background image

14

920-159-03

Error

Code Code Translation

Action Taken by Unit

Possible Cause

0 2

An extreme low voltage condition 

exists <198V for 230V units and 

<239V for 265V units. 

Shut down unit.  Display Error code and 

flash. Once voltage rises to normal level 

system power is restored.

• Inadequate power supply

• Defective breaker

• Blown fuse

0 3

Return air thermistor sensor open or 

short circuit

Set return air sensor = 75°F.  Alternately flash 

set point and error code.  Leave unit running.

• Defective sensor

0 4

Indoor coil thermistor sensor open 

or short circuit

Set ID coil temp = 40°F.  Alternately flash set 

point and error code.  Leave unit running.

• Defective sensor

0 5

Outdoor coil thermistor sensor open 

Or short circuit

Set OD coil temp = 20°F.  Alternately flash 

set point and error code.  Automatically 

change over to Electric heat Mode only.  

Leave unit running.

• Defective sensor

0 6

If O.D. coil Temperature > 175 Deg 

F for 2 consecutive minutes.  (Heat 

Pump models only)

Alternately flash set point and error code.  

Shut unit down for 5 minutes, then try again 

 

2 times. If it fails the 3rd time, shut down unit 

to prevent high head pressure.

• Dirty coil

• Fan motor failure

• Restricted air flow

• Non-condensables in

 

  refrigeration system

0 7

I.D coil temperature <30 Deg F for 2 

consecutive minutes.

Alternately flash set point and error code.  

Continue fan operation while the compressor 

is locked out until the indoor coil thermistor 

reaches 45° F, then energize the compres

-

sor.  However, compressor must still wait a 

lockout time of 180 to 240 seconds.

• Dirty filters

• Dirty coil

• Fan motor failure

• Restricted airflow

• Improper refrigerant charge

• Restriction in refrigerant circuit

0 8

Unit cycles (Heat or Cool demand) 

> 9 times per hour

Store error code in memory.

Keep unit running

• Unit oversized

• Low load conditions

0 9

Unit cycles (Heat or Cool demand) 

< 3 times per hour

Store Error Code in memory.

Keep unit running

• Unit undersized

• High load conditions

1 0

Room Freeze Protection triggered

Alternately flash set point and error code.  

Keep unit running.

• Room temperature fell below     

   40°F

1 1

No Signal to “GL or “GH” terminal 

(Remote Thermostat mode only)

Shut down unit. Display error code and flash.

• Defective remote thermostat

• Defective thermostat wiring

1 3

If Pressure limit switch opens

Turn OFF compressor. Alternate flash set 

point and error code

 

Factory Dip Switch Configuration

1 2 3 4 5 6 7 8

O

N

Error Codes

The chart below lists the possible error codes and their description:

Summary of Contents for VEA24K25 Series

Page 1: ...920 159 03 11 07 VERT I PAK A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONINGSYSTEM 24 000 BTU h INSTALLATION OPERATION GUIDE...

Page 2: ...ectrical and Thermostat Wiring Diagrams 11 Chassis Operation Fresh Air Door 12 Low Ambient Protection 12 Room Freeze Protection 12 Emergency Heat Override 12 Emergency Heat Operation 12 Service Servic...

Page 3: ...louver should be maintained For major obstructions such as a solid fence wall or other heat rejecting device like a condensing unit a mini mum distance of 72 should be kept 12 24 60 VPAK VPAK VPAK POL...

Page 4: ...I Pak Chassis Specifications Voltage V 230 208 Refrigerant R 22 Chassis Width 23 125 Chassis Depth 23 125 Chassis Height 47 25 Supply Duct Collar 10 Drain Connection 3 4 FPT Min Circuit Amps See Namep...

Page 5: ...grounded Wire Sizing Use recommended wire size given in tables and install a single branch circuit All wiring must comply with local and national codes NOTE Use copper conductors only CAUTION Electric...

Page 6: ...ions 24 5 8 wide x 30 7 8 high VPRG4 Access Panel cutout dimensions 27 wide by 55 3 4 high See Figure 8 Page 10 for proper chassis installation Figure 3 Typical Utility Closet Chassis Shown in Closet...

Page 7: ...ide wall plenum Part A Inside Wall Plenum Part B Wall Plenum Outdoor Louver Installation Rough opening dimension 24 5 8 wide x 30 7 8 high Ensure that the bottom of the plenum is 1 1 2 from the floor...

Page 8: ...tedrainsystemmustbeconnected to one of the two 3 4 FPT connections 3 The remaining connection must be plugged using the 3 4 pipe plug provided and field suppled teflon tape or pipe joint compound 4 Fa...

Page 9: ...the condensate exit location Be sure to use teflon tape or approved pipe sealant on all drain connections and plugs see page 8 C Place the chassis into the closet with the outdoor side facing the wall...

Page 10: ...n the wires through the side hole in the box and under the control components in the box to reach the connection terminal for the wiring 4 Make the wire connections appropriately matching the wires as...

Page 11: ...03 NOTE THE DIAGRAM ABOVE ILLUSTRATES THE TYPICAL THERMOSTAT WIRING SEE THE UNIT CONTROL PANEL FOR THE ACTUAL UNIT WIRING DIAGRAM AND SCHEMATIC CONNECTION TERMINAL Electrical Thermostat Wiring Diagram...

Page 12: ...h Air Door is an intake system The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil Move the slide left to open and right to close the fresh air door...

Page 13: ...heefficiencyofyourVert I Pakandallows lint and dirt to accumulate on the indoor air coil Lint and dirt on the indoor air coil can damage your unit and void the warranty The air filter should be replac...

Page 14: ...coil Fan motor failure Restricted air flow Non condensables in refrigeration system 07 I D coil temperature 30 Deg F for 2 consecutive minutes Alternately flash set point and error code Continue fan o...

Page 15: ...pecial color to match the exterior wall ARCHITECTURAL LOUVER Extruded aluminum louver that attaches to the outdoor section of the wall plenum DIMENSIONS 31 1 16 high x 25 9 16 wide Same as VPAWP1 8 bu...

Page 16: ...n contact the Friedrich Air Conditioning Company International Division Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part Reasonable proof must...

Reviews: