background image

11

Avoid Service Checklist

Before  calling  for service,  review  this  list. It  may  save  you time and expense. This list 
includes common occurrences that are  not  the result of defective workmanship or 

  OCCURRENCE                        SOLUTION

   Air conditioner will not operate.  

Wall plug disconnected. Push plug firmly into wall outlet.

House  fuse  blown  or circuit  breaker  tripped.  Replace fuse with time delay type or reset 
circuit breaker.

Control is OFF. Turn control On and set to desired FAN or COOL setting.

Unit turned off and then on too quickly. Turn unit off and wait 3 minutes before restarting.

   Air from unit does not feel cold
   enough.

Room temperature below 60 F (15 C). Cooling may not occur until room  temperature
rises above 60 F (15 C).

Temperature sensor touching cold coil, located behind air filter. Straighten away from
coil.

Air conditioner cooling, but
room is too warm- ice forming
on cooling coil behind 
decorative front.

Outdoor  temperature  below  60 F (15 C).  To  defrost  the coil,  set  selector  to  FAN
position. Then, set thermostat to warmer position.

Air filter may be dirty. Clean filter. Refer to Care and Cleaning section. To defrost, set
selector to FAN ONLY mode.

Temperature  is  too  low  for  night-time cooling. To defrost  the coil, set to FAN ONLY 
mode. Then, set temperature to a higher number.

Air conditioner cooling, but 
room is too warm-NO ice
forming on cooling coil
behind decorative front.

Dirty air filter-air restricted. Clean air filter. Refer to Care and Cleaning section.

Temperature is  too high. Set temperature to a lower number.

Current device tripped. Preset RESET  button.

Reset to a lower temperature.

Compressor  shut-off  by  changing  modes.  Wait  approximately 3 minutes, and listen for
compressor to restart when set in the COOL mode.

Vent set at OPEN position. Set vent at CLOSED position for maximum cooling.

Air direction louvers positioned improperly. Position louvers for better air distribution.

Front of unit is blocked by drapes, blinds, furniture, etc.-restricts air distribution.Clear 
blockage in front of unit. 

Doors,   windows,  registers,  etc,  open- cold  air  escapes.  Close  doors,  windows,
registers, etc.

Unit  recently  turned  on  in  hot  room,  allow additional time to remove 

“ 

stored heat

from walls, ceiling, floor and furniture.

Air conditioner turns on and 
off rapidly.

Dirty air filter-air restricted. Clean air filter. 

Outside  temperature  extremely  hot.  Set  FAN  speed  to a faster setting to bring air
past cooling coils more frequently.

Noise when unit is cooling

Air movement sound. This is normal. If too loud, set to a slower FAN setting.
Sound  of  fan  hitting  water-moisture  removal system. This is normal when humidity 
is high. Close doors windows and registers.

Window  vibration- poor  installation.  Refer  to  installation instructions or check with 
installer.

Water dripping INSIDE when
unit is cooling.

Improper   installation.  Tilt  air   conditioner  slightly  to  the  outside  to  allow   water 
drainage. Refer to installation instructions - check with installer.

Water dripping OUTSIDE when
unit is cooling.

Unit  removing  large  quantity  of  moisture  from  humid room.  This  is normal during
excessively humid days. 

Room too cold

Not in HEAT mode. Change mode.(On HEAT models only)

Setting too low. Increase temperature setting.

12

 
materials in this appliance

Summary of Contents for FAH12EP2T1

Page 1: ...L THIS AIR CONDITIONER IS EQUIPPED WITH A NEW INDUSTRY STANDARD POWER SUPPLY CORD WITH A TEST RESET FUNCTION READ AND SAVE THESE INSTRUCTIONS THRU THE WALL AIR CONDITIONER 3 SPEED ELECTRONIC CONTROL P N 819042072 01 ...

Page 2: ...warranty does not cover the following 1 CONSEQUENTIAL OR INCIDENTAL DAMAGES SUCH AS PROPERTY DAMAGE AND INCIDENTAL EXPENSES RESULTING FROM ANY BREACH OF THIS WRITTEN OR ANY IMPLIED WARRANTY Note Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation or exclusion may not apply to you 2 Service calls which do not involve malfunction or defects ...

Page 3: ...through the evaporator during normal operation High Pitched Chatter Today s high efficiency compressors may have a high pitched chatter during the cooling cycle Sound of Rushing Air At the front of the unit you may hear the sound of rushing air being moved by the fan Pinging or Swishing Droplets of water hitting the condenser during normal operation may cause pinging or swishing sounds Vibration U...

Page 4: ...d To minimize shock and fire hazards proper grounding is important The power cord is equipped with a three prong grounding plug and a current leakage detection device for protection against shock firehazards Your air conditioner must be used in a properly grounded wall receptacle If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breake...

Page 5: ...s this is also indicated by a light on the plug head NOTES Do not use this device to turn the unit on or off Always make sure the RESET button is pushed in for correct operation The power supply cord must be replaced if it fails to reset when either the TEST button is pushed or it cannot be reset A new one can be obtained from the product manufacturer If power supply cord is damaged it CANNOT be r...

Page 6: ...igh High Fan Fan Temp Timer Temp Timer Temp Timer Temp Timer Sleep Sleep On Off On Off Timer Timer Cool Cool Energy Saver Energy Saver Fan Fan Heat Heat Mode Mode Check Filter Check Filter Auto Auto Low Low Med Med High High Fan Fan Temp Timer Temp Timer Temp Timer Temp Timer Sleep Sleep On Off On Off Timer Timer Cool Cool Energy Saver Energy Saver Fan Fan Heat Heat Mode Mode Check Filter Check Fi...

Page 7: ...onditioner Features continued TO USE AUTO COOL FEATURE YOU WILL SEE DO THIS PRESS TO SELECT AUTO TO OPERATE ON FAN ONLY YOU WILL SEE DO THIS PRESS MODE BUTTON CHOOSE FAN NOTE Use this function only when cooling is not desired such as for room air circulation or to exhaust stale air Remember to open vent during this function but keep it closed during cooling for maximum cooling efficiency You can c...

Page 8: ...TON NOTE In this MODE the selected temperature will increase by 2 F 30 minutes after the mode is selected The temperature will then increase by another 2 F after an additional 30 minutes This new temperature will be maintained for 7 hours before it returns to the originally selected temperature This ends the Sleep MODE and the unit will continue to operate as originally programmed The Sleep MODE p...

Page 9: ...en in the Heat Mode the fan will run continuously while heat is needed The temperature will automatically be maintained anywhere between 60 F 15 and 90 F 32 When the room set temperature is satisfied the fan will cycle off and on to circulate and sample the room air DO THIS PRESS MODE BUTTON SELECT HEAT LIGHT ON Auto Auto Low Low Med Med High High Fan Fan Temp Timer Temp Timer Temp Timer Temp Time...

Page 10: ...lter Care and Cleaning Clean your air conditioner occasionally to keep it looking new Be sure to unplug the unit before cleaning to prevent shock or fire hazards Air Filter Cleaning The air filter should be checked at least once a month to see if cleaning is necessary Trapped particles in the filter can build up and cause an accumulation of frost on the cooling coils Grasp the filter by the center...

Page 11: ...wer number Current device tripped Preset RESET button Reset to a lower temperature Compressor shut off by changing modes Wait approximately 3 minutes and listen for compressor to restart when set in the COOL mode Vent set at OPEN position Set vent at CLOSED position for maximum cooling Air direction louvers positioned improperly Position louvers for better air distribution Front of unit is blocked...

Reviews: