187
PB
UPDATING VRP FIRMWARE
VRP Remote Upgrade Procedure
VRP Remote Upgrade Procedure
Introduction
The Remote Upgrade procedure on the Friedrich VRP system is designed to greatly reduce the
amount of effort required in upgrading the system firmware. The procedure can upgrade the
Friedrich Main Controller (FMC), Wall Controller (WC), and Motor Control System (MCS) boards. It is
capable of upgrading just one board, all the boards at once, or any combination of any two boards.
All that is required from the user is having a correctly formatted SD Card that is inserted into the
Wall Controller. After insertion into the SD Card slot of the Wall Controller, the process is
autonomous and regular operation resumes after a successful update.
Setup
In-Board SD Cards
The first step in making sure the unit is properly configured for Remote Upgrade is ensuring that
there are SD Cards in both the FMC and MCS boards. If the procedure is started without these cards
present the WC will display an error and the procedure will terminate [See Errors].
Procedure
To Remote Upgrade, the Wall Controller (WC) must be Version 03.02.00.00 or higher, Friedrich
Main Controller (FMC) Version 03.02.00.07 only, and Motor Control System (MCS) Version
03.02.00.04 only. The Wall Controller can be upgraded from any version to 03.02.00.01 by inserting
the “WC 3.2.0.1” SD Card. If the FMC or MCS version do not match the above, a direct upgrade must
be done.
1
Summary of Contents for VRP12K
Page 46: ...46 OPERATION Component Identification Indoor Coil 36k ...
Page 48: ...48 OPERATION Component Identification Outdoor Coil Monitored by 1 thermistor ...
Page 49: ...49 OPERATION Component Identification Outdoor Fan BLDC Variable Speed 600 1000 RPM ...
Page 53: ...53 OPERATION Component Identification 4 Way Reversing Valve 208 230v Reversing valve assembly ...
Page 177: ...177 UPDATING VRP FIRMWARE Or ...
Page 184: ...184 UPDATING VRP FIRMWARE Open zip file Copy to SD Card Insert into SD Card Slot ...
Page 193: ...193 UPDATING VRP FIRMWARE Retrieving VRP Data Remove SD Card from FMC and Locate DF Folder ...
Page 196: ...196 WIRINGDIAGRAMS 12 24K BTU 208 230V 7 5 10 0 KW Figure 801 Wiring Diagram ...
Page 197: ...197 WIRING DIAGRAMS 12 24K BTU 208 230V 2 5 3 4 5 0 KW Figure 802 Wiring Diagram ...
Page 198: ...198 WIRING DIAGRAMS 12 24K BTU 265V 2 5 3 4 5 0 kW Figure 803 Wiring Diagram ...
Page 199: ...199 WIRING DIAGRAMS 12 24K BTU 265V 7 5 10 kW Figure 804 Wiring Diagram ...
Page 200: ...200 WIRING DIAGRAMS 36K BTU 208 230V Figure 805 Wiring Diagram ...