Frigidaire FEX831FS - 27

4

 

Do not allow combustible materials (for

example: clothing, draperies/curtains, paper) to come in
contact with exhaust system. 

The dryer 

MUST NOT

 be

exhausted into a chimney, a wall, a ceiling, or any concealed
space of a building which can accumulate lint, resulting in a fire
hazard.

 Exceeding the length of duct pipe or number

of elbows allowed in the "MAXIMUM LENGTH" charts 

can

cause an accumulation of lint in the exhaust system.  Plugging
the system could create a fire hazard, as well as increase drying
times.

 

Do not screen the exhaust ends of the vent

system, nor use any screws, rivets or other fastening means
that extend into the duct and catch lint to assemble the
exhaust system.

 Lint can become caught in the screen, on the

screws or rivets, clogging the duct work and creating a fire hazard
as well as increasing drying times. Use an approved vent hood
to terminate the duct outdoors, and seal all joints with duct
tape. All male duct pipe fittings 

MUST

 be installed downstream

with the flow of air.

 Explosion hazard. Do not install the dryer

where gasoline or other flammables are kept or stored.

 If

the dryer is installed in a garage, it must be a minimum of 18
inches (45.7 cm) above the floor. Failure to do so can result in
death, explosion, fire or burns.

  The exhaust system back pressure

MUST 

not exceed 0.6 inches (1.52 cm) of water column,

measured with an inclined manometer at the point the exhaust
connects to the dryer.  The exhaust system should be inspected
and cleaned a  minimum of every 

18 months

 with normal

usage. The more the dryer is used, the more often you should
check the exhaust system and vent hood for proper operation.

The maximum length of the exhaust system depends upon the
type of duct used, number of elbows and type of exhaust hood.

The maximum length for both rigid and flexible duct is shown in
the chart below.

 Do not install flexible plastic or flexible foil venting

material.  If installing semi-rigid venting, do not exceed 8 ft.
(2.4m) duct length

.

CORRECT

CORRECT

INCORRECT

INCORRECT

   

EXHAUST SYSTEM REQUIREMENTS

Use only 4 inch (10.2 cm) diameter (minimum) rigid or flexible

metal 

duct and approved vent hood which has a swing-out

damper(s) that open when the dryer is in operation. When the
dryer stops, the dampers automatically close to prevent drafts
and the entrance of insects and rodents. To avoid restricting the
outlet, maintain a minimum of 12 inches (30.5 cm) clearance
between the vent hood and the ground or any other obstruction.

 

The following are specific requirements for

proper and safe operation of your dryer. Failure to follow
these instructions can create excessive drying times and
fire hazards.

 

Do not install a clothes dryer with flexible

plastic venting materials.  

If your present system is made up

of plastic duct or metal foil duct, 

replace it

 with a rigid or flexible

metal duct.  Flexible venting materials  are known to collapse,
be easily crushed and trap lint.  These conditions will obstruct
clothes dryer airflow and increase the

 risk of fire.  

  

Ensure the

present duct is free of any lint prior to installing dryer
duct.

 

- Risk of Fire

 - 

A clothes dryer must be

exhausted outdoors

.  Do not exhaust dryer into  a chimney, a

wall, a ceiling, an attic, a crawl space or any concealed space
of a building.  A clothes dryer produces combustible lint.  If the
dryer is not exhausted outdoors, some fine lint will be expelled
into the laundry area. An accumulation of lint in any area of the
home can create a health and fire hazard. 

The dryer must be

connected to an exhaust outdoors.

  Regularly inspect the

outdoor exhaust opening and remove any accumulation of lint
around the outdoor exhaust opening and in the surrounding
area.

EXHAUST DUCT LENGTHS

Number

of 90°

Turns

MAXIMUM LENGTH OF 4-INCH (10.2 CM)

DIAMETER  RIGID METAL DUCT

EXHAUST HOOD TYPE

0
1
2
3

56 ft. (17.07 m)
46 ft. (14.02 m)
34 ft. (10.36 m)
32 ft. (9.75 m)

42 ft. (12.8 m)
36 ft. (10.97 m)
28 ft. (8.53 m)
18 ft. (5.48 m)

Louvered

4”

(10.2 CM)

2.5”

(6.35 CM)

Summary of Contents for FEX831FS - 27" Electric Laundry Center

Page 1: ...9 cm Wide LAUNDRY CENTER Washer Dryer Installation Instructions CENTRO DE LAVANDERÍA de 27 69 cm de ancho Lavadora Secadora Instrucciones para la instalación Indice MATERIA PAGINA Requerimientosdeinstalaciónpreliminares 12 Requerimientos eléctricos 13 Requerimientosdelsuministrodeagua 13 Requerimientosdedesagüe 13 Requerimientosdelsistemadeescape 14 15 Requerimientosdelsuministrodegas 15 Ubicación...

Page 2: ...l Gas Code ANSI Z223 1 or in Canada CAN ACG B149 1 2000 The Laundry Center is designed under ANSI Z 21 5 1 or ANZI UL 2158 CAN CSA C22 2 No 112 latest editions for HOME USE only This Laundry Center is not recommended for commercial applications such as restaurants or beauty salons etc Do not install a Laundry Center with flexible plastic venting materials Flexible venting materials are known to co...

Page 3: ...pliance is to be connected by means of a cord kit use 4 conductor cord for this purpose USE COPPER CONDUCTOR ONLY OUTLET RECEPTACLE NEMA 10 30R receptacle to be located so the power supply cord is accessible when the dryer is in the installed position Canada NEMA 14 30R receptacle WATER SUPPLY REQUIREMENTS Hot and cold water faucets MUST be installed within 42 inches 106 68 cm of your laundry cent...

Page 4: ...le plastic or flexible foil venting material If installing semi rigid venting do not exceed 8 ft 2 4m duct length CORRECT CORRECT INCORRECT INCORRECT EXHAUST SYSTEM REQUIREMENTS Use only 4 inch 10 2 cm diameter minimum rigid or flexible metal duct and approved vent hood which has a swing out damper s that open when the dryer is in operation When the dryer stops the dampers automatically close to p...

Page 5: ...left 4 Right 8 inch 20 32 cm length of 4 inch 10 16 cm rigid duct 1 elbow down and 1 elbow right To exhaust up add an 11 inch 27 94 cm length of standard 4 inch 10 16 cm diameter duct and a 90 elbow The unit will be positioned about 4 inches 11 43 cm away from the wall flush to wall exhausting may be done by going below the dryer then sideways An exhaust hood positioned to line up with the dryer e...

Page 6: ... 16 IN 29 5 CM 1 7 8 IN 4 76 CM 3 IN 9 52 CM 9 3 8 IN 23 81 CM 41 IN 104 77 CM 29 7 16 IN 74 77 CM 27 IN 68 58CM DRAIN OUTLET REAR WATER INLETS REAR VENT 5 IN 13 33 CM GAS SUPPLY PIPE REAR 43 IN 109 22 CM 54 5 16 IN 137 95 CM 75 IN 191 77 CM 43 IN 109 22 CM ELECTRICAL CONNECTION 12 IN 31 75 CM ROUGH IN DIMENSIONS ...

Page 7: ...revent water syphoning DO NOT REMOVE THESE CLAMPS 6 Carefully move the laundry center to within 4 feet 1 22 m of the final location to begin the installation 1 Dryer MUST be exhausted outside outdoors not beneath the mobile home using metal ducting that will not support combustion Metal ducting must be 4 inches 10 16 cm in diameter with no obstructions Rigid metal duct is preferred 2 If dryer is e...

Page 8: ...ted laundry center 1 The laundry center MUST be grounded In the event of malfunction or breakdown grounding will reduce the risk of electrical shock by a path of least resistance for electrical current 2 If your laundry center is equipped with a power supply cord having an equipment grounding conductor and a grounding plug the plug MUST be plugged into an appropriate copper wired receptacle that i...

Page 9: ...CANADIAN ELECTRIC Laundry Center NEUTRAL GROUND WIRE 1 Remove the screw securing the terminal block access cover to the rear panel and remove cover 2 Install a U L approved strain relief connector in the entry hole on the back panel 3 Remove the neutral ground wire from the green ground screw located above the termial block 4 Insert a NEMA 14 30 Type ST or SRDT U L approved power cord through the ...

Page 10: ...f the ground Gently set the laundry center back down to allow the rear legs to self adjust Place a level on top of the washer Check it side to side then front to back Screw the front leveling legs up or down to ensure the laundry center is resting solid on all four legs no rocking of the laundry center should exist NOTE Keep the leg extension at a minimum to prevent excessive vibration 7 GAS CONNE...

Page 11: ...er make sure the dryer area is clear and free from combustible materials gasoline and other flammable vapors Also see that nothing such as boxes clothing etc obstructs the flow of combustion and ventilation air WARNING WARNING REPLACEMENT PARTS If replacement parts are needed for your laundry center contact the source where you purchased your laundry center Destroy the carton plastic bags and meta...

Page 12: ... Eléctrico Canadiense Parte 1 La alimentación de gas para la centro de lavadaría deberá cumplir con los códigos y reglamentos locales y con la última edición del Código Nacional para Gases Combustibles ANSI Z223 1 o en Canadá CAN CGA B149 12 La secadora está clasificada para USO DOMESTICO solamente de acuerdo con la norma ANSI Z 21 5 1 o ANSI UL 2158 CAN CSA C22 2 No 112 las últimas ediciónes Esta...

Page 13: ...n nuevos 2 casas rodantes 3 vehículos recreativos y 4 áreas cuyas leyes locales no permiten la puesta a tierra a través del neutro 1 desconecte el enlace al neutro 2 use un terminal o cable de puesta a tierra para realizar la conexión según las leyes locales y 3 conecte el terminal o cable del neutro al neutro del circuito de bifurcación como se hace normalmente si el electrodoméstico se va a cone...

Page 14: ...es como rigidos Si va a instalar conductos de ventilación semirrígidos no exceda una longitud de 8 pies 2 4 m INCORRECT INCORRECT 0 56 pies 17 07 m 42 pies 12 8 m 1 46 pies 14 02 m 36 pies 10 97 m 2 34 pies 10 36 m 28 pies 8 53 m 3 32 pies 9 75 m 18 pies 5 48 m TIPO DE CAPERUZA DE SALIDA Preferido Número de Codos a 90 LARGO MÁXIMO del Conducto Metálico Rigido de 4 10 2 cm de Diámetro 4 10 2 cm Ape...

Page 15: ...ilgadas 20 32 cm de longitud y 4 pulgadas 10 16 cm de diàmetro 1 ducto acodado hacia abajo y un ducto acodado hacia la derecha 4 Hacia la derecha ducto rigido 8 pulgadas 20 32 cm de longitud y 4 pulgadas 10 16 cm de diàmetro 1 ducto acodado hacia abajo y un ducto acodado hacia la derecha Aungue un sistema vertical sea aceptable algunas circunstancias atenuantes pueden afectar el funcionamiento de ...

Page 16: ... 11 7 16 IN 29 5 CM 41 IN 104 77 CM 29 7 16 IN 74 77 CM 27 IN 68 58CM DRAIN OUTLET REAR WATER INLETS REAR VENT 1 7 8 IN 4 76 CM 5 IN 13 33 CM GAS SUPPLY PIPE REAR 43 IN 109 22 CM 54 5 16 IN 137 95 CM 75 IN 191 77 CM 43 IN 109 22 CM ELECTRICAL CONNECTION 12 IN 31 75 CM LINA DE ALIMENTATION DE GAS ATRAS CONEXIÓN ES ELÉCTRICA S ENTRADAS DE AGUA ATRAS SALIDA AL DRENAJE ATRAS ...

Page 17: ...rrada el ducto de escape DEBEterminarfueradelrecinto conelextremofinalasegurado en contra de la estructura de la casa móvil 3 Al instalar una secadora de gas en una casa móvil hay que instalarunaprovisióndeairefrescosuplementario Laprovisión tienequesermásgrandequedosveceselespaciodelescape de la secadora 4 Vea las páginas 2 y 3 para otros requísitos importantes de ventilación 5 La instalación DEB...

Page 18: ...quipadaconuncordóneléctricoqueposee un conductor de puesta a tierra del equipo y un enchufe de puesta a tierra dicho enchufe DEBE ser conectado a un tomacorriente adecuado debidamente instalado y puesto a tierra de acuerdo con todos los códigos y reglamentos locales Sitienealgunadudaconsulteaunelectricistaprofesional No modifique el enchufe proporcionado la aplicación Para una lavanderia conectada...

Page 19: ...licates Conecte con cuidado el tubo superior de entrada a la llave de agua FRIA apriete a mano y luege apriete 2 3 vuelta con unos alicates NO ESTROPEE LAS ROSCAS NI APRIETE ESTAS CONEXIONES EXCESIVAMENTE Abra la llave del agua y compuebe que no haya fugas en ninguna de lasdos conexiones 5 Con cuidado mueve el centro de lavanderia hasta su ubicación definitiva para instalación final 6 Para verific...

Page 20: ...les gasolina y otros vapores inflamables cerca de la secadora Ademásasegúresedequenohayanada talcomocajas ropas etc queobstruyaelflujodelairedecombustiónyventilación 14 Haga funcionar la secadora durante un ciclo completo para comprobarsubuenfuncionamiento NOTA En las secadoras a gas antes de encender el quemador esnecesariopurgarelairedelatuberíadelgas Sielquemador no enciende dentro de 45 segund...

Reviews: