42
22 – AUTOMATIC HUMIDITY CONTROL
†
00
Disable automatic humidity control;
01 *
Enable automatic humidity control;
When “Automatic Humidity Control” is enabled, thermostat will turn on
air conditioning in an unoccupied room when humidity raises above
60% and room temperature is above 72°F until either room humidity
is below 55% or room temperature is below 72°F;
*
Indicates default setting;
†
This setting is active only on thermostats with enabled humidity
features. Changing this setting on a non-humidity thermostat will have
no effect on thermostat operation.
Humidity features can be enabled on compatible thermostats via
remote management.
Certain models only. Additional fees apply.
Custom Energy Savings Settings