background image

8

9

920-138-02 (3-04)

920-138-02 (3-04)

MODEL

Flange outward

MODEL

Flange inward

OES/OHS18&24

36.9

OES/OHS18&24

33.9

OES/OHS30&36

41.9

OES/OHS30&36

38.9

OES/OHS42,48&60

43.9

OES/OHS42,48&60

40.8

MOUNTING THE UNIT

Mounting Information

Two holes must be cut in the wall for the supply and return air 

openings. (See Figures 7 and 8)
On wood frame walls, the wall may need to be reinforced in 

order to hold up to the weight of the unit.
Concrete block walls must be thoroughly inspected to insure 

that they can handle the unit weight.
It is the installer's responsibility to insure that hardware used 

for mountng of unit is correct for wall material. 

New Installation

OES/OHS  units  are  affixed  to  the  wall  by  way  of  three 

mounting brackets. The bottom bracket supports the majority 

of the weight load, and the side brackets hold the unit in place 

(See Figures 6 and 7).
Friedrich recommends a 1 inch clearance to combustible 

material for the first 3 feet of duct attached to the outlet air 

frame.

1.  

Locate and mark lag bolt locations and bottom 

mounting bracket location. (See Figure 8)

2.  

Mount bottom mounting bracket.

3.  

Connect the side mounting brackets to the rear 

corner posts of the unit. Brackets may be mounted 

with flanges outward or inward. See Figure 6 

for dimensions for new installation. Friedrich 

recommends installing the brackets outward.

4.  

Connect the rain flashing to the back flange of the 

unit top by using screws in the top panel. Top rain 

flashing is shipped secured to the back of the unit. 

(See Figure 9)

5.  

Position the unit in the opening and secure to the 

wall with 5/16 inch lag bolts; use 7/8 inch diameter 

flat washers on the lag bolts.

6.  

Secure the rain flashing to the exterior wall and caulk 

across the entire length of the top. (See Figure 9)

7.  

On side by side installations, maintain a minimum 

of 20 inches clearance on both sides to allow 

access to heat strips and to allow proper airflow 

out of the outdoor coil. Additional clearance may 

be required to meet local or national codes.

Replacement Installation

Friedrich  mounting  brackets  are  removable  and  can  be 

mounted in two ways to ensure the bracket holes are in line 

with the studs. (See Figure 6)
When  doing  a  replacement  project  measure  the  space 

between the studs, then look at the chart below, which gives 

the space between mounting brackets for all chassis sizes. 

Decide in which position the brackets should be mounted 

to best match the stud spacing. If the unit is to be installed 

with  the brackets facing outwards, (Figure 6) first mount the 

brackets onto the unit and then secure to the wall. If the unit 

is to be installed with the brackets facing inwards (Figure 

6), first mount brackets to the wall, then position the unit up 

against the wall and secure brackets to the unit.

Flanges Inward

Mount flanges to wall first

Flange Inward

Flanges Outward

Mount flanges to chassis first

Flange Outward

Figure 6

Mounting Options

Summary of Contents for OES Series

Page 1: ...Wall Mount Outdoor Wall mounted Air Conditioners Heat Pumps OES OHS Series 920 138 02 3 04 Installation Operation Manual...

Page 2: ...Model Information Form 19 Warranty Information 20 21 TABLE OF CONTENTS Please read this manual thoroughly prior to equipment installation or operation It is the installer s responsibility to properly...

Page 3: ...208 230V 1 PH 60HZ Chassis Color X Alaskan Beige standard Future Revision Digit Figure 2 Unit Dimensions MODEL DIMENSIONS A B C D E F G H I J K L M N O P Q R S T OES OHS18 24 36 9 20 0 6 2 7 9 20 1 2...

Page 4: ...0B for special installation requirements Recognize safety information This is the safety alert symbol When you see this symbol on the unit or in instructions and manuals be alert to the potential for...

Page 5: ...external static pressures The supply and return air duct system pressure losses including filter louver grille and registers must not exceed the listed external static pressures for the indoor air sys...

Page 6: ...filters monthly Replace disposable type filters before they become clogged Use water and mild detergent to clean washable type filters NOTE Most filters are marked with an arrow to indicate the proper...

Page 7: ...o the rear of the cabinet See Figure 5 Repeat the above steps for each of the eight perforated metal flanges on the rear of the cabinet When completed there will be eight duct flanges that are perpend...

Page 8: ...in flashing to the back flange of the unit top by using screws in the top panel Top rain flashing is shipped secured to the back of the unit See Figure 9 5 Position the unit in the opening and secure...

Page 9: ...may be required for some walls Framing Material 2 x 4 s 2 x 6 s and or structural steel See Unit Dimensions Figure 2 for duct dimensions See Unit Dimensions Figure 2 for actual dimensions SUPPLY AIR O...

Page 10: ...g its entire length Top Front of unit Wall Structure SUPPLY AIR DUCT RETURN AIR DUCT NOTE It is recommended that a bead of silicone be placed behind the side mounting flanges and under the top flashin...

Page 11: ...d local codes national electric code and NFPA 70 Unit and controls will NOT operate unless properly grounded A ground lug is provided for ground connection Use only approved copper wire and connectors...

Page 12: ...A 30 N A 10 N A 10 N A 19 9 30 10 10 05 2 230 208 60 1 198 253 19 9 26 0 30 30 10 10 10 10 28 30 10 10 08 2 230 208 60 1 198 253 19 9 39 0 30 40 10 8 10 10 41 50 6 10 10 2 230 208 60 1 198 253 19 9 52...

Page 13: ...30 8 10 10 10 51 60 6 10 08 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10 64 70 4 8 10 2 230 208 60 1 198 253 22 8 52 0 40 60 8 6 10 10 77 80 4 8 15 2 230 208 60 1 198 253 22 8 39 0 40 40 8 8 10 10...

Page 14: ...Fully closed halfway open and fully open Fully open provides 15 of rated airflow of outside air The damper position is fixed Adjustment 1 Remove louvered panel from unit See Figure 11 2 Remove one 1...

Page 15: ...aneltogainaccesstothedampermotorcontrol Adjust the thumb wheel on the back of the motor to achieve desired set point Figure 13 Commerical Room Ventilator Components Thumbwheel Fresh Air Damper Shaft E...

Page 16: ...ns closed and energizes the compressor for cooing operation Adjustment 1 1 2 5 Ton Chassis 1 Step 1 2 for 1 1 2 3 ton models only Through the return air opening remove two 2 screws on the access cover...

Page 17: ...is not required to be mixed with conditioned air Units with vent packages have louvered front panels to allow for air intake Units without ventilation packages have a BOP blank off plate instead of a...

Page 18: ...cuit breakers inside unit are ON 2 Check to see if all duct work is sealed to unit for an airtight fit 3 Thermostat is level and properly installed Heat anticipator indicator is set to the correct set...

Page 19: ...L MOUNT MODEL WALL MOUNT SERIAL IF WALL MOUNT WAS PURCHASED INSTALLED IN A MANUFACTURED STRUCTURE DATE OF PURCHASE DEALER NAME DEALER PHONE DEALER FAX DEALER ADDRESS DEALER CITY STATE ZIP MANUFACTURER...

Page 20: ...da This limited warranty applies only if the unit is installed and operated in accordance with FRIEDRICH instructions and in compliance with applicable local installation and building codes and good t...

Page 21: ...stributor 4 This limited warranty applies only to units remaining at the site of the original installation except for mobile home installations and only to units installed within the continental Unite...

Page 22: ...22 920 138 02 3 04...

Page 23: ...23 920 138 02 3 04...

Page 24: ...2 3 04 FRIEDRICH AIR CONDITIONING CO Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in...

Reviews: