20
PB
SPECIFICATIONS
Electrical Data
VRP
Model
Voltage
Heater
Watts
Heating
Btu
Heater
Amps
ID Blower
Amps
OD Blower
Amps
Heating
Amps
MCA
MOP /
MOCP
VRP12K
230
2500
8530
10.9
0.34
0.57
11.2
14.0
15
208
2030
6980
9.8
0.38
0.63
10.2
230
3400
11601
14.8
0.34
0.57
15.1
18.9
20
208
2780
9480
13.4
0.38
0.63
13.8
230
5000
17060
21.7
0.34
0.57
22
27.5
30
208
4100
13980
19.7
0.38
0.63
20.1
VRP12R
265
2500
8530
9.4
0.2
0.5
9.8
12.3
15
3400
11601
12.8
0.2
0.5
13.2
16.5
20
5000
17060
18.9
0.2
0.5
19.3
24.1
25
VRP24K
230
2500
8530
10.8
0.77
1.06
11.6
14.5
15
208
2030
6980
9.8
0.85
1.17
10.7
230
3400
11600
14.8
0.77
1.06
15.6
19.5
20
208
2780
9480
13.4
0.85
1.17
14.3
230
5000
17050
21.8
0.77
1.06
22.6
28.3
30
208
4100
13980
19.7
0.85
1.17
20.6
230
7500
25590
32.6
0.77
1.06
33.4
41.8
45
208
6130
20900
29.5
0.85
1.17
30.4
230
10000
34120
43.5
0.77
1.06
44.3
55.4
60
208
8180
27890
39.3
0.85
1.17
40.2
VRP24R
265
2500
8530
9.4
0.7
1.0
10.8
13.5
15
3400
11601
12.8
0.7
1.0
14.2
17.8
20
5000
17060
18.9
0.7
1.0
20.3
25.4
25
7500
25590
28.3
0.7
1.0
29.7
37.1
40
10000
34120
37.7
0.7
1.0
39.1
48.9
60
VRP36K
230
0
0
0
/
/
/
18.2
30
208
0
0
0
/
/
/
230
10000
34120
43.5
/
/
/
55.8
60
208
8180
27890
39.3
/
/
/
230
15000
51150
65.3
/
/
/
83.0
90 (60
+ 30)
208
12280
41870
59.0
/
/
/
MCA = Minimum Circuit Ampacity
MOP / MOCP = Maximum Overcurrent Protection / Breaker Size
Minimum Circuit Amps (MCA) and MOCP values in the above table are calculated in accordance with The NEC. Article 440
Figure 207 (Electrical Data)
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...