Friedrich VERT-I-PAK B-SERIES Installation & Operation Manual Download Page 16

16

920-164-02 (10-04)

particularly cool and humid weather. When this occurs, your 
heat pump senses this condition and goes through a defrost 
cycle. During the defrost cycle, the outdoor-air blower is turned 
off, and the reversing valve reverses the fl ow of refrigerant 
through the outdoor-air coil so it is heated and the frost or ice 
melts. You may notice the defrost cycle inside your home by a 
faint click and hissing sound and a slight change in the sound 
created by the blower as the defrost cycle begins and ends. 
During the defrost cycle, you may also notice that the air is 
quickly heated as the defrost cycle ends. Outside the home, 
a cloud of water vapor created by the melting frost or ice may 
be visible as it is exhausted. This is normal and keeps the unit 
working effi ciently. Do not be alarmed!

Condensate

The heat pump may generate condensate during both the 
cooling and heating modes of operation.  For proper operation, 
a condensate drain line must be extended from the drain fi tting 
on the right side of the unit to the  perimeter of the home or to 
a proper drain location. The drain line must be sloped towards 
the outside of the home or drain  location and be protected 
from freezing.

NOTE:

  In order for condensate to drain freely, the unit must 

be installed level.

Typical Heat /Cool Thermostat

Thermostat Operation

The operation of the system is controlled by the indoor 
thermostat. Most thermostats have 3 controls: a temperature 
control selector, a FAN control, and a SYSTEM or MODE 
control. (See Figure 3.)

The temperature control is a selector or set of buttons that 
allows you to establish the degree of temperature that you 
wish to maintain for your personal comfort. Some thermostats 
have two temperature control selectors: one for setting the 
temperature desired during the cooling cycle, and one for 
setting the heating operation temperature.

Typical settings are 78°F for cooling and 68°F for heating.

Fan Control

The FAN control offers two options for controlling the indoor-air 
blower: AUTO and ON. When the FAN control is set to AUTO, 
the blower will operate only while the thermostat operates the 
cooling or heating equipment. When the FAN control is set 
to ON, the blower will operate continuously – regardless of 
whether cooling or heating equipment is operating. This setting 
allows for continuous air circulation and fi ltration.

System Control

The SYSTEM or MODE control on your thermostat offers 
the following selections: COOL, OFF, HEAT, and EM HEAT. 

Neither the cooling nor heating equipment will operate when 
the SYSTEM or MODE control is set to OFF. With the SYSTEM 
or MODE control set to COOL, your unit will operate in cooling 
mode. With the SYSTEM or MODE control set to HEAT, your 
unit will operate in heating mode.

Auxiliary Heating

Your system also includes an auxiliary electric heating source. 
The SYSTEM or MODE control options HEAT and EM 
HEAT provide convenient selection between the two heating 
appliances. The heat pump will operate when SYSTEM or 
MODE control is set to HEAT. The auxiliary electric heater may 
also be used on cold days to supplement heat pump heating. 
With the SYSTEM or MODE control set to EM HEAT, the heat 
pump is turned off and the auxiliary electric heat is activated. 
The unit is now operating as an electric furnace.

On heat pump systems, the wall thermostat regulates the use 
of auxiliary electric heat to maximize energy effi ciency and 
your home comfort.

Cooling Cycle

When operating in the cooling cycle, your unit will operate 
until the indoor temperature is lowered to the level you have 
selected on the indoor thermostat. On extremely hot days, your 
unit will operate for longer periods of time and have shorter 
“off” periods than on moderate days.

The following are typical conditions that add extra heat and/or 
humidity to your home and force your cooling unit to work 
longer to keep your home comfortable:

•  Entrance doors are frequently opened and closed.

•  Laundry appliances are being operated.

• A shower is running.

•  More than usual number of people are present in the home.

•  More than the normal number of electric lights are in use.

•  Drapes or blinds are open on the sunny side of the 

building or home.

Summary of Contents for VERT-I-PAK B-SERIES

Page 1: ...920 164 02 10 04 VERT I PAK B SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 18 000 60 000 BTU h INSTALLATION OPERATION GUIDE ...

Page 2: ... Supply Air System 10 Outdoor Fan Performance 10 Indoor Fan Performance 11 2 Electrical A Grounding 12 B Power Supply 12 3 Thermostat Mounting and Wiring A Thermostat Location 13 B Thermostat Mounting Wiring 13 C Wire Thermostat Cable to Unit Terminal 14 4 Condensate Drain Line 14 Installation Final Checklist 14 Test Run 14 IV Owners Manual Operating Information Identifying your System 15 Importan...

Page 3: ... for ducted return units This could cause a refrigerant leak DO handle unit with care DO provide minimum installation and service clearances DO build closet so that unit may be removed if necessary DO follow all guidelines for indoor and outdoor air system DO NOT substitute any components without checking with your dealer or distributor If you do substitute get approval in writing Substitutions wi...

Page 4: ...WP5 plenums Recommended for use with 60 000 Btu h units DIMENSIONS 341 4 high x 40 wide CUTOUT DIMENSIONS 341 2 high x 401 4 wide Architectural louver for VPBWP6 plenums Custom colored architectural louver for VPBWP6 plenums WALL PLENUM Used when chassis is positioned against an exterior wall for outdoor air infiltration ARCHITECTURAL LOUVER Extruded aluminum outdoor louver that attaches to wall sl...

Page 5: ...7 Cabinet B 68 Cabinet NOMINAL CAPACITY A Series Btu h 09 9 000 12 12 000 18 18 000 24 24 000 VOLTAGE K 208 230V 1Ph 60Hz ELECTRIC HEATER SIZE A Series B Series 00 No electric heat 00 No electric heat 25 2 5 KW 05 5 0 KW 34 3 4 KW 10 10 0 KW 50 5 0 KW 15 15 0 KW 75 7 5 KW 20 20 0 KW 10 10 0 KW 25 25 0 KW ENGINEERING CODE OPTIONS RT Standard Remote Operation SP Seacoast Protected B Series Btu h 18 ...

Page 6: ...H B49 BACK VIEW 2 00 23 25 14 00 2 00 19 00 12 00 16 25 21 00 OUTDOOR AIR INTAKE OUTDOOR AIR EXHAUST 1 5 2 0 9 5 11 6 22 5 11 6 19 1 22 5 OUTDOOR AIR INTAKE OUTDOOR AIR EXHAUST 38 00 INDOOR AIR RETURN 19 x 27 NOM SERVICE PORT ACCESS 68 00 CONTROL BOX ACCESS 11 10 2 00 14 50 5 50 INDOOR AIR SUPPLY 13 25 2 00 13 87 11 75 INDOOR AIR SUPPLY TOP VIEW ...

Page 7: ... contained system the Vert I Pak unit requires an adequate supply of outdoor air to exchange heat Figure4 UnitConfiguration from the outdoor air coil The outdoor air intake and discharge openingsarelocatedonthebacksideoftheunit Theunitmay be installed where the outdoor air path runs through the wall of the building directly behind the unit or where the outdoor air intake and discharge paths are duc...

Page 8: ...8 920 164 02 10 04 Figure6 VPBWP4 8 14WallPlenum Figure5 VPBWP3 8 14WallPlenum For Models VE VHB18 VE VHB24 For Models VE VHB18 VE VHB24 VE VHB30 VE VHB36 ...

Page 9: ...9 920 164 02 10 04 Figure7 VPBWP5 8 14WallPlenum Figure8 VPBWP6 8 14WallPlenum For Models VE VHB42 VE VHB49 For Model VE VHB60 ...

Page 10: ...TSIDE WALL Table1 Outdoor Blower Air Flow SCFM ESP 0 0 0 1 0 2 0 3 VEB18 VHB18 Outdoor 1160 1080 990 920 VEB24 VHB24 Outdoor 1160 1080 990 920 VEB30 VHB30 Outdoor 1300 1227 1131 1026 VEB36 VHB36 Outdoor 1600 1550 1480 1420 VEB42 VHB42 Outdoor 2100 2000 1900 1800 VEB49 VHB49 Outdoor 2400 2300 2200 2100 VEB60 VHB60 Outdoor 2600 2550 2450 2350 Italics numbers indicate performance outside the required...

Page 11: ... front of the RA opening a minimum of 7 in clearance is required between the front of the unit and the back side of the door The minimum net free open area required for the RA louver or grille is listed in Table 2 Front Free Return Front Ducted Return Figure10 ReturnAirOptions NOTE Ducted return air configuration requires field fabrication of a duct mounted filter box IndoorFanPerformance Table2 Indo...

Page 12: ...Range MCA HACR Max Breaker Size Wire Size field Groung Wire Size field MCA HACR Max Breaker Size Wire Size field Groung Wire Size field Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 1 Ckt 1 Ckt 1 VEB18K 00 1 230 208 60 1 198 253 14 N A 20 N A 12 N A 12 N A 14 20 10 12 05 2 230 208 60 1 198 253 14 27 20 30 12 10 12 10 27 30 10 10 75 2 230 208 60 1 198 253 14 39 20 40 12 8 12 10 40 40 6 10 1...

Page 13: ... 10 10 N A N A N A N A Unit Wiring with VPDB1 Distribution Block Heat Pump Field Wiring Auxiliary Heater 1 Field Wiring Ground Field Wiring Ground Lug Auxiliary Heater 2 Field Wiring Auxiliary Heater 2 Auxiliary Heater 1 Heat Pump Line Voltage And Ground Connections 3 ThermostatMountingAndWiring A ThermostatLocation Locate the thermostat about 5 ft above the floor in an area with good circulation a...

Page 14: ...s The condensate line must have a minimum drop of 1 4 per running foot as it leaves the unit When a horizontal run of 15 ft or longer is required it may be necessary to install a vent tee in the drain line near the unit or use a larger diameter drain line This is to eliminate air trapping and allow proper condensate drainage Heatpumpsgeneratecondensateduringbothcoolingand heatingmodes Condensatedr...

Page 15: ...re variations within the home Dehumidification Duringthecoolingseason theVert I Pakalsodehumidifiesthe air in the home while is it cooling the air After a few minutes of operation water should run freely from the condensate drain line extended to the outside of your home If condensate is not runningfromthedrainline checktobesurethatthedrainhose or pipe is properly connected to the drain fitting locat...

Page 16: ...onsforcontrollingtheindoor air blower AUTO and ON When the FAN control is set to AUTO the blower will operate only while the thermostat operates the cooling or heating equipment When the FAN control is set to ON the blower will operate continuously regardless of whethercoolingorheatingequipmentisoperating Thissetting allows for continuous air circulation and filtration SystemControl The SYSTEM or M...

Page 17: ... dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replaced as it becomes dirty To replace the filter front air return units 1 Slide the filter to the right until it clears the filter rails See Figure 12 2 Remove the filter 3 Install new disposable filter CAUTION Do not operate your system without a filter in place nor block the front of the unit return air o...

Page 18: ...18 920 164 02 10 04 ...

Page 19: ...19 920 164 02 10 04 ...

Page 20: ...tory Certified Parts FRIEDRICH AIR CONDITIONING CO INC Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in the U S A ...

Reviews: