The
Note: Unit is operated by a wired remote wall t-stat which is connected to an electronic control board
at the VPAK unit.
Heat Mode in Cool with Electric Heat Units
Heat Pump With Electric Heat Operation
If the Compressor is Locked Out on the 3 Minute Time Delay and Electric Heat is Available
Condition 1
set point of the t-stat
if
(Compressor Heat)
Heat / Cool Units
This heating has two heating methods. If the ambient indoor temperature is below the heat set point and the
compressor is not locked out, the compressor turns on. If the ambient temperature rises above the t-stat’s heat set
point, the compressor turns off.
1. The control turns on the electric heat until the compressor is not locked out.
2. After lockout, the control turns off the electric heat, waits 5 seconds, then turns on the compressor.
(The wired remote wall t-stat’s time delay may override this feature).
When the t-stat is in the Heat Mode, if the indoor ambient temperature is below the heat set point, the fan turns on
5 seconds prior then the electric heat will turn on. When the t-stat is satisfied, the electric heat will turn off. The fan
turns off 15 seconds later.
Thereafter, the unit will switch back to Heat Pump
45 or greater.
heat until the outdoor coil temperature sensor rises to
10
Summary of Contents for VERT-I-PAK R410A
Page 50: ...8 1 9 10 11 2 7 4 5 6 3 2011 VPAK 9K 18K BTU h Models 49...
Page 51: ...17 16 12 15 13 14 2011 VPAK 9K 18K BTU h Models 50...
Page 52: ...24 26 25 28 27 23 16 2011 VPAK 9K 18K BTU h Models 51...
Page 53: ...20 21 22 18 19 2011 VPAK 9K 18K BTU h Models 52...
Page 55: ...8 9 4 2 1 6 7 5 3 2011 VPAK 24K BTU h Models 54...
Page 56: ...18 17 16 10 14 15 23 12 13 22 21 6 20 19 11 2011 VPAK 24K BTU h Models 55...
Page 57: ...25 14 29 30 24 26 28 2011 VPAK 24K BTU h Models 56...