Friedrich VERT-I-PAK B-SERIES Installation & Operation Manual Download Page 13

13

920-164-02 (10-04)

Table 5

Heat Pumps

Multiple Circuits

Single Circuit

Factory 

Circuit 

Breakers Voltage / Hz / Ph

Voltage 

Range

MCA

HACR / 

Max Breaker Size

Wire Size (fi eld)*

Groung Wire Size* 

(fi eld)

MCA

HACR / 

Max 

Breaker 

Size

Wire Size* 

(fi eld)

Groung 

Wire Size* 

(fi eld)

Ckt 1

Ckt 2

Ckt 1

Ckt 2

Ckt 1

Ckt 2

Ckt 1

Ckt 2

Ckt 1

Ckt 1

Ckt 1

Ckt 1

VHB18K

05

2

230/208-60-1

198-253

14

26

20

30

12

10

12

10

39

40

8

10

75

2

230/208-60-1

198-253

14

39

20

40

12

8

12

10

52

60

6

10

10

2

230/208-60-1

198-253

14

52

20

60

12

6

12

10

65

70

4

8

VHB24K

05

2

230/208-60-1

198-253

20

26

30

30

10

10

10

10

41

40

8

10

75

2

230/208-60-1

198-253

20

39

30

40

10

8

10

10

54

60

6

10

10

2

230/208-60-1

198-253

20

52

30

60

10

6

10

10

67

70

4

8

VHB30K

05

2

230/208-60-1

198-253

23

26

40

30

8

10

10

10

51

60

6

10

75

2

230/208-60-1

198-253

23

39

40

40

8

8

10

10

64

70

4

8

10

2

230/208-60-1

198-253

23

52

40

60

8

6

10

10

77

80

4

8

15**

2

230/208-60-1

198-253

23

52

40

60

8

8

10

10

81

90

4

8

VHB36K

05

2

230/208-60-1

198-253

28

26

40

30

8

10

10

10

54

60

6

10

75

2

230/208-60-1

198-253

28

39

40

40

8

8

10

10

67

70

4

8

10

2

230/208-60-1

198-253

28

52

40

60

8

6

10

10

80

80

4

8

15*

2

230/208-60-1

198-253

28

52

40

60

8

8

10

10

81

90

4

8

VHB42K

10

2

230/208-60-1

198-253

34

53

50

60

6

6

10

10

86

90

4

8

15

3

230/208-60-1

198-253

34

53/27

50

60/30

6

6/8

10

10/10

112

120

2

4

VHB49K

15

3

230/208-60-1

198-253

36

53/27

50

60/30

6

6/6

10

10/10

114

120

2

4

20

3

230/208-60-1

198-253

36

53/53

50

60/60

6

6/6

10

10/10

N/A

N/A

N/A

N/A

VHB60K

20

3

230/208-60-1

198-253

48

53/53

70

60/60

4

6/6

8

10/10

N/A

N/A

N/A

N/A

25

4

230/208-60-1

198-253

48

53/53/27

70

60/60/30

4

6/6/8

8

10/10/10

N/A

N/A

N/A

N/A

Unit Wiring with VPDB1 Distribution Block

Heat Pump
(Field Wiring)

Auxiliary

Heater #1

(Field Wiring)

Ground

(Field Wiring)

Ground Lug

Auxiliary Heater #2
(Field Wiring)

Auxiliary 
Heater #2

Auxiliary
Heater #1

Heat Pump

Line Voltage And Ground Connections

3) Thermostat Mounting And Wiring

A. Thermostat Location

Locate the thermostat about 5 ft. above the fl oor 
in an area with good circulation at average indoor 
temperature.

Do not mount thermostat where it may be affected by:

•  Drafts or dead-air spots behind doors and in 

corners.

•  Hot or cold air fl ow from ducts.

•  Radiant heat from sun or appliances.

•  Concealed pipes or chimneys.

•  Unheated (uncooled) areas behind thermostat, 

such as an outside wall.

B. Thermostat Mounting and Wiring

The thermostat is a precision instrument and was carefully 
adjusted at the factory.  Handle it carefully.

CAUTION:

  Disconnect the power supply before begin-

ning installation of the thermostat to prevent electrical shock 
or equipment damage.  Do not short across the thermostat 
terminals. This can burn out the thermostat anticipator.

All wiring for the thermostat circuit must comply with NEC, 
state and local codes.  Use No. 20 AWG color-coded, insulated 
(35°C minimum) wire.  If the thermostat is located more than 

 * If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).  The ampacity of nonmetalic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C 

(140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-30.  If other than uncoated (non-plated), 60°C or 75°C (140°F or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, 
stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

 **  VHB30K15 and VHB36K15 models were confi gured to stage electric heat with the “D” suffi x revision. Refer to unit nameplate for actual requirements.

Summary of Contents for VERT-I-PAK B-SERIES

Page 1: ...920 164 02 10 04 VERT I PAK B SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 18 000 60 000 BTU h INSTALLATION OPERATION GUIDE ...

Page 2: ... Supply Air System 10 Outdoor Fan Performance 10 Indoor Fan Performance 11 2 Electrical A Grounding 12 B Power Supply 12 3 Thermostat Mounting and Wiring A Thermostat Location 13 B Thermostat Mounting Wiring 13 C Wire Thermostat Cable to Unit Terminal 14 4 Condensate Drain Line 14 Installation Final Checklist 14 Test Run 14 IV Owners Manual Operating Information Identifying your System 15 Importan...

Page 3: ... for ducted return units This could cause a refrigerant leak DO handle unit with care DO provide minimum installation and service clearances DO build closet so that unit may be removed if necessary DO follow all guidelines for indoor and outdoor air system DO NOT substitute any components without checking with your dealer or distributor If you do substitute get approval in writing Substitutions wi...

Page 4: ...WP5 plenums Recommended for use with 60 000 Btu h units DIMENSIONS 341 4 high x 40 wide CUTOUT DIMENSIONS 341 2 high x 401 4 wide Architectural louver for VPBWP6 plenums Custom colored architectural louver for VPBWP6 plenums WALL PLENUM Used when chassis is positioned against an exterior wall for outdoor air infiltration ARCHITECTURAL LOUVER Extruded aluminum outdoor louver that attaches to wall sl...

Page 5: ...7 Cabinet B 68 Cabinet NOMINAL CAPACITY A Series Btu h 09 9 000 12 12 000 18 18 000 24 24 000 VOLTAGE K 208 230V 1Ph 60Hz ELECTRIC HEATER SIZE A Series B Series 00 No electric heat 00 No electric heat 25 2 5 KW 05 5 0 KW 34 3 4 KW 10 10 0 KW 50 5 0 KW 15 15 0 KW 75 7 5 KW 20 20 0 KW 10 10 0 KW 25 25 0 KW ENGINEERING CODE OPTIONS RT Standard Remote Operation SP Seacoast Protected B Series Btu h 18 ...

Page 6: ...H B49 BACK VIEW 2 00 23 25 14 00 2 00 19 00 12 00 16 25 21 00 OUTDOOR AIR INTAKE OUTDOOR AIR EXHAUST 1 5 2 0 9 5 11 6 22 5 11 6 19 1 22 5 OUTDOOR AIR INTAKE OUTDOOR AIR EXHAUST 38 00 INDOOR AIR RETURN 19 x 27 NOM SERVICE PORT ACCESS 68 00 CONTROL BOX ACCESS 11 10 2 00 14 50 5 50 INDOOR AIR SUPPLY 13 25 2 00 13 87 11 75 INDOOR AIR SUPPLY TOP VIEW ...

Page 7: ... contained system the Vert I Pak unit requires an adequate supply of outdoor air to exchange heat Figure4 UnitConfiguration from the outdoor air coil The outdoor air intake and discharge openingsarelocatedonthebacksideoftheunit Theunitmay be installed where the outdoor air path runs through the wall of the building directly behind the unit or where the outdoor air intake and discharge paths are duc...

Page 8: ...8 920 164 02 10 04 Figure6 VPBWP4 8 14WallPlenum Figure5 VPBWP3 8 14WallPlenum For Models VE VHB18 VE VHB24 For Models VE VHB18 VE VHB24 VE VHB30 VE VHB36 ...

Page 9: ...9 920 164 02 10 04 Figure7 VPBWP5 8 14WallPlenum Figure8 VPBWP6 8 14WallPlenum For Models VE VHB42 VE VHB49 For Model VE VHB60 ...

Page 10: ...TSIDE WALL Table1 Outdoor Blower Air Flow SCFM ESP 0 0 0 1 0 2 0 3 VEB18 VHB18 Outdoor 1160 1080 990 920 VEB24 VHB24 Outdoor 1160 1080 990 920 VEB30 VHB30 Outdoor 1300 1227 1131 1026 VEB36 VHB36 Outdoor 1600 1550 1480 1420 VEB42 VHB42 Outdoor 2100 2000 1900 1800 VEB49 VHB49 Outdoor 2400 2300 2200 2100 VEB60 VHB60 Outdoor 2600 2550 2450 2350 Italics numbers indicate performance outside the required...

Page 11: ... front of the RA opening a minimum of 7 in clearance is required between the front of the unit and the back side of the door The minimum net free open area required for the RA louver or grille is listed in Table 2 Front Free Return Front Ducted Return Figure10 ReturnAirOptions NOTE Ducted return air configuration requires field fabrication of a duct mounted filter box IndoorFanPerformance Table2 Indo...

Page 12: ...Range MCA HACR Max Breaker Size Wire Size field Groung Wire Size field MCA HACR Max Breaker Size Wire Size field Groung Wire Size field Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 2 Ckt 1 Ckt 1 Ckt 1 Ckt 1 VEB18K 00 1 230 208 60 1 198 253 14 N A 20 N A 12 N A 12 N A 14 20 10 12 05 2 230 208 60 1 198 253 14 27 20 30 12 10 12 10 27 30 10 10 75 2 230 208 60 1 198 253 14 39 20 40 12 8 12 10 40 40 6 10 1...

Page 13: ... 10 10 N A N A N A N A Unit Wiring with VPDB1 Distribution Block Heat Pump Field Wiring Auxiliary Heater 1 Field Wiring Ground Field Wiring Ground Lug Auxiliary Heater 2 Field Wiring Auxiliary Heater 2 Auxiliary Heater 1 Heat Pump Line Voltage And Ground Connections 3 ThermostatMountingAndWiring A ThermostatLocation Locate the thermostat about 5 ft above the floor in an area with good circulation a...

Page 14: ...s The condensate line must have a minimum drop of 1 4 per running foot as it leaves the unit When a horizontal run of 15 ft or longer is required it may be necessary to install a vent tee in the drain line near the unit or use a larger diameter drain line This is to eliminate air trapping and allow proper condensate drainage Heatpumpsgeneratecondensateduringbothcoolingand heatingmodes Condensatedr...

Page 15: ...re variations within the home Dehumidification Duringthecoolingseason theVert I Pakalsodehumidifiesthe air in the home while is it cooling the air After a few minutes of operation water should run freely from the condensate drain line extended to the outside of your home If condensate is not runningfromthedrainline checktobesurethatthedrainhose or pipe is properly connected to the drain fitting locat...

Page 16: ...onsforcontrollingtheindoor air blower AUTO and ON When the FAN control is set to AUTO the blower will operate only while the thermostat operates the cooling or heating equipment When the FAN control is set to ON the blower will operate continuously regardless of whethercoolingorheatingequipmentisoperating Thissetting allows for continuous air circulation and filtration SystemControl The SYSTEM or M...

Page 17: ... dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replaced as it becomes dirty To replace the filter front air return units 1 Slide the filter to the right until it clears the filter rails See Figure 12 2 Remove the filter 3 Install new disposable filter CAUTION Do not operate your system without a filter in place nor block the front of the unit return air o...

Page 18: ...18 920 164 02 10 04 ...

Page 19: ...19 920 164 02 10 04 ...

Page 20: ...tory Certified Parts FRIEDRICH AIR CONDITIONING CO INC Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in the U S A ...

Reviews: