5
30" ELECTRIC SLIDE-IN RANGE INSTALLATION INSTRUCTIONS
Canada Style
Figure 2
1.
Power Supply Cord Kit (U.S.A.)
The user is responsible for connecting the power supply
cord to the connection block located behind the back
panel access cover.
This appliance may be connected by means of
permanent "hard wiring"; flexible armored or
nonmetallic shielded copper cable (when local code
allow it) or by means of a power supply cord kit. See
chart (on next page) for the minimum wire size (general
UL listing, local code may differ).
NOTE:
Electric Slide-in Range is shipped from factory
with 1 1/8" (2.9 cm) dia. hole as shown on figure 4. If a
larger hole is required, punch out the knockout.
Risk of fire or electrical shock exists if
an incorrect size range cord kit is used, the
Installation Instructions are not followed, or the
strain relief bracket is discarded.
2.
Factory Connected Power Supply
Cord (Canada only)
This range is equipped with a factory-connected power
cord (see Figure 2). Cord must be connected to a
grounded 120/240 volt or 120/208 volt range outlet. If
not outlet is available, have one installed by a qualified
electrician.
Range Connection Opening Size Chart
Refer to chart below for proper range connection opening size and power
supply cord kit ampere rating information. See serial plate on appliance for
kilowatt rating data.
See serial Plate on the
Appliance for KW Rating
Cord Kit
Ampere
Rating
Diameter (inches (cm)) of
Appliance Connection Opening
120/240 Volts
120/208 Volts
Cord Kit
Direct
Connection
0 - 8.7 kw
8.8 - 16.5 kw
16.6 - 22.5 kw
0 - 7.8 kw
7.9 - 12.5 kw
12.6 - 18.5 kw
30 Amp
40 Amp
50 Amp
1 1/8 (2.9)
1 3/8 (3.5)
1 3/8 (3.5)
7/8 (2.2)
1 1/8 (2.9)
1 3/8 (3.5)
For mobile homes, new installations or recreational
vehicles, use only a power supply kit designed for a
range at 125V/250V 40A. Cord must have either 3
(when local code permits grounding through neutral) or
4 conductors. Terminal on end of wires must be either
closed loop or open spade lug with upturned ends. Cord
must have strain-releif clamp. See chart for the
minimum wire size (general UL listing , local code may
differ).
Do not loosen the nuts which secure
the factory-installed range wiring to terminal block
while connecting range. Electrical failure or loss of
electrical connection may occur.
Appliance Rating Watts
120V / 208V
0 - 3120
3121 - 3900
3901 - 4160
4161 - 5200
5201 - 5570
5571 - 7430
7431 - 7800
7801 - 12500
12501 - 14500
Minimum Conductor Size, AWG
L1 and L2
Conductors
16
16
14
14
12
12
12
10
8
Neutral
Conductor
16
16
16
16
16
14
12
12
12
Ground
Conductor
14
12
12
10
10
10
10
10
10
Appliance Rating Watts
120V / 240V
0 - 3600
3601 - 4500
4501 - 4800
4801 - 6000
6001 - 6425
6426 - 8749
8750 - 14500
14501 - 16500
16501 - 24000
Minimum Conductor Size, AWG
L1 and L2
Conductors
16
16
14
14
12
12
10
10
8
Neutral
Conductor
16
16
16
16
16
12
12
10
10
Ground
Conductor
14
12
12
10
10
10
10
10
8