplied connecting cable from the outdoor unit to indoor unit consists of four wires and provides the power for the indoor unit as well as the communication signal and ground between the outdoor and indoor unit Two wires are high voltage AC power one is low voltage DC signal and one is a...

Page 18: ...ing the screw 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoors respectively 5 Wrap those cables not connected with terminals with insulation tapes so that they will not touch any electrical components Secure the cable onto the control board with the cord clamp Connect the cable to the indoor unit Electrical work cover Electrical box designation 16AWG or...

Page 19: ...1 ...

Page 20: ...eans for disconnection from a power supply shall be incorporated in each active phase conductors Caution After the confirmation of the above conditions prepare the wiring as follows Air purging below 1 Pressure in the system rises 2 Operating current rises 4 Moisture in the refrigerant circuit may freeze and block capillary tubing 5 Water may lead to corrosion of parts in the refrigeration system ...

Page 21: ...packed valve Open the valve stem until it hits against 2 Operation of closing packed valve Securely tighten the valve stem with a special tool Then securely tighten the valve stem cap with a spanner or the like Refer to 23 Flare nut Stopper Cap Valve stem Charge port Valve body Caution in handling the packed valve integrated in the outlets of outdoor unit for valve stem cap tightening torque tight...

Page 22: ... This procedure verifies if the refrigerant goes through the tubes correctly o manifold valve to the vacuum pump seconds after the gas comes 5 Make evacuation for 15 minutes or more and check that the compound meter indicates 7 6 x 10 MicronsHg 1x10 Pa 5 1 Completely tighten the flare nuts at connection point A B C and D Connect valve core removal tool to the charging port then connect vacuum hose...

Page 23: ...unit check point Cover indoor unit check point 1 Insulated resistance The insulated resistance must be more than 2M 2 Grounding work After finishing grounding work measure the grounding resistance by visual detection and grounding resistance tester Make sure the grounding resistance is less than 4 3 Electrical leakage check performing during test running During test operation after finishing insta...

Page 24: ...ntrolled by the remote controller to run in cooling mode manual operation can be taken Manual operation is used only when the remote controller is disable or maintenance necessary Test running Manual control button Auto OFF oF the unit 3 When the ambient temperature is too low lower than 63 function AUTO and FAN to check if all the functions work well 2 Use the MODE button to select COOL HEAT Only...

Page 25: ...bove conditions certain safety protection features may come into operation and cause the unit to function abnormally Optimum performance will be achieved within these operating temperature Preparing the device for operation Preparing the device for operation Cool MODE Indoor Indoor Outdoor Indoor Outdoor Attention Dehumidifier Temperature Temperature Temperature Heat excess of this figure the surf...

Reviews: