background image

9

coolinG onlY room air conditionerS: troUBleSHootinG tiPS 

 

 

n

o

it

c

A

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

Compressor runs

  

for short periods

  

only. Cycles on 

overload

Overload inoperative. Opens too

soon

 Check operation of unit. Replace overload if
 system operation is satisfactory 

Compressor restarted before 
system pressures equalized 

 

Allow a minimum of 2 minutes to allow 

 pressures to equalize before attempting to 
 restart. Instruct customer of waiting period 

Low or 

 uctuating voltage 

 Check voltage with unit operating. Check for
 other appliances on circuit. 

Air conditioner  

 should be in separate circuit for proper voltage

  

 & fused separately 

Incorrect wiring 

 Refer to appropriate wiring diagram 

Shorted or incorrect capacitor 

 Check by substituting a known good capacitor

  

 of correct rating 

Restricted or low air 

 

ow through 

condenser coil or evaporator coil 

 Check for proper fan speed or blocked

 coils 

Compressor running abnormally 

hot

 Check for kinked discharge line or restricted

 condenser

. Check amperage 

 

n

o

it

c

A

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

T

-stat does not 

turn unit on 

Loss of charge in t-stat bulb 

 Place jumper across t-stat terminals to check if

  

 unit operates. If unit operates, replace t-stat. 

Loose or broken parts in t-stat 

 Check as above 

Incorrect wiring 

 Refer to appropriate wiring diagram 

Defective thermistor

 Replace thermistor or electronic control board

 

n

o

it

c

A

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

Noisy operation 

Poorly installed

 Refer to Installation Manual for proper

 installation 

Fan blade striking chassis 

 Reposition - adjust motor mount 

Compressor vibrating 

 Check that compressor grommets have not 
 deteriorated. Check that compressor mounting 
 parts are not missing 

Improperly mounted or loose
cabinet parts 

 Check assembly & parts for looseness,
 rubbing & rattling 

 

n

o

it

c

A

 

 

e

s

u

a

C

 

e

l

b

i

s

s

o

P

 

 

m

e

l

b

o

r

P

W

ater leaks into

  

the room 

Evaporator drain pan over

 

owing 

  Clean obstructed drain trough 

Condensation forming on base pan 

 Evaporator drain pan broken or cracked.

 Reseal or replace. No chassis gasket installed.

 Install chassis gasket

Poor installation resulting in rain 
entering the room 

 Check installation instructions. Reseal as
 required 

Condensation on discharge grille 
louvers

 Dirty evaporator coil. Use pressure wash

 or biodegradable cleaning agent to clean.

 Environmental phenomena: point supply 

 louvers upward

Chassis gasket not installed

  

Install gasket, per Installation manual 

Downward slope of unit is too
steep inward

 Refer to installation manual for proper

 installation 

Summary of Contents for CP15F10

Page 1: ...Compact Programmable CP 15 18 24 ServParts 05 10 Model 2010 Service Parts Manual R410A Models ...

Page 2: ... Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 877 599 5665 x 846 FAX 210 357 4490 Email tac friedrich com www friedrich com Printed in the U S A TECHNICAL SUPPORT CONTACT INFORMATION ...

Page 3: ...pecifications 4 How to Operate the Air Conditioner with Remote Control 5 Method of Charging Repairs 6 Compressor Replacement 7 Troubleshooting 8 10 Wiring Diagrams for 2010 Model 11 Exploded View of Parts for 2010 Model 12 Parts for 2010 Models 13 14 Warranty 15 ...

Page 4: ...Jul K Oct B Feb E May H Aug L Nov C Mar F Jun J Sept M Dec 3rd and 4th Digit Approximate BTU HR Cooling Heating BTU Hr capacity listed in the Specification Performance Data Section 7th Digit Options 0 Straight Cool Heat Pump Models 6th Digit Voltage 1 115 Volts 3 230 208 Volts 5th Digit Alphabetical Modifier COMPACT PROGRAMMABLE Model Number Code C P 15 F 1 0 RAC Serial Number Identification Guide...

Page 5: ... electrical ratings on unit s rating plate Proper circuit protection is the responsibiity of the homeowner Grounding Unit MUST be grounded from branch circuit through service cord to unit or through separate ground wire provided on permanently connected units Be sure that branch circuit or general purpose outlet is grounded Ground wire must be connected to ground screw located in lower right corne...

Page 6: ...lary Capillary Starting Method Working Temp Range 64 110 64 110 64 110 Condenser Aluminum fin copper Aluminum fin copper Aluminum fin copper Pipe Diameter inch Rows Fin Gap inch 2 1 20 2 1 20 2 1 20 Coil length l xheight H xcoil width 27 7 X15 75 X 1 34 X15 75X 34X15 75X1 Fan Type Piece Axial fan 1 Axial fan 1 Axial fan 1 Fan Diameter inch 15 6 15 6 15 6 Sound Pressure Level dB A H M L 61 60 58 61...

Page 7: ...panel will flash 2 Press the plus or minus button to change the delay time from 1 to 24 hours 3 Press TIMER again or wait 10 seconds Indicator light on air conditioner control panel will remain on To set Timer to turn onair conditioner keepingprevious settings 1 Turn off air conditioner 2 Press TIMER Indicator light on air conditioner control panel will flash 3 Press the plus or minus button to ch...

Page 8: ...RD FREEZE HAZARD Proper safety procedures must be followed and proper protective clothing must be worn when working with a torch Failure to follow these procedures could result in moderate or serious injury WARNING BURN HAZARD Method Of Charging Repairs The acceptable method for charging the RAC system is the Weighed in Charge Method The weighed in charge method is applicable to all units It is th...

Page 9: ...w slight the system will need to be cleaned up following proper procedures 7 Install the replacement compressor 8 Pressurize with nitrogen and leak test all connections with an electronic or Halide leak detector Recover refrigerant and repair any leaks found Repeat Step 8 to insure no more leaks are present Unplug and or disconnect all electrical power to the unit before performing inspections mai...

Page 10: ...ce coil check for leak Inoperative fan motor Test fan motor replace if inoperative Partially restricted capillary tube De ice coil Check temp differential delta T across coil Touch test coil return bends for same temp Test for low running current n o i t c A e s u a C e l b i s s o P m e l b o r P Compressor runs continually does not cycle off Excessive heat load Unit undersized Test cooling perfo...

Page 11: ...ck if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Defective thermistor Replace thermistor or electronic control board n o i t c A e s u a C e l b i s s o P m e l b o r P Noisy operation Poorly installed Refer to Installation Manual for proper installation Fan blade striking chassis Reposition adju...

Page 12: ...g structure particularly floors Advise customer n o i t c A e s u a C e l b i s s o P m e l b o r P Thermistor short cycles Defective thermistor Replace thermistor or electronic control board Plenum gasket not sealing allowing discharge air to short cycle unit Check gasket Reposition or replace as needed Restricted coil or dirty filter Clean advise customer of periodic cleaning maintenance needs of ...

Page 13: ...11 ELECTRONIC CONTROL WIRING DIAGRAM 2010 MODEL CP15F10 CP18F30 CP24F30 ...

Page 14: ...EXPLODED VIEW AND LIST OF PARTS 2010 MODEL CP15F10 CP18F30 AND CP24F30 12 ...

Page 15: ... r e v u o L e d i u G 2 6 67700230 63 Filter 1 67700231 4 1 r e v u o L e d i u G 4 6 67700232 65 Front Case 1 67700233 66 Front Panel 1 67700234 1 l e n a P w o d n i W S A 7 6 67700235 1 l e n a P r e v o C e t o m e R 8 6 67700236 1 s i s s a h c n a p e s a B 9 6 67700296 1 r e x i F s i s s a h C 0 7 67700105 71 Remote Control 1 67700171 1 Supporter Assy 1 67700132 2 Self threading Screw ST4...

Page 16: ... L g n i w S 1 3 67700124 1 r e v u o L g n i w S r o t o M 2 3 67700133 1 s i x A l a n o i t c e l f n I 3 3 67700121 1 t r o p p u S g n i w S 4 3 67700125 1 r o o D r i A h s e r F 5 3 67700212 1 l e e h W r e w o l B 6 3 67700243 1 d r a o b p a l c e c i f i r O 7 3 67700108 67700106 1 y s s A r o t a r o p a v E 9 3 67700266 1 r e d l o H r o s n e S 0 4 67700213 67700290 67700293 3 8 M r e...

Page 17: ...allation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood alterations and or misapplication of the product and or units installed in a corrosive atmosphere default or delay in performance caused by war government restrictions or restraints strikes material shortages beyond the control of FRIEDRICH or acts of God OBTAINING WARRANTY PERFORMANC...

Reviews: