background image

9

EQUIPMENT REQUIRED

 1.  Voltmeter

 2.  Ammeter

 3.  Ohmmeter 

  4. 

E.P.A. Approved Refrigerant Recovery System.

  5. 

Vacuum Pump (capable of 200 microns or less vacuum.)

 6.  Acetylene Welder

  7. 

Electronic Halogen Leak Detector (G.E. Type H-6 or 

equivalent.)

  8. 

Accurate refrigerant charge measuring device such as:

 

 

a. Balance Scales - 1/2 oz. accuracy

 

 

b. Charging Board - 1/2 oz. accuracy

  9. 

High Pressure Gauge - (0 - 400 lbs.)

 10. 

Low Pressure Gauge - (30 - 150 lbs.)

 11. 

Vacuum Gauge - (0 - 1000 microns)

EQUIPMENT MUST BE CAPABLE OF:

  1. 

Recovery CFC’s as low as 5%.

  2. 

Evacuation from both the high side and low side of the 

system simultaneously.

  3. 

Introducing refrigerant charge into high side of the 

system.

  4. 

Accurately weighing the refrigerant charge actually 

introduced into the system.

 5.  Facilities for fl owing nitrogen through refrigeration tubing 

during all brazing processes.

HERMETIC COMPONENT REPLACEMENT

The following procedure applies when replacing components 

in the sealed refrigeration circuit or repairing  refrigerant leaks. 

(Compressor, condenser, evaporator, capillary tube, refrigerant 

leaks, etc.)

  1. 

Recover the refrigerant from the system at the process 

tube located on the high side of the system by installing a 
line tap on the process tube. Apply gauge from process 
tube to EPA approved  gauges from process tube to EPA 

approved recovery system. Recover CFC’s in system to at 

least 5%.

  2. 

Cut the process tube below pinch off on the suction side 

of the compressor.

  3. 

Connect the line from the nitrogen tank to the suction 

process tube.

  4. 

Drift dry nitrogen through the system and un-solder the 

more distant connection fi rst. (Filter drier, high side process 
tube, etc.)

  5. 

Replace inoperative component, and always install a new 

fi lter drier. Drift dry nitrogen through the system when 
making these connections.

 

HERMETIC COMPONENT REPLACEMENT cont’d

  6. 

Pressurize system to 30 PSIG with proper refrigerant and boost 

refrigerant pressure to 150 PSIG with dry nitrogen.

  7. 

Leak  test  complete  system  with  electric  halogen  leak 

detector, correcting any leaks found.

  8. 

Reduce the system to zero gauge pressure.

  9. 

Connect vacuum pump to high side and low side of system 

with deep vacuum hoses, or copper tubing. (Do not use 
regular hoses.)

 10. 

Evacuate system to maximum absolute holding pressure 

of 200 microns or less. NOTE:  This process can be 
accelerated  by  use  of  heat  lamps,  or  by  breaking  the 
vacuum with refrigerant or dry nitrogen at 5,000 microns. 
Pressure system to 5 PSIG and leave in system a 
minimum of 10 minutes. Release refrigerant, and proceed 
with evacuation of a pressure of 200 microns or less.

 11. 

Break vacuum by charging system from the high side with 

the correct amount of liquid refrigerant specifi ed. This will 
prevent boiling the oil out of the crankcase, and damage 
to the compressor due to over heating.

NOTE:

  If the entire charge will not enter the high side, allow the 

remainder to enter the low side in small increments while operating 
the unit.

12.   

Restart unit several times after allowing pressures to stabilize. 

Pinch off process tubes, cut and solder the ends. Remove 
pinch off tool, and leak check the process tube ends.

SPECIAL PROCEDURE IN THE CASE OF COMPRESSOR 
MOTOR BURNOUT

  1. 

Recover all refrigerant and oil from the system.

  2. 

Remove compressor, capillary tube and fi lter drier from the 

system.

  3. 

Flush evaporator condenser and all connecting tubing with 

dry nitrogen or equivalent, to remove all contamination 
from system. Inspect suction and discharge line for carbon 
deposits. Remove and clean if necessary.

  4. 

Reassemble the system, including new drier strainer and 

capillary tube.

  5. 

Proceed with processing as outlined under hermetic 

component replacement.

ROTARY COMPRESSOR SPECIAL  TROUBLESHOOTING 

AND SERVICE

Basically, troubleshooting and servicing rotary compressors 
is the same as on the reciprocating compressor with only one 
main exception:

NEVER, under any circumstances, charge a rotary compressor 
through the LOW side. Doing so would cause permanent damage 
to the new compressor.

IMPORTANT

ANY SEALED SYSTEM REPAIRS TO COOL-ONLY MODELS REQUIRE THE INSTALLATION OF A LIQUID LINE DRIER.  

ALSO, ANY SEALED SYSTEM REPAIRS TO HEAT PUMP MODELS REQUIRE THE INSTALLATION OF A SUCTION LINE DRIER.

Sealed Refrigeration System Repairs

Summary of Contents for CP14-18-24 CP14N10

Page 1: ...Service Parts Manual 2007 Compact Programmable Models CP14N10 CP18N30 CP24N30 CP 14 18 24 Svc Prts 07 3 07...

Page 2: ...ion and repair and who is equipped with the proper tools and test instruments Installation or repairs made by unqualified persons can result in hazards subjecting the unqualified person making such re...

Page 3: ...15 59 15 59 15 59 Fan Motor Speed rpm H M L 900 780 730 900 780 730 1000 900 800 Output of Fan Motor W 200 200 190 Fan Motor RLA A 3 1 45 1 35 Fan Motor Capacitor uF 15 MFD 7 MFD 7 MFD Permissible Exc...

Page 4: ...4 Outer Component Identification Models CP14N10 CP18N30 CP24N30 Cabinet Air inlet louver Front grille Power cord Control panel cover Front intake grille Air filter behind front intake grille...

Page 5: ...5 Installation Dimensions Models CP14N10 CP18N30 CP24N30 Top View Fence obstruction Over 2 Over 1 Over 1 Wall Or window Front View Side View Ceiling Over 1 Over 1 25 98 16 85 Less than 8 66 Over 2...

Page 6: ...6 CP24N30 CP18N30 CP14N10 Wiring Diagrams...

Page 7: ...OMPONENTS Thermostat Used to maintain the specified room side comfort level Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan...

Page 8: ...consuming if not in some cases entirelyimpossible Therefrigerationsystemusesfourbasic principles laws in its operation they are as follows 1 Heat always flows from a warmer body to a cooler body 2 Hea...

Page 9: ...leaks found 8 Reduce the system to zero gauge pressure 9 Connect vacuum pump to high side and low side of system with deep vacuum hoses or copper tubing Do not use regular hoses 10 Evacuate system to...

Page 10: ...pressor eventually causing a mechanical failure within the compressor This mechanical failure can manifest itself as valve failure bearing failure and or other mechanical failure The specific type of...

Page 11: ...10 to 15 minutes check the gauge pressures Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures UNDERCHARGED REFRIGERANT SYSTEMS NOTE He...

Page 12: ...considerably less than normal as the compressor is running in a deep vacuum no load Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be stored...

Page 13: ...perative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed switch open Test switch replace if inoperative Inoperative f...

Page 14: ...emp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does not cycle off Excessive heat...

Page 15: ...stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram Problem Possible Cause Acti...

Page 16: ...ntial too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty filter Clean advise custome...

Page 17: ...ontacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bulb removed from or not making good coil contact Reinstal...

Page 18: ...h Problem Possible Cause Action Cooling adequate but heating insufficient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating capillary tube Check valve...

Page 19: ...19 Components Model CP14N10...

Page 20: ...67700205 15 Washer 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700207 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700...

Page 21: ...10 120V 1 67700220 50 Transformer 41X26 5C 1 67700221 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700222 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 5...

Page 22: ...7700150 15 Washer 4 1 67700158 16 Self threading Screw ST4 2x22 6 67700153 17 Top Rail 1 67700134 18 Self threading Screw with Gasket ST4X10 4 67700152 19 Condenser Assy 1 67700104 20 Nut with Washer...

Page 23: ...200V 240V TUV 1 67700147 50 Power Transformer 41X26 5F 1 67700146 51 Capacitor Clamp 1 67700114 52 Electric box 1 67700136 53 Main PCB J25713J 1 67700142 54 Fixed Clamp 1 67700160 55 Power cord 1 677...

Page 24: ...24 Components Model CP24N30...

Page 25: ...er 4 1 67700158 16 Screw ST4 2X22 4 67700153 17 Top Rail Assy 1 67700206 18 Screw ST4X10 4 67700152 19 Condenser Assy 1 67700239 20 Nut with Washer M10 1 67700157 21 Washer 10 1 67700159 22 Fan Blade...

Page 26: ...ransformer 41X26 5C 1 67700247 51 Capacitor clamp 1 67700114 52 Main PCB M2A91J 1 67700248 53 Electric box 1 67700136 54 Isolation Washer D 1 67700223 55 Wire Clamp 1 67700160 56 Power cord 1 67700249...

Page 27: ...been removed 3 Products which have defects or damage which results from improper installation wiring electrical current characteristics or maintenance or caused by accident misuse or abuse fire flood...

Page 28: ...Prts 07 3 07 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Print...

Reviews: